You have no products on your list...
When browsing product pages on this website, you have the possibility to add products to a list - and send your list to us, thereby requesting a quotation.
You add products to the list by clicking the "GET A QUOTE" button on the individual product pages.
When you have submitted the list, we will get back to you as quickly as possible.
If you don't submit the list, it will be visible to you on the website for 7 days (we will place a so-called' cookie on your pc or tablet).
We hope you will find the functionality useful. Go to the product pages to add products to your list.
9106B
HART transparent repeater
- 24 VDC supply via power rail or connectors
- Active and passive mA input
- Active or passive output via the same two terminals
- Splitter function - 1 in and 2 out
- SIL3 Full Assessment and certified acc. to IEC 61508
Application
- 9106B is a 1- or 2-channel isolated 1:1 repeater barrier for intrinsic safety applications.
- The device supplies 2-wire SMART transmitters and can also be used for 2-wire SMART current sources. HART & BRAIN protocols are supported and are transferred bi-directionally.
- 9106B can be mounted in the safe area or in zone 2 / Cl. 1, div. 2 and receive signals from zone 0, 1, 2 and zone 20, 21, 22 including mining / Class I/II/III, Div. 1, Gr. A-G.
- For duplication/migration purposes, the outputs can be sent to two different DCS/PLC/HMI or any monitoring system.
- In safety applications (SIL loops), the 9106BxB can be used as a splitter with the following output configuration:
· When using 9106BxB in a SIL2 safety function, channel 1 is used for the safety loop. Channel 2 can be used for any non-safety device.
· For higher safety purposes (SIL 3), 9106BxB can be used as a splitter for SIL 3 loops. Channel 1 and 2 are then connected to the same safety PLC, where channel 2 is used as a redundant diagnostic channel. (for more information, consult the FMEDA Report and the Safety Manual).
Advanced features
- The PR 4501 detachable display and the green and red front LEDs indicate operation status for each channel.
- Monitoring of error events and cable breakage on input via the individual status relay and/or a collective electronic signal via the power rail.
Technical characteristics
- High galvanic isolation of 2.6 kVAC.
- Fast response time <5 ms
- High accuracy better than 0.1%.
- 2-wire transmitter supply >16 V.
Mounting
- The devices can be mounted vertically or horizontally without distance between neighboring units.
Brazilian manual
Environmental Conditions
| Operating temperature | -20°C to +60°C |
| Storage temperature | -20°C to +85°C |
| Calibration temperature | 20...28°C |
| Relative humidity | < 95% RH (non-cond.) |
| Protection degree | IP20 |
| Installation in | Pollution degree 2 & meas. / overvoltage cat. II |
Mechanical specifications
| Dimensions (HxWxD) | 109 x 23.5 x 104 mm |
| Dimensions (HxWxD) w/ 4501/4511 | 109 x 23.5 x 116 / 131 mm |
| Weight approx. | 250 g |
| Weight incl. 4501 / 4511 (approx.) | 265 g / 280 g |
| DIN rail type | DIN EN 60715/35 mm |
| Wire size | 0.13...2.08 mm2 AWG 26...14 stranded wire |
| Screw terminal torque | 0.5 Nm |
| Vibration | IEC 60068-2-6 |
| 2...13.2 Hz | ±1 mm |
| 13.2...100 Hz | ±0.7 g |
Common specifications
Supply |
|
| Supply voltage | 19.2...31.2 VDC |
| Fuse | 1.25 A SB / 250 VAC |
| Max. required power | ≤ 1.1 W / ≤ 1.9 W (1 ch. / 2 ch.) |
| Max. power dissipation, 1 / 2 ch. | ≤ 0.8 W / ≤ 1.2 W |
Isolation voltage |
|
| Test /working: Input to any | 2.6 kVAC / 300 VAC reinforced isolation |
| Analog output to supply | 2.6 kVAC / 300 VAC reinforced isolation |
| Status relay to supply | 1.5 kVAC / 150 VAC reinforced isolation |
Response time |
|
| Response time (0...90%, 100...10%) | < 5 ms |
| Programming | PR 45xx |
| Signal dynamics, input | Analog signal chain |
| Signal dynamics, output | Analog signal chain |
| SMART bi-directional communication frequency range | 0.5...7.5 kHz |
| Signal / noise ratio | > 60 dB |
| Accuracy | Better than 0.1% of sel. range |
| mA, absolute accuracy | ≤ ±16 μA |
| mA, temperature coefficient | ≤ ±1.6 μA / °C |
| Effect of supply voltage change on output (nom. 24 VDC) | < ±10 μA |
| EMC immunity influence | < ±0.5% of span |
| Extended EMC immunity: NAMUR NE21, A criterion, burst | < ±1% of span |
Input specifications
Current input |
|
| Measurement range | 3.5...23 mA |
| 2-wire transmitter supply 9106B1x (Uo = 27.5 VDC) | >16 V / 20 mA |
| 2-wire transmitter supply 9106B2x (Uo = 25.3 VDC) | >15 V / 20 mA |
| Sensor error detection: Loop break 4...20 mA | < 1 mA |
| Input voltage drop, supplied unit | < 4 V @ 23 mA |
| Input voltage drop, non-supplied unit | < 6 V @ 23 mA |
Output specifications
Current output |
|
| Signal range | 3.5...23 mA |
| Load (@ current output) | ≤ 600 Ω |
| Load stability | ≤ 0.01% of span / 100 Ω |
| Current limit | ≤ 28 mA |
Passive 2-wire mA output |
|
| Effect of external 2-wire supply voltage variation | < 0.005% of span / V |
| Max. load resistance [Ω] | (Vsupply-3.5)/0.023 A |
| Max. external 2-wire supply | 26 VDC |
Status relay |
|
| Relay function | N.C. |
| Programmable low setpoint | 0...29.9 mA |
| Programmable high setpoint | 0...29.9 mA |
| Hysteresis for setpoints | 0.1 mA |
| Max. voltage | 110 VDC / 125 VAC |
| Max. current | 0.3 ADC / 0.5 AAC |
| Max. voltage - hazardous installation | 32 VDC / 32 VAC |
| Max. current - hazardous installation | 1 ADC / 0.5 AAC |
| of span | = normal measurement range 4...20 mA |
Observed authority requirements
| EMC | 2014/30/EU |
| LVD | 2014/35/EU |
| RoHS | 2011/65/EU |
| EAC | TR-CU 020/2011 |
Approvals
| ATEX 2014/34/EU | DEKRA 11ATEX0244 X |
| IECEx | DEK 11.0084X |
| FM | FM16US0465X / FM16CA0213X |
| INMETRO | DEKRA 16.0001 X |
| UL | UL 61010-1 |
| EAC Ex TR-CU 012/2011 | RU C-DK.GB08.V.00410 |
| DNV-GL Marine | Stand. f. Certific. No. 2.4 |
| ClassNK | TA18527M |
| SIL | SIL 2 / SIL 3 certified & fully assessed acc. to IEC 61508 |
3405
Power connector unit
4501
Display / programming front
4511
Communication enabler
8510
8 unit 4511 Modbus cable
8511
4511 Y-splitter Modbus cable
8513
RJ45 Modbus termination
8514
3 X RJ45 female Y-splitter
8515
RJ45 female to female cable adapter
8516
RJ45 female to female shielded cable adabter
8517
3 x RJ45 female shielded Y-splitter
9400_1
Power rail 15 mm profile
9400_2
Power rail 7.5 mm profile
9402
Extra end covers for power rail
9404
Module stop
9410
Power control unit