Items 0
4131
 

4131

 

Universal trip amplifier

 

  • Input for RTD, TC, Ohm, potentiometer, mA and V
  • 2 adjustable alarm limits
  • FM-approved for installation in Div. 2
  • 2 relay outputs
  • Universal AC or DC supply
  1. Overview

  2. Technical details

  3. Accessories


Advanced features

  • Programmable via detachable display front (4501), process calibration, relay simulation, password protection, error diagnostics and selection of help text in several languages.

Application

  • Process control with 2 pairs of potential-free relay contacts which can be configured to suit any application.
  • Trip amplifier with window function defined by a high and a low setpoint. The relay changes state outside the window.
  • Relay latch function, where the relay is activated and can only be reset manually.
  • Sophisticated sensor error surveillance, where one relay holds the state immediately prior to the sensor error, while allowing the process to continue. The other relay can be set for sensor error alarm so that the defect sensor can be replaced immediately.

Technical characteristics

  • When 4131 is used with the 4501 display / programming front, all operational parameters can be modified to suit any application. As the 4131 is designed with electronic hardware switches, it is not necessary to open the device for setting of DIP-switches.
  • A green front LED indicates normal operation and malfunction. A yellow LED is ON for each active output relay.
  • Continuous check of vital stored data for safety reasons.
  • 3-port 2.3 kVAC galvanic isolation.

Environmental Conditions

Operating temperature -20°C to +60°C
Calibration temperature 20...28°C
Relative humidity < 95% RH (non-cond.)
Protection degree IP20

Mechanical specifications

Dimensions (HxWxD) 109 x 23.5 x 104 mm
Dimensions (HxWxD) w/ 4501 / 4511 109 x 23.5 x 116 / 131 mm
Weight approx. 170 g
Weight incl. 4501 / 4511 (approx.) 185 g / 270 g
Wire size 1 x 2.5 mm2 stranded wire
Screw terminal torque 0.5 Nm
Vibration IEC 60068-2-6
2...13.2 Hz ±1 mm
13.2...100 Hz ±0.7 g

Common specifications

Supply

Supply voltage, universal 21.6...253 VAC, 50...60 Hz or 19.2...300 VDC
Fuse 400 mA SB / 250 VAC
Max. required power ≤ 2.0 W

Isolation voltage

Isolation voltage, test / working 2.3 kVAC / 250 VAC

Response time

Temperature input (0...90%, 100...10%) ≤ 1 s
mA / V input (0...90%, 100...10%) ≤ 400 ms

Auxiliary supplies

2-w. supply (term. 44...43) 25...16 VDC / 0...20 mA
Programming Communication enabler 4511 / Programming front 4501
Signal / noise ratio Min. 60 dB (0...100 kHz)
Accuracy Better than 0.1% of selected range
EMC immunity influence < ±0.5% of span
Extended EMC immunity: NAMUR NE21, A criterion, burst < ±1% of span

Input specifications

RTD input

RTD type Pt10/20/50/100/200/250; Pt300/400/500/1000; Ni50/100/120/1000; Cu10/20/50/100
Cable resistance per wire 50 Ω (max.)
Sensor current Nom. 0.2 mA
Effect of sensor cable resistance (3-/4-wire) < 0.002 Ω / Ω
Sensor error detection Yes
Short circuit detection < 15 Ω

Linear resistance input

Linear resistance min....max. 0 Ω...10000 Ω

Potentiometer input

Potentiometer min....max. 10 Ω...100 kΩ

TC input

Thermocouple type B, E, J, K, L, N, R, S, T, U, W3, W5, LR
Cold junction compensation (CJC) via ext. sensor in connector 5910 20...28°C ≤ ±1°C, -20...20°C / 28...70°C ≤ 2°C
CJC via internally mounted sensor ±(2.0°C + 0.4°C * Δt)
Δt = Internal temp.-ambient temp.
Sensor error detection Yes
Sensor error current: When detecting / else Nom. 2 μA / 0 μA

Current input

Measurement range 0...20 mA
Programmable measurement ranges 0...20 and 4...20 mA
Input resistance Nom. 20 Ω + PTC 50 Ω

Voltage input

Measurement range 0...12 VDC
Programmable measurement ranges 0/0.2...1, 0/1...5, 0/2...10 VDC
Input resistance Nom. 10 MΩ

Output specifications

Relay output

Relay functions Setpoint, Window, Sensor error, Latch, Power and Off
Hysteresis 0...100%
ON and OFF delay 0...3600 s
Max. voltage 250 VRMS
Max. current 2 AAC or 1 ADC
Max. AC power 500 VA
Sensor error reaction Break / Make / Hold
of span = of the currently selected measurement range

Observed authority requirements

EMC 2014/30/EU
LVD 2014/35/EU
EAC TR-CU 020/2011

Approvals

FM 3025177
UL UL 508 / C22.2 no. 14
DNV-GL Marine Stand. f. Certific. No. 2.4
EU RO Mutual Recognition Type Approval MRA000000Z
Your request has been sent successfully. - 0 Items on your list
Product description Quantity
Please specify variant(s) (see data sheet) - or indicate ‘Variant unknown’
Your contact information
Continue browsing
No products added
You have no products on your list...

When browsing product pages on this website, you have the possibility to add products to a list - and send your list to us, thereby requesting a quotation.
You add products to the list by clicking the "GET A QUOTE" button on the individual product pages.

When you have submitted the list, we will get back to you as quickly as possible.

If you don't submit the list, it will be visible to you on the website for 7 days (we will place a so-called' cookie on your pc or tablet).

We hope you will find the functionality useful. Go to the product pages to add products to your list.
Thank you for your request for a quotation.
We will get back to you by phone or email as soon as possible.