9116B
Universal converter
- Input for RTD, TC, Ohm, potentiometer, mA and V
- Supply for 2-wire transmitters
- Active / passive mA output and relay output
- Can be supplied separately or installed on power rail, PR type 9400
- SIL 2-certified via Full Assessment
Advanced features
- Configuration and monitoring by way of detachable display front (PR 4501); process calibration, signal and relay simulation.
- Advanced relay configuration, e.g. setpoint, window, delay, sensor error indication and power monitoring.
- Copying of the configuration from one device to others of the same type via PR4501.
- Reduced Uo Ex data < 8.3 V for active input signals.
- TC inputs with internal CJC or external CJC for higher accuracy.
- Active / passive mA output via the same two terminals.
Application
- 9116B can be mounted in the safe area and in zone 2 / cl. 1 div. 2 and receive signals from zone 0, 1, 2 and zone 20, 21, 22 including M1 / Class I/II/III, Div. 1, Gr. A-G.
- Conversion and scaling of temperature, voltage, potentiometer and linear resistance signals.
- Power supply and signal isolator for 2-wire transmitters.
- Monitoring of error events and cable breakage via the individual status relay and/or a collective electronic signal via the power rail.
- The 9116 has been designed, developed and certified for use in SIL 2 applications according to the requirements of IEC 61508.
- Suitable for the use in systems up to Performance Level “d” according to ISO-13849.
Technical characteristics
- 1 green and 1 red front LED indicate operation status and malfunction. 1 yellow LED indicates relay status.
- 2.6 kVAC galvanic isolation between input, output and supply.
Mounting
- The devices can be mounted vertically or horizontally without distance between neighbouring units.
Brazilian manual
Environmental Conditions
| Operating temperature | -20°C to +60°C |
| Storage temperature | -20°C to +85°C |
| Calibration temperature | 20...28°C |
| Relative humidity | < 95% RH (non-cond.) |
| Protection degree | IP20 |
| Installation in | Pollution degree 2 & meas. / overvoltage cat. II |
Mechanical specifications
| Dimensions (HxWxD) | 109 x 23.5 x 104 mm |
| Dimensions (HxWxD) w/ 4501/4511 | 109 x 23.5 x 116 / 131 mm |
| Weight approx. | 185 g |
| Weight incl. 4501 / 4511 (approx.) | 200 g / 215 g |
| DIN rail type | DIN EN 60715/35 mm |
| Wire size | 0.13...2.08 mm2 AWG 26...14 stranded wire |
| Screw terminal torque | 0.5 Nm |
| Vibration | IEC 60068-2-6 |
| 2...13.2 Hz | ±1 mm |
| 13.2...100 Hz | ±0.7 g |
Common specifications
Supply |
|
| Supply voltage | 19.2...31.2 VDC |
| Fuse | 1.25 A SB / 250 VAC |
| Max. required power | ≤ 2.1 W |
| Max. power dissipation | ≤ 1.7 W |
Isolation voltage |
|
| Test /working: Input to any | 2.6 kVAC / 300 VAC reinforced isolation |
| Analog output to supply | 2.6 kVAC / 300 VAC reinforced isolation |
| Status relay to supply | 1.5 kVAC / 150 VAC reinforced isolation |
Response time |
|
| Temperature input, programmable (0...90%, 100...10%) | 1...60 s |
| mA / V input (programmable) | 0.4...60 s |
Auxiliary supplies |
|
| 9116B1: 2-w. sup. (term. 54...52) | 28...16.5 VDC / 0...20 mA |
| 9116B2: 2-w. sup. (term. 54...52) | 21.4...16.5 VDC / 0...20 mA |
| Signal dynamics, input | 24 bit |
| Signal dynamics, output | 16 bit |
| Signal / noise ratio | Min. 60 dB (0...100 kHz) |
| Accuracy | Better than 0.1% of sel. range |
