9113A
Temperature / mA converter
- Input for RTD, TC and mA
- Active / passive mA output via the same two terminals
- 1 or 2 channels
- Can be supplied separately or installed on power rail, PR type 9400
- SIL 2-certified via Full Assessment
Advanced features
- Configuration and monitoring by way of detachable display front (PR 4511/4501); process calibration and signal simulation.
- Copying of the configuration from one device to others of the same type via the display front.
- TC inputs can use either the internal CJC or a terminal with a built-in Pt100 sensor (PR 5910, channel 1 / PR 5913, channel 2) for higher accuracy.
- Advanced monitoring of internal communication and stored data.
- SIL 2 functionality is optional and must be activated in a menu point.
Application
- The device can be mounted in and receive signals from non-classified area and zone 2.
- Conversion and scaling of temperature (Pt, Ni and TC) and active current signals.
- 9113A has been designed, developed and certified for use in SIL 2 applications according to the requirements of IEC 61508.
Technical characteristics
- 1 green and 2 red front LEDs indicate operation status and malfunction.
- 2.6 kVAC galvanic isolation between input, output and supply.
Mounting
- The devices can be mounted vertically or horizontally without distance between neighbouring units.
Environmental Conditions
| Operating temperature | -20°C to +60°C |
| Storage temperature | -20°C to +85°C |
| Calibration temperature | 20...28°C |
| Relative humidity | < 95% RH (non-cond.) |
| Protection degree | IP20 |
| Installation in | Pollution degree 2 & meas. / overvoltage cat. II |
Mechanical specifications
| Dimensions (HxWxD) | 109 x 23.5 x 104 mm |
| Dimensions (HxWxD) w/ 4501/4511 | 109 x 23.5 x 116 / 131 mm |
| Weight approx. | 250 g |
| Weight incl. 4501 / 4511 (approx.) | 265 g / 280 g |
| DIN rail type | DIN EN 60715/35 mm |
| Wire size | 0.13...2.08 mm2 AWG 26...14 stranded wire |
| Screw terminal torque | 0.5 Nm |
| Vibration | IEC 60068-2-6 |
| 2...13.2 Hz | ±1 mm |
| 13.2...100 Hz | ±0.7 g |
Common specifications
Supply |
|
| Supply voltage | 19.2...31.2 VDC |
| Max. required power | ≤ 0.8 W/≤ 1.4 W (1 ch./2 ch.) |
| Max. power dissipation, 1 / 2 ch. | ≤ 0.8 W / ≤ 1.4 W |
| Fuse | 400 mA SB / 250 VAC |
Isolation voltage |
|
| Test /working: Input to any | 2.6 kVAC / 300 VAC reinforced isolation |
| Analog output to supply | 2.6 kVAC / 300 VAC reinforced isolation |
| Status relay to supply | 1.5 kVAC / 150 VAC reinforced isolation |
Response time |
|
| Temperature input, programmable (0...90%, 100...10%) | 1...60 s |
| mA / V input (programmable) | 0.4...60 s |
| Programming | PR 45xx |
| Signal / noise ratio | Min. 60 dB (0...100 kHz) |
| Signal dynamics, input | 24 bit |
| Signal dynamics, output | 16 bit |
| Accuracy | Better than 0.1% of sel. range |
| EMC immunity influence | < ±0.5% of span |
| Extended EMC immunity: NAMUR NE21, A criterion, burst | < ±1% of span |
Input specifications
RTD input |
|
| RTD type | Pt10/20/50/100/200/250/300/Pt400/500/1000; Ni50/100/120/1000 |
| Cable resistance per wire | 50 Ω (max.) |
| Sensor current | Nom. 0.2 mA |
| Effect of sensor cable resistance (3-/4-wire) | < 0.002 Ω / Ω |
| Sensor error detection | Programmable ON / OFF |
TC input |
|
| Thermocouple type | B, E, J, K, L, N, R, S, T, U, W3, W5, LR |
| Cold junction compensation (CJC) via ext. sensor in 5910 | 20...28°C ≤ ±1°C, -20...20°C / 28...70°C ≤ 2°C |
| CJC via int. mounted sensor | ±(2.0°C + 0.4°C * Δt) |
| Δt = | Internal temp.-ambient temp. |
| Sensor error detection | Programmable ON or OFF (only wire breakage) |
| Sensor error current: When detecting / else | Nom. 2 μA / 0 μA |
Current input |
|
| Measurement range | 0...23 mA |
| Programmable measurement ranges | 0...20 and 4...20 mA |
| Input resistance | Nom. 20 Ω + PTC 50 Ω |
| Sensor error detection | Programmable ON / OFF |
Output specifications
Current output |
|
| Signal range | 0...23 mA |
| Programmable signal ranges | 0...20/4...20/20...0/20...4 mA |
| Load (@ current output) | ≤ 600 Ω |
| Load stability | ≤ 0.01% of span / 100 Ω |
| Sensor error indication | 0 / 3.5 / 23 mA / none |
| NAMUR NE43 Upscale/Downscale | 23 mA / 3.5 mA |
| Output limitation, on 4...20 and 20...4 mA signals | 3.8...20.5 mA |
| Output limitation, on 0...20 and 20...0 mA signals | 0...20.5 mA |
| Current limit | ≤ 28 mA |
Passive 2-wire mA output |
|
| Max. external 2-wire supply | 26 VDC |
| Max. load resistance [Ω] | (Vsupply-3.5)/0.023 A |
| Effect of external 2-wire supply voltage variation | < 0.005% of span / V |
Status relay |
|
| Max. voltage | 110 VDC / 125 VAC |
| Max. current | 0.3 ADC / 0.5 AAC |
| Max. AC power | 62.5 VA / 32 W |
| of span | = of the currently selected measurement range |
Observed authority requirements
| EMC | 2014/30/EU |
| LVD | 2014/35/EU |
| RoHS | 2011/65/EU |
| EAC | TR-CU 020/2011 |
Approvals
| ATEX 2014/34/EU | KEMA 07ATEX0148 X |
| IECEx | KEM 09.0052X |
| UL | UL 61010-1 |
| DNV-GL Marine | Stand. f. Certific. No. 2.4 |
| ClassNK | TA18527M |
| SIL | SIL 2 certified & fully assessed acc. to IEC 61508 |
3405
Power connector unit
4501
Display / programming front
4511
Communication enabler
4590
ConfigMate
5910
CJC connector
5913
CJC connector
7423
Ceramic socket for Pt100 sensor
7430B
Pt100 cable sensor
7430C
Pt100 cable sensor
7440
Thermowell for PR 7400 Pt100 sensor
8510
8 unit 4511 Modbus cable
8511
4511 Y-splitter Modbus cable
8513
RJ45 Modbus termination
8514
3 X RJ45 female Y-splitter
8515
RJ45 female to female cable adapter
8516
RJ45 female to female shielded cable adabter
8517
3 x RJ45 female shielded Y-splitter
9400_1
Power rail 15 mm profile
9400_2
Power rail 7.5 mm profile
9402
Extra end covers for power rail
9404
Module stop
9410
Power control unit