4179

 

Universal AC / DC transmitter

 

  • Measures AC current and voltage signals
  • Outputs passive or active current signals
  • Programming, process monitoring and diagnostics via 4511 / 4501
  • Response time < 0.75 s and excellent accuracy better than 0.3%
  • Universally powered by 21.6…253 VAC / 19.2...300 VDC
  1. Overview

  2. Technical details

  3. Accessories


Application

  • The 0...5 AAC RMS range makes it possible to accurately measure a typical current transformer.
  • The 0...300 VAC RMS range allows accurate supply voltage monitoring.
  • The 4179 measures standard input ranges, and can be freely configured to customer-defined input range.
  • Converts narrow AC current / voltage inputs to wide bipolar or unipolar outputs, e.g. 0...1 VAMS input = ±10 volt or 4...20 mA output with a minimum span of 0.5 AAC RMS or 0.5 VAC RMS.
  • Configurable input limits control the output value for increased safety.

Technical characteristic

  • The latest analog and digital techniques are used to obtain maximum accuracy and immunity to interference.
  • Possibility of output safety feedback by selecting S4...20 mA output.
  • The current output can drive up to 800 Ohms, with an adjustable response time of 0.0…60.0 seconds.
  • Exceptional mA output load stability of <0.001% of span / 100 Ohm.
  • Meets the NAMUR NE21 recommendations, ensuring high accuracy in harsh EMC environments.
  • Meets the NAMUR NE43 recommendations, allowing the control system to easily detect an input error.
  • Each unit is tested to a high 2.3 kVAC, 3-port galvanic isolation level.
  • Excellent signal to noise ratio of > 60 dB.

Mounting / installation / programming

  • Very low power consumption means units can be mounted side by side without an air gap – even at 60°C ambient temperature.
  • Configuration, monitoring, 2-point process calibration and more are accomplished using either the 4501 detachable display or the 4511 detachable digital communication enabler.
  • All programming can be password-protected.

Manuals


Data sheet


Declaration of Conformity


Safety note


Modbus configuration manual


PPS manual


4801 Gateway manual


Russian manual


UL certificate


Environmental Conditions

Operating temperature -20°C to +60°C
Storage temperature -20°C to +85°C
Calibration temperature 20...28°C
Relative humidity < 95% RH (non-cond.)
Protection degree IP20
Installation in Pollution degree 2 & measurement / overvoltage cat. II

Mechanical specifications

Dimensions (HxWxD) 109 x 23.5 x 104 mm
Dimensions (HxWxD) w/ 4501 / 4511 109 x 23.5 x 116 / 131 mm
Weight approx. 250 g
Weight incl. 4501 / 4511 (approx.) 285 g / 350 g
DIN rail type DIN EN 60715/35 mm
Wire size 0.13...2.08 mm2 AWG 26...14 stranded wire
Screw terminal torque 0.5 Nm
Vibration IEC 60068-2-6
2...13.2 Hz ±1 mm
13.2...100 Hz ±0.7 g

Common specifications

Supply

Supply voltage, universal 21.6...253 VAC, 50...60 Hz or 19.2...300 VDC
Max. required power ≤ 1.8 W nom.
Internal power dissipation ≤ 2.5 W

Isolation voltage

Test voltage 2.3 kVAC
Working voltage 250 VAC (reinforced) / 500 VAC (basic)

Response time

Response time (0...90%, 100...10%) < 0.75 s
Programming Communication enabler 4511 / Programming front 4501
Signal dynamics, input 20 bit
Signal dynamics, output 18 bit
Signal / noise ratio > 60 dB
Output referred common mode rejection ratio 0.02 ppm / VHz
Accuracy Better than 0.3% of selected range*
EMC immunity influence < ±0.5% of span*
Extended EMC immunity: NAMUR NE21, A criterion, burst < ±1% of span*
of span = of selected standard range

Input specifications

Current input

Signal range 0...5 AAC / 40...400 Hz
Maximum input limit 6.00 AAC @ 40°C
Programmable measurement ranges 0...0.5; 0…1; 0…2.5 & 0...5 AAC
Custom configurable signal range 0...5 AAC /40...400 Hz
Min. measurement range (span) 0.5 AAC
Input resistance Nom. < 0.07 Ω

Voltage input

Signal range 0...300 VAC / 40...400 Hz
Programmable measurement ranges 0...0.5, 0...1, 0...2.83, 0…5, 0…120, 0…230 & 0…300 VAC
Custom configurable signal range 0...300 VAC / 40...400 Hz
Min. measurement range (span) 0.5 VAC
Input resistance Nom. 3 MΩ || 100 pF

Output specifications

Active unipolar and bipolar mA output

Programmable ranges 0...20, 4...20 and S4...20 mA ±10 and ±20 mA
Direct or Inverted Action
Load (@ current output) ≤ 800 Ω
V-curve function, active signals, 100-0-100% 20-0-20 mA

Passive 2-wire mA output

Programmable ranges 0...20 and 4...20 mA Direct or Inverted action
V-curve function, 100-0-100% 20-0-20 mA
External loop supply 3.5...30 V

Current output

Signal range 0...23 mA (unipolar) -23...+23 mA (bipolar)
Current limit ≤ 28 mA (unipolar) ± 28 mA (bipolar)
Load stability ≤ 0.001% of span / 100 Ω
Response time, programmable 0.0...60.0 s

Voltage output

Programmable signal ranges 0/0.2...1; 0/1...5 ; 0/2...10; 1...0.2/0; 5...1/0; 10...2/0 V ±1, ±5 and ±10 V
Direct or Inverted action
V-curve function, 100-0-100% 1-0-1, 5-0-5 and 10-0-10 V
Load (@ voltage output) ≥ 500 kΩ
Response time, programmable 0.0...60.0 s

Observed authority requirements

EMC 2014/30/EU
LVD 2014/35/EU
RoHS 2011/65/EU

Approvals

UL UL 508 / C22.2 no. 14

NB

* / ** For custom configurable signal ranges, general accuracy and EMC specifications are 0.3% of full scale
Your request has been sent successfully. - 0 Items on your list
Product description Quantity
Please specify variant(s) (see data sheet) - or indicate ‘Variant unknown’
Your contact information
Continue browsing
No products added
You have no products on your list...

When browsing product pages on this website, you have the possibility to add products to a list - and send your list to us, thereby requesting a quotation.
You add products to the list by clicking the "GET A QUOTE" button on the individual product pages.

When you have submitted the list, we will get back to you as quickly as possible.

If you don't submit the list, it will be visible to you on the website for 7 days (we will place a so-called' cookie on your pc or tablet).

We hope you will find the functionality useful. Go to the product pages to add products to your list.
Thank you for your request for a quotation.
We will get back to you by phone or email as soon as possible.