3114
Isolated universal converter
- Input for RTD, TC, Ohm, potentiometer, mA and V
- 2-wire supply >15 V
- I.S. approvals: FM Div. 2, ATEX Zone 2, IECEx Zone 2
- Output for current and voltage
- Slimline housing of 6 mm
Advanced features
Programmable by way of detachable display front 4501 and ConfigMate 4590, process calibration, signal simulation, password protection, error diagnostics and help text available in several languages.
Applications
- Linearised, electronic temperature measurement with RTD or TC sensor.
- Conversion of linear resistance variation to a standard analog current / voltage signal, i.e. from solenoids and butterfly valves or linear movements with attached potentiometer.
- Power supply and signal isolator for 2-wire transmitters.
- Process control with standard analog output.
- Galvanic separation of analog signals and measurement of floating signals.
Technical characteristics
- When 3114 is used in combination with the 4501 display / programming front and ConfigMate 4590, all operational parameters can be modified to suit any application. As the 3114 is designed with electronic hardware switches, it is not necessary to open the device for setting of DIP-switches.
- A green front LED indicates normal operation and malfunction.
- Continuous check of vital stored data for safety reasons.
- 3-port 2.5 kVAC galvanic isolation.
Environmental Conditions
| Operating temperature | -25°C to +70°C |
| Storage temperature | -40°C to +85°C |
| Calibration temperature | 20...28°C |
| Relative humidity | < 95% RH (non-cond.) |
| Protection degree | IP20 |
| Installation in | Pollution degree 2 & meas. / overvoltage cat. II |
Mechanical specifications
| Dimensions (HxWxD) | 113 x 6.1 x 115 mm |
| Weight approx. | 70 g |
| DIN rail type | DIN EN 60715/35 mm |
| Wire size | 0.13 x 2.5 mm2 / AWG 26...12 stranded wire |
| Screw terminal torque | 0.5 Nm |
| Vibration | IEC 60068-2-6 |
| 2...25 Hz | ±1.6 mm |
| 25...100 Hz | ±4 g |
Common specifications
Supply |
|
| Supply voltage | 16.8...31.2 VDC |
| Fuse | 400 mA SB / 250 VAC |
| Max. required power | 1.20 W |
| Max. power dissipation | 0.65 W |
Isolation voltage |
|
| Isolation voltage, test / working | 2.5 kVAC / 300 VAC (reinforced) |
| Zone 2 / Div. 2 | 250 VAC |
Response time |
|
| Temperature input (0...90%, 100...10%) | ≤ 1 s |
| mA / V input (0...90%, 100...10%) | ≤ 400 ms |
| Signal / noise ratio | Min. 60 dB (0...100 kHz) |
| Signal dynamics, input | 24 bit |
| Signal dynamics, output | 16 bit |
| Programming | ConfigMate 4590 |
| Accuracy | Better than 0.1% of sel. range |
| EMC immunity influence | < ±0.5% of span |
| Extended EMC immunity: NAMUR NE21, A criterion, burst | < ±1% of span |
Input specifications
RTD input |
|
| RTD type | Pt10/20/50/100/200/250/300/Pt400/500/1000; Ni50/100/120/1000 |
| Cable resistance per wire | 50 Ω (max.) |
| Sensor current | Nom. 0.2 mA |
| Effect of sensor cable resistance (3-/4-wire) | < 0.002 Ω / Ω |
| Sensor error detection | Yes |
| Short circuit detection | < 15 Ω |
Linear resistance input |
|
| Linear resistance min....max. | 0 Ω...10000 Ω |
Potentiometer input |
|
| Potