Items 0
2281
 

2281

 

Ramp generator

 

  • Multiple functions
  • Programmable from front
  • 3-digit LED display
  • NPN and PNP inputs
  • Internal ramp time or external pulses
  • Reset or preset function
  1. Overview

  2. Technical details

  3. Accessories


Advanced features

  • The user interface consists of a 3-digit display and 3 function keys in the front to change a function, ramp time or an output signal range.

Application

  • To convert digital signals to a time-controlled analog signal with either internally entered up/down time or with external pulses for up/down function.
  • 2-phase encoder.
  • Ramp generator with internal time measurement.
  • Ramp generator with external pulses.

Technical characteristics

  • LED’s for up, reset and down.
  • 6 digital inputs make it possible to choose reset and up/down functions as either NPN or PNP input (+24 VDC).
  • Via an analog switch the up and down inputs can be switched between input filters for a pulse length > 10 ms or > 0.5 ms. The 10 ms filter is used for elimination of contact-bounce.
  • Analog standard current output of 0/4...20 mA or jumper selectable 0/2...10 mA, and standard voltages of 0/0.2...1 VDC, 0/2...10 VDC or special.
  • Mounting for a standard 11-pole socket which can be adapted for DIN rail or plate use with PR’s 7023 adaptor and 7024 mounting keying.

Environmental Conditions

Operating temperature -20°C to +60°C
Calibration temperature 20...28°C
Relative humidity < 95% RH (non-cond.)
Protection degree IP50

Mechanical specifications

Dimensions (HxWxD) 80.5 x 35.5 x 84.5 mm (D is without pins)
Weight approx. 120 g

Common specifications

Supply

Supply voltage 19.2...28.8 VDC
Max. required power 2.7 W
Internal power dissipation 2.4 W

Response time

Response time < 60 ms
Signal / noise ratio Min. 60 dB
Signal dynamics, output 16 bit
Up ramp time 0.1...999999 s
Down ramp time 0.1...999999 s
External pulses 1...15,615,744
Effect of supply voltage change < 0.005% of span / VDC
Temperature coefficient < ±0.01% of span / °C
Linearity error < 0.1% of span
EMC immunity influence < ±0.5%

Input specifications

Digital input Up / down inputs Reset inputs
NPN, digital input Pull up 24 VDC / 6.9 mA
PNP, digital input Pull down 0 VDC / 6.9 mA
Pulse length >10 ms / > 0.5 ms (programmable) > 30 ms
Input frequency 50 Hz / 1 kHz (max.) 16 Hz

Output specifications

Current output

Signal range 0...20 mA
Min. signal range 5 mA
Load (@ current output) ≤ 600 Ω
Load stability ≤ 0.01% of span / 100 Ω
Current limit 20.5 mA
Voltage output through internal shunt See manual for details
of span = of the presently selected range

Observed authority requirements

EMC 2014/30/EU
EAC TR-CU 020/2011
Your request has been sent successfully. - 0 Items on your list
Product description Quantity
Please specify variant(s) (see data sheet) - or indicate ‘Variant unknown’
Your contact information
Continue browsing
No products added
You have no products on your list...

When browsing product pages on this website, you have the possibility to add products to a list - and send your list to us, thereby requesting a quotation.
You add products to the list by clicking the "GET A QUOTE" button on the individual product pages.

When you have submitted the list, we will get back to you as quickly as possible.

If you don't submit the list, it will be visible to you on the website for 7 days (we will place a so-called' cookie on your pc or tablet).

We hope you will find the functionality useful. Go to the product pages to add products to your list.
Thank you for your request for a quotation.
We will get back to you by phone or email as soon as possible.