Items 0
9116A
 
 

9116A

 

Universal converter

 

  • Input for RTD, TC, Ohm, potentiometer, mA and V
  • Supply for 2-wire transmitters
  • Active / passive mA output and relay output
  • Can be supplied separately or installed on power rail, PR type 9400
  • SIL 2-certified via Full Assessment
  1. Overview +

  2. Technical details +

  3. Accessories +


Advanced features

  • Configuration and monitoring by way of detachable display front (PR 4511/4501); process calibration, signal and relay simulation.
  • Advanced relay configuration, e.g. setpoint, window, delay, sensor error indication and power monitoring.
  • Copying of the configuration from one device to others of the same type via the display front.
  • TC inputs with internal CJC or external CJC for higher accuracy.
  • Active / passive mA output via the same two terminals.

Application

  • The device can be mounted in and receive signals from non-classified area and zone 2.
  • Conversion and scaling of temperature, voltage, potentiometer and linear resistance signals.
  • Power supply and signal isolator for 2-wire transmitters.
  • Monitoring of error events and cable breakage via the individual status relay and/or a collective electronic signal via the power rail.
  • 9116A has been designed, developed and certified for use in SIL 2 applications according to the requirements of IEC 61508.

Technical characteristics

  • 1 green and 1 red front LED indicate operation status and malfunction. 1 yellow LED indicates relay status.
  • 2.6 kVAC galvanic isolation between input, output and supply.

Mounting

  • The devices can be mounted vertically or horizontally without distance between neighbouring units.

Environmental Conditions

  • Operating temperature

    -20°C to +60°C

  • Storage temperature

    -20°C to +85°C

  • Calibration temperature

    20...28°C

  • Relative humidity

    < 95% RH (non-cond.)

  • Protection degree

    IP20

  • Installation in

    Pollution degree 2 & meas. / overvoltage cat. II

Mechanical specifications

  • Dimensions (HxWxD)

    109 x 23.5 x 104 mm

  • Dimensions (HxWxD) w/ 4501/4511

    109 x 23.5 x 116 / 131 mm

  • Weight approx.

    185 g

  • Weight incl. 4501 / 4511 (approx.)

    200 g / 285 g

  • DIN rail type

    DIN EN 60715/35 mm

  • Wire size

    0.13...2.08 mm2 AWG 26...14 stranded wire

  • Screw terminal torque

    0.5 Nm

  • Vibration

    IEC 60068-2-6

  • 2...13.2 Hz

    ±1 mm

  • 13.2...100 Hz

    ±0.7 g

Common specifications

  • Supply

  • Supply voltage

    19.2...31.2 VDC

  • Fuse

    1.25 A SB / 250 VAC

  • Max. required power

    ≤ 2.1 W

  • Max. power dissipation

    ≤ 1.7 W

  • Isolation voltage

  • Test /working: Input to any

    2.6 kVAC / 300 VAC reinforced isolation

  • Analog output to supply

    2.6 kVAC / 300 VAC reinforced isolation

  • Status relay to supply

    1.5 kVAC / 150 VAC reinforced isolation

  • Response time

  • Temperature input, programmable (0...90%, 100...10%)

    1...60 s

  • mA / V input (programmable)

    0.4...60 s

  • Auxiliary supplies

  • 9116B1: 2-w. sup. (term. 54...52)

    28...16.5 VDC / 0...20 mA

  • 9116B2: 2-w. sup. (term. 54...52)

    21.4...16.5 VDC / 0...20 mA

  • Programming

    Communication enabler 4511 / Programming front 4501

  • Signal dynamics, input

    24 bit

  • Signal dynamics, output

    16 bit

  • Signal / noise ratio

    Min. 60 dB (0...100 kHz)

  • Accuracy

    Better than 0.1% of sel. range

Input specifications

  • RTD input

  • RTD type

    Pt10/20/50/100/200/250/300/Pt400/500/1000; Ni50/100/120/1000

  • Cable resistance per wire

    50 Ω (max.)

