5105B
Ex-isolated driver
- 1- or 2-channel version
- 3- / 5-port 3.75 kVAC galvanic isolation
- Driver for Ex / I.S. area
- 20 programmable measurement ranges
- Universal supply by AC or DC
Application
- Safety barrier for current signals transmitted to I/P converters and displays mounted in hazardous area.
- Safety barrier for analog current / voltage signals transmitted to hazardous area.
- 1 : 1 or signal conversion of analog current / voltage signals.
Technical characteristics
- The 20 factory-calibrated measurement ranges in the 5105B can be selected by the internal DIP-switches without the need for a recalibration. Special measurement ranges can be delivered.
- PR5105B is based on microprocessor technology for gain and offset. The analog signal is transmitted at a response time of less than 25 ms.
- Inputs, outputs, and supply are floating and galvanically separated.
Mounting / installation
- Mounted vertically or horizontally on a DIN rail. By way of the 2-channel version up to 84 channels per meter can be mounted.
Environmental Conditions
| Operating temperature | -20°C to +60°C |
| Calibration temperature | 20...28°C |
| Relative humidity | < 95% RH (non-cond.) |
| Protection degree | IP20 |
Mechanical specifications
| Dimensions (HxWxD) | 109 x 23.5 x 130 mm |
| Weight approx. | 225 g |
| DIN rail type | DIN 46277 |
| Wire size | 1 x 2.5 mm2 stranded wire |
| Screw terminal torque | 0.5 Nm |
| Vibration | IEC 60068-2-6 |
| 2...13.2 Hz | ±1 mm |
| 13.2...100 Hz | ±0.7 g |
Common specifications
Supply |
|
| Supply voltage, universal | 21.6...253 VAC, 50...60 Hz or 19.2...300 VDC |
| Fuse | 400 mA SB / 250 VAC |
| Max. required power | ≤ 2 W (2 channels) |
| Internal power dissipation | ≤ 2 W (2 channels) |
Isolation voltage |
|
| Isolation voltage, test / working | 3.75 kVAC / 250 VAC |
| PELV/SELV | IEC 61140 |
Response time |
|
| Response time (0...90%, 100...10%) | < 25 ms |
| Signal / noise ratio | Min. 60 dB (0...100 kHz) |
| Accuracy | Better than 0.1% of sel. range |
| EMC immunity influence | < ±0.5% of span |
| Extended EMC immunity: NAMUR NE21, A criterion, burst | < ±1% of span |
Input specifications
Common input specifications |
|
| Max. offset | 20% of max. value |
Current input |
|
| Measurement range | 0...20 mA |
| Min. measurement range (span) | 16 mA |
| Input resistance | Nom. 10 Ω + PTC 10 Ω |
Voltage input |
|
| Measurement range | 0...10 VDC |
| Min. measurement range (span) | 8 VDC |
| Input resistance | > 2 MΩ |
Output specifications
Current output |
|
| Signal range | 0...20 mA |
| Min. signal range | 16 mA |
| Load (@ current output) | ≤ 770 Ω |
| Load stability | ≤ 0.01% of span / 100 Ω |
| Current limit | ≤ 28 mA |
Voltage output |
|
| Signal range | 0...1 VDC / 0...10 VDC |
| Min. signal range | 0.8 VDC / 8 VDC |
| Load (@ voltage output) | ≥ 500 kΩ |
| of span | = of the presently selected range |
Observed authority requirements
| EMC | 2014/30/EU |
| LVD | 2014/35/EU |
| EAC | TR-CU 020/2011 |
Approvals
| ATEX 2014/34/EU | DEMKO 99ATEX126014, II (1) GD [EEx ia] IIC |
| UL | UL 913, UL 508 |
| EAC Ex TR-CU 012/2011 | RU C-DK.GB08.V.00410 |
| DNV-GL Marine | Stand. f. Certific. No. 2.4 |