Items 0
3111
 

3111

 

TC converter - isolated

 

  • Excellent accuracy, better than 0.05% of span
  • Slimline housing of 6 mm
  • Excellent EMC performance and 50/60 Hz noise suppression
  • Selectable < 30 ms / 300 ms response time
  • Pre-calibrated temperature ranges are selectable via DIP-switches
  1. Overview

  2. Technical details

  3. Accessories


Application

  • The 3111 temperature converter measures standard TC J and K temperature sensors, and provides an isolated analog voltage or current output.
  • High 3 port isolation provides surge suppression and protects the control system from transients and noise.
  • The 3111 can be mounted in the safe area or in Zone 2 / Division 2 areas.
  • Approved for marine applications.

Technical characteristics

  • Flexibly powered by 24 VDC (±30%) via power rail or connectors.
  • < 30 ms fast response time with simultaneous sensor error detection when selected.
  • Selectable 300 ms response time when signal dampening is needed.
  • Selectable internal/external CJC.
  • Excellent conversion accuracy in all available ranges, better than 0.05% of span.
  • Meeting the NAMUR NE21 recommendations, the 3111 provides top measurement performance in harsh EMC environments.
  • The device meets the NAMUR NE43 standard defining out of range and sensor error output values.
  • A visible green LED indicates operational status of the unit and the input sensor.
  • All terminals are protected against overvoltage and polarity error.
  • High galvanic isolation of 2.5 kVAC.
  • Excellent signal/noise ratio of > 60 dB.

Mounting / installation / programming

  • Selectable DIP-settings for easy configuration of more than 1000 factory calibrated measurement ranges.
  • The narrow 6 mm housing allows up to 165 units to be mounted per meter of DIN rail, without any air gap between units.
  • Wide ambient temperature range of -25...+70°C.

Environmental Conditions

Operating temperature -25°C to +70°C
Storage temperature -40°C to +85°C
Calibration temperature 20...28°C
Relative humidity < 95% RH (non-cond.)
Protection degree IP20
Installation in Pollution degree 2 & measurement / overvoltage cat. II

Mechanical specifications

Dimensions (HxWxD) 113 x 6.1 x 115 mm
Weight approx. 70 g
DIN rail type DIN EN 60715/35 mm
Wire size 0.13 x 2.5 mm2 / AWG 26...12 stranded wire
Screw terminal torque 0.5 Nm
Vibration IEC 60068-2-6
2...25 Hz ±1.6 mm
25...100 Hz ±4 g

Common specifications

Supply

Supply voltage 16.8...31.2 VDC
Max. required power 0.7 W

Isolation voltage

Isolation voltage, test / working 2.5 kVAC / 300 VAC (reinforced)
Zone 2 / Div. 2 250 VAC

Response time

Response time (0...90%, 100...10%) < 30 ms / 300 ms (selectable)
Signal / noise ratio > 60 dB
Programming DIP-switches
Signal dynamics, input 23 bit
Signal dynamics, output 18 bit
Accuracy Better than 0.05% of selected range
EMC immunity influence < ±0.5% of span
Extended EMC immunity: NAMUR NE21, A criterion, burst < ±1% of span
Incorrect DIP-switch setting identification 0 V / 0 mA output; LED 0.5 s / 1 Hz

Input specifications

TC input

Temperature range, TC J -100...+1200°C
Temperature range, TC K -180...+1372°C
Min. measurement range (span) - TC J & K 50°C
Accuracy: the greater of Better than 0.05% of span or 0.5°C
Temperature coefficient: the greater of 0.1°C/°C or ≤ ±0.01%/°C
Sensor cable resistance < 5 kΩ per wire
Cold junction compensation (CJC): Accuracy @ external Pt100 input Better than ±0.15°C
Cold junction compensation (CJC): Accuracy @ internal CJC Better than ±2.5°C
Internal CJC error detection Yes
External CJC error detection Yes - selectable via DIP-switch
Open Thermocouple detection Yes - selectable via DIP-switch

Output specifications

Common output specifications

Updating time 10 ms

Current output

Signal range 0...23 mA
Programmable signal ranges 0 / 4...20 mA
Sensor error indication (0...20 mA) 0 mA or 23 mA / OFF
Sensor error indication (4...20 mA) 3.5 mA or 23 mA / acc. to NAMUR NE43 or OFF
Load (@ current output) ≤ 600 Ω
Load stability ≤ 0.01% of span / 100 Ω
Current limitation @ low output load < 60 mA peak / < 4 mA average

Voltage output

Programmable signal ranges 0/1...5 and 0/2...10 V
Sensor error indication 0 V / 10% above the max. / none
Open output < 18 V

Observed authority requirements

EMC 2014/30/EU
LVD 2014/35/EU
RoHS 2011/65/EU
EAC TR-CU 020/2011

Approvals

ATEX 2014/34/EU KEMA 10ATEX0147 X
IECEx KEM 10.0068X
FM FM17US0004X / FM17CA0003X
DNV-GL Marine Stand. f. Certific. No. 2.4 V1-7-2
UL UL 61010-1
Your request has been sent successfully. - 0 Items on your list
Product description Quantity
Please specify variant(s) (see data sheet) - or indicate ‘Variant unknown’
Your contact information
Continue browsing
No products added
You have no products on your list...

When browsing product pages on this website, you have the possibility to add products to a list - and send your list to us, thereby requesting a quotation.
You add products to the list by clicking the "GET A QUOTE" button on the individual product pages.

When you have submitted the list, we will get back to you as quickly as possible.

If you don't submit the list, it will be visible to you on the website for 7 days (we will place a so-called' cookie on your pc or tablet).

We hope you will find the functionality useful. Go to the product pages to add products to your list.
Thank you for your request for a quotation.