  • Sensor current

    Nom. 0.2 mA

  • Effect of sensor cable resistance (3-/4-wire)

    < 0.002 Ω / Ω

  • Sensor error detection

    Programmable ON / OFF

  • Short circuit detection

    Yes

  • TC input

  • Thermocouple type

    B, E, J, K, L, N, R, S, T, U, W3, W5, LR

  • Cold junction compensation (CJC) via ext. sensor in 5910

    20...28°C ≤ ±1°C, -20...20°C / 28...70°C ≤ 2°C

  • CJC via int. mounted sensor

    ±(2.0°C + 0.4°C * Δt)

  • Δt =

    Internal temp.-ambient temp.

  • Sensor error detection

    Programmable ON or OFF (only wire breakage)

  • Current input

  • Measurement range

    0...23 mA

  • Programmable measurement ranges

    0...20 and 4...20 mA

  • Input resistance

    Nom. 20 Ω + PTC 50 Ω

  • Sensor error detection

    Loop break 4...20 mA

  • Voltage input

  • Measurement range

    0...12 VDC

  • Programmable measurement ranges

    0/0.2...1, 0/1...5, 0/2...10 VDC

  • Input resistance

    Nom. >10 MΩ

Output specifications

  • Current output

  • Signal range

    0...23 mA

  • Programmable signal ranges

    0...20/4...20/20...0/20...4 mA

  • Load (@ current output)

    ≤ 600 Ω

  • Load stability

    ≤ 0.01% of span / 100 Ω

  • Sensor error indication

    0 / 3.5 / 23 mA / none

  • NAMUR NE43 Upscale/Downscale

    23 mA / 3.5 mA

  • Current limit

    ≤ 28 mA

  • Passive 2-wire mA output

  • Max. external 2-wire supply

    26 VDC

  • Max. load resistance [Ω]

    (Vsupply-3.5)/0.023 A

  • Effect of external 2-wire supply voltage variation

    < 0.005% of span / V

  • Relay output

  • Relay functions

    Setpoint, Window, Sensor error, Power and Off

  • Max. voltage

    250 VAC / VDC

  • Max. current

    2 A

  • Max. AC power

    500 VA

  • Max. DC current, resistive load ≤ 30 VDC

    2 ADC

  • Max. DC current, resistive load > 30 VDC

    See manual for details

  • Status relay

  • Max. voltage

    110 VDC / 125 VAC

  • Max. current

    0.3 ADC / 0.5 AAC

  • Max. AC power

    62.5 VA / 32 W

Observed authority requirements

  • EMC

    2014/30/EU

  • LVD

    2014/35/EU

  • RoHS

    2011/65/EU

  • EAC

    TR-CU 020/2011

Approvals

  • ATEX 2014/34/EU

    KEMA 10ATEX0053 X

  • IECEx

    KEM 10.0022X

  • UL

    UL 61010-1

  • DNV-GL Marine

    Stand. f. Certific. No. 2.4

  • ClassNK

    TA18527M

  • SIL

    SIL 2 certified & fully assessed acc. to IEC 61508

Your request has been sent successfully. - 0 Items on your list
Product description Quantity
Please specify variant(s) (see data sheet) - or indicate ‘Variant unknown’
Your contact information
Continue browsing
No products added
You have no products on your list...

When browsing product pages on this website, you have the possibility to add products to a list - and send your list to us, thereby requesting a quotation.
You add products to the list by clicking the "GET A QUOTE" button on the individual product pages.

When you have submitted the list, we will get back to you as quickly as possible.

If you don't submit the list, it will be visible to you on the website for 7 days (we will place a so-called' cookie on your pc or tablet).

We hope you will find the functionality useful. Go to the product pages to add products to your list.
Thank you for your request for a quotation.
We will get back to you by phone or email as soon as possible.