Input specifications
RTD input |
|
| RTD type | Pt10/20/50/100/200/250/300/Pt400/500/1000; Ni50/100/120/1000 |
| Cable resistance per wire | 50 Ω (max.) |
| Sensor current | Nom. 0.2 mA |
| Effect of sensor cable resistance (3-/4-wire) | < 0.002 Ω / Ω |
| Sensor error detection | Programmable ON / OFF |
| Short circuit detection | Yes |
TC input |
|
| Thermocouple type | B, E, J, K, L, N, R, S, T, U, W3, W5, LR |
| Cold junction compensation (CJC) via ext. sensor in 5910 | 20...28°C ≤ ±1°C, -20...20°C / 28...70°C ≤ 2°C |
| CJC via int. mounted sensor | ±(2.0°C + 0.4°C * Δt) |
| Δt = | Internal temp.-ambient temp. |
Current input |
|
| Measurement range | 0...23 mA |
| Programmable measurement ranges | 0...20 and 4...20 mA |
| Input resistance | Nom. 20 Ω + PTC 50 Ω |
| Sensor error detection | Loop break 4...20 mA |
Voltage input |
|
| Measurement range | 0...12 VDC |
| Programmable measurement ranges | 0/0.2...1, 0/1...5, 0/2...10 VDC |
| Input resistance | Nom. >10 MΩ |
Output specifications
Current output |
|
| Signal range | 0...23 mA |
| Programmable signal ranges | 0...20/4...20/20...0/20...4 mA |
| Load (@ current output) | ≤ 600 Ω |
| Load stability | ≤ 0.01% of span / 100 Ω |
| Sensor error indication | 0 / 3.5 / 23 mA / none |
| NAMUR NE43 Upscale/Downscale | 23 mA / 3.5 mA |
| Current limit | ≤ 28 mA |
Passive 2-wire mA output |
|
| Max. external 2-wire supply | 26 VDC |
| Max. load resistance [Ω] | (Vsupply-3.5)/0.023 A |
| Effect of external 2-wire supply voltage variation | < 0.005% of span / V |
Relay output |
|
| Relay functions | Setpoint, Window, Sensor error, Power and Off |
| Max. voltage | 250 VAC / VDC |
| Max. current | 2 A |
| Max. AC power | 500 VA |
| Max. DC current, resistive load ≤ 30 VDC | 2 ADC |
| Max. DC current, resistive load > 30 VDC | See manual for details |
Status relay |
|
| Max. voltage | 110 VDC / 125 VAC |
| Max. current | 0.3 ADC / 0.5 AAC |
| Max. AC power | 62.5 VA / 32 W |
Observed authority requirements
| EMC | 2014/30/EU |
| LVD | 2014/35/EU |
| RoHS | 2011/65/EU |
| EAC | TR-CU 020/2011 |
Approvals
| ATEX 2014/34/EU | KEMA 10ATEX0053 X |
| IECEx | KEM 10.0022X |
| FM | 3038267-C |
| INMETRO | DEKRA 16.0004 X |
| UL | UL 61010-1 |
| EAC Ex TR-CU 012/2011 | RU C-DK.GB08.V.00410 |
| DNV-GL Marine | Stand. f. Certific. No. 2.4 |
| ClassNK | TA18527M |
| SIL | SIL 2 certified & fully assessed acc. to IEC 61508 |
3405
Power connector unit
4501
Display / programming front
4511
Communication enabler
4590
ConfigMate
5910Ex
CJC connector
5913Ex
CJC connector
7007
2-digit digital potentiometer
7008
3-digit digital potentiometer
7009
10-turn potentiometer, 200 Ω
7011
Dial for 10-turn potentiometer
7012
1-turn potentiometer, 1 kΩ
7015
1-turn potentiometer, 10 kΩ
7020
Knob for 1-turn potentiometer
7020A
Knob for 10-turn potentiometer
7028
10-turn potentiometer, 2 kΩ
7423
Ceramic socket for Pt100 sensor
7430B
Pt100 cable sensor
7430C
Pt100 cable sensor
7440
Thermowell for PR 7400 Pt100 sensor
8510
8 unit 4511 Modbus cable
8511
4511 Y-splitter Modbus cable
8513
RJ45 Modbus termination
8514
3 X RJ45 female Y-splitter
8515
RJ45 female to female cable adapter
8516
RJ45 female to female shielded cable adabter
8517
3 x RJ45 female shielded Y-splitter
9400_1
Power rail 15 mm profile
9400_2
Power rail 7.5 mm profile
9402
Extra end covers for power rail
9404
Module stop
9410
Power control unit