6350A
Profibus PA / Foundation Fieldbus transmitter
- PROFIBUS PA ver. 3.0
- FOUNDATION Fieldbus ver. ITK 4.6
- Automatic switch between protocols
- Basic or LAS capability with F.F.
- 1- or 2-channel version
Application
- Linearized temperature measurement with RTD or TC sensor.
- Difference, average or redundancy temperature measurement with RTD or TC sensor.
- Converts analog mA signals into digital values on the bus communication.
- Linear resistance, potentiometer and bipolar mV measurement.
Technical characteristics
- Bus transmitter with both PROFIBUS PA and FOUNDATION Fieldbus communication. A unique switch function ensures automatic shift between the two protocols.
- Set-up for PROFIBUS PA can be done via Siemens Simatic® PDM®, ABB Melody / Harmony and Metso DNA software and for FOUNDATION Fieldbus via Emerson DeltaV, Yokogawa CS 1000 / CS 3000, ABB Melody / Harmony and Honeywell Experion software.
- Built-in simulation mode function.
- Polarity-independent bus connection.
- 24 bit A/D converter ensures high resolution.
- PROFIBUS PA function blocks:
2 analog. - FOUNDATION Fieldbus function blocks:
2 analog and 1 PID. - FOUNDATION Fieldbus capability:
Basic or LAS.
Mounting / installation
- Mounted vertically or horizontally on a DIN rail. Using the 2-channel version up to 84 channels per meter can be mounted.
Environmental Conditions
| Operating temperature | -40°C to +85°C |
| Storage temperature | -40°C to +85°C |
| Calibration temperature | 20...28°C |
| Relative humidity | < 95% RH (non-cond.) |
| Protection degree | IP20 |
Mechanical specifications
| Dimensions (HxWxD) | 109 x 23.5 x 104 mm |
| Weight (1 / 2 channels) | 145 / 185 g |
| DIN rail type | DIN EN 60715/35 mm |
| Wire size | 0.13...2.08 mm2 AWG 26...14 stranded wire |
| Screw terminal torque | 0.5 Nm |
Common specifications
Supply |
|
| Supply voltage | 9.0...32 VDC |
| Power dissipation, per channel | < 11 mA |
Isolation voltage |
|
| Test voltage | 1.5 kVAC for 60 s |
| Working voltage | 50 VRMS / 75 VDC |
Response time |
|
| Response time (programmable) | 1...60 s |
| Warm-up time | 30 s |
| Signal / noise ratio | Min. 60 dB |
| Accuracy | Better than 0.05% of selected range |
| Updating time | < 400 ms |
| Execution time, PID controller | < 200 ms |
| Execution time, analog input | < 50 ms |
| Signal dynamics, input | 24 bit |
| EMC immunity influence | < ±0.1% of reading |
| Extended EMC immunity: NAMUR NE21, A criterion, burst | < ±1% of reading |
Input specifications
RTD input |
|
| RTD type | Pt25…1000, Ni25…1000, Cu10…1000, lin. R, potentiometer |
| Cable resistance per wire | 50 Ω (max.) |
| Sensor current | Nom. 0.2 mA |
| Effect of sensor cable resistance (3-/4-wire) | < 0.002 Ω / Ω |
| Sensor error detection | Yes |
| Short circuit detection | < 15 Ω |
Linear resistance input |
|
| Linear resistance min....max. | 0 Ω...10000 Ω |
Potentiometer input |
|
| Potentiometer min....max. | 10 Ω...100 kΩ |
TC input |
|
| Thermocouple type | B, E, J, K, L, N, R, S, T, U, W3, W5 |
| Cold junction compensation (CJC) | < ±0.5°C |
| Sensor error detection | Yes |
| Sensor error current: When detecting / else | Nom. 2 μA / 0 μA |
| Short circuit detection | < 3 mV |
Bipolar current input |
|
| Measurement range | -100…+100 mA |
| Input resistance | 10 Ω + PTC < 20 Ω |
| Cable breakage detection (4...20 mA) | < 0.3 mA |
Bipolar mV input |
|
| Measurement range | -800…+800 mV |
| Min. measurement range (span) | 2.5 mV |
| Input resistance | 10 MΩ |
| Short circuit detection | < 3 mV |
Output specifications
PROFIBUS PA connection |
|
| PROFIBUS PA protocol | Profile A&B, ver. 3.0 |
| PROFIBUS PA protocol standard | EN 50170 vol. 2 |
| PROFIBUS PA address (at delivery) | 126 |
| PROFIBUS PA function blocks | 2 analog |
FOUNDATION Fieldbus connection |
|
| FOUNDATION Fieldbus protocol | FF protocol |
| FOUNDATION Fieldbus protocol standard | FF design specifications |
| FOUNDATION Fieldbus version | ITK 4.6 |
| FOUNDATION Fieldbus capability | Basic or LAS |
| FOUNDATION Fieldbus function blocks | 2 analog and 1 PID |
Observed authority requirements
| EMC | 2014/30/EU |
| EAC | TR-CU 020/2011 |
Approvals
| ATEX 2014/34/EU | KEMA 03ATEX1013 X |
| IECEx | DEK 14.0071X |
| FM | 3015609 |
| CSA | 1418937 |
5910
CJC connector
5913
CJC connector
7007
2-digit digital potentiometer
7008
3-digit digital potentiometer
7009
10-turn potentiometer, 200 Ω
7010
10-turn potentiometer, 20 kΩ
7011
Dial for 10-turn potentiometer
7012
1-turn potentiometer, 1 kΩ
7015
1-turn potentiometer, 10 kΩ
7016
1-turn potentiometer, 100 kΩ
7020
Knob for 1-turn potentiometer
7020A
Knob for 10-turn potentiometer
7028
10-turn potentiometer, 2 kΩ
7423
Ceramic socket for Pt100 sensor
7430B
Pt100 cable sensor