You have no products on your list...
When browsing product pages on this website, you have the possibility to add products to a list - and send your list to us, thereby requesting a quotation.
You add products to the list by clicking the "GET A QUOTE" button on the individual product pages.
When you have submitted the list, we will get back to you as quickly as possible.
If you don't submit the list, it will be visible to you on the website for 7 days (we will place a so-called' cookie on your pc or tablet).
We hope you will find the functionality useful. Go to the product pages to add products to your list.
5114B
Programmable transmitter
- Input for RTD, TC, mV, linear resistance, mA, and V
- 3-port 3.75 kVAC galvanic isolation
- Current and voltage output
- Universal voltage supply
- 1- and 2-channel versions
- Loop supply > 17.1 V in Ex / I.S. zone 0
Advanced features
- The 5114 transmitter can be configured using the PReset software and the Loop Link communications unit.
Application
- Jumper selectable inputs for current/voltage or temperature.
- Programmable current (0...100 mA) and voltage (0...250 VDC) inputs.
- Linearized, electronic temperature measurement.
- Conversion of linear resistance variation e.g, from solenoids and butterfly valves or linear movements with attached potentiometer.
- 17.1 VDC loop and 2.5 VDC potentiometer supplies.
- Automatic 4- / 3-wire or programmable 2-wire cable compensation.
- Configurable sensor error detection including NAMUR NE43.
Technical characteristics
- Active or Passive current output and selectable voltage output.
- Separation of circuits in PELV/SELV installations.
- I.S. barrier for temperature sensors, potentiometers, and current / voltage signals.
- I.S. barrier with I.S. power supply for 2-wire transmitters in zone 0, 1, 2, 20, 21 and 2.
Environmental Conditions
| Operating temperature | -20°C to +60°C |
| Calibration temperature | 20...28°C |
| Relative humidity | < 95% RH (non-cond.) |
| Protection degree | IP20 |
Mechanical specifications
| Dimensions (HxWxD) | 109 x 23.5 x 130 mm |
| Weight approx. | 225 g |
| DIN rail type | DIN 46277 |
| Wire size | 1 x 2.5 mm2 stranded wire |
| Screw terminal torque | 0.5 Nm |
| Vibration | IEC 60068-2-6 |
| 2...13.2 Hz | ±1 mm |
| 13.2...100 Hz | ±0.7 g |
Common specifications
Supply |
|
| Supply voltage, universal | 21.6...253 VAC, 50...60 Hz or 19.2...300 VDC |
| Fuse | 400 mA SB / 250 VAC |
| Max. required power | 2.1 W / 2.8 W (1 / 2 ch.) |
Isolation voltage |
|
| Isolation voltage, test / working | 3.75 kVAC / 250 VAC |
| PELV/SELV | IEC 61140 |
Response time |
|
| Temperature input, programmable (0...90%, 100...10%) | 400 ms...60 s |
| mA / V input (programmable) | 250 ms...60 s |
Auxiliary supplies |
|
| 2-wire supply (pin 44...42 and 54...52) | 28...17.1 VDC / 0...20 mA |
| Programming | Loop Link |
| Signal / noise ratio | Min. 60 dB (0...100 kHz) |
| Accuracy | Better than 0.05% of selected range |
| Updating time |
115 ms (temperature input)
75 ms (mA / V / mV input) |
| Signal dynamics, input | 22 bit |
| Signal dynamics, output | 16 bit |
| Auxiliary voltages: Reference voltage | 2.5 VDC ±0.5% / 15 mA |
| EMC immunity influence | < ±0.5% of span |
| Extended EMC immunity: NAMUR NE21, A criterion, burst | < ±1% of span |
Input specifications
Common input specifications |
|
| Max. offset | 50% of selected max. value |
RTD input |
|
| RTD type | Pt100, Ni100, lin. R |
| Cable resistance per wire | 10 Ω (max.) |
| Sensor current | Nom. 0.2 mA |
| Effect of sensor cable resistance (3-/4-wire) | < 0.002 Ω / Ω |
TC input |
|
| Thermocouple type | B, E, J, K, L, N, R, S, T, U, W3, W5, LR |
| Cold junction compensation (CJC) | < ±1.0°C |
| Sensor error current | Nom. 30 μA |
| Sensor error detection | Yes |
Current input |
|
| Measurement range | 0...100 mA |
| Min. measurement range (span) | 4 mA |
| Input resistance: Supplied unit | Nom. 10 Ω + PTC 10 Ω |
| Input resistance: Non-supplied unit | RSHUNT = ∞, VDROP < 6 V |
Voltage input |
|
| Measurement range |
0...250 VDC
-150...+150 mV |
| Min. measurement range (span) | 5 mV |
| Input resistance |
Nom. 10 MΩ (≤ 2.5 VDC)
Nom. 5 MΩ (> 2.5 VDC) Nom. 10 MΩ (mV input) |
Output specifications
Current output |
|
| Signal range | 0...20 mA |
| Min. signal range | 10 mA |
| Load (@ current output) | ≤ 600 Ω |
| Load stability | ≤ 0.01% of span / 100 Ω |
| Current limit | ≤ 28 mA |
| Sensor error indication | Programmable 0...23 mA |
| NAMUR NE43 Upscale/Downscale | 23 mA / 3.5 mA |
Passive 2-wire mA output |
|
| Signal range | 4...20 mA |
| Load stability | ≤ 0.01% of span / 100 Ω |
| Max. load resistance [Ω] | (Vsupply-3.5)/0.023 A |
| Max. external 2-wire supply | 29 VDC |
| Effect of external 2-wire supply voltage variation | < 0.005% of span / V |
Voltage output |
|
| Signal range | 0...10 VDC |
| Min. signal range | 500 mV |
| Load (@ voltage output) | ≥ 500 kΩ |
| of span | = of the presently selected range |
Observed authority requirements
| EMC | 2014/30/EU |
| LVD | 2014/35/EU |
| RoHS | 2011/65/EU |
| EAC | TR-CU 020/2011 |
Approvals
| ATEX 2014/34/EU | DEMKO 99ATEX124571, II (1) GD [EEx ia] IIC |
| EAC Ex TR-CU 012/2011 | RU C-DK.GB08.V.00410 |
| DNV-GL Marine | Stand. f. Certific. No. 2.4 |
5909
Loop Link communications interface
5910Ex
CJC connector
5913Ex
CJC connector
7007
2-digit digital potentiometer
7008
3-digit digital potentiometer
7009
10-turn potentiometer, 200 Ω
7011
Dial for 10-turn potentiometer
7012
1-turn potentiometer, 1 kΩ
7020
Knob for 1-turn potentiometer
7020A
Knob for 10-turn potentiometer
7028
10-turn potentiometer, 2 kΩ
7423
Ceramic socket for Pt100 sensor
7430B
Pt100 cable sensor
7430C
Pt100 cable sensor
7440
Thermowell for PR 7400 Pt100 sensor
8201L
Power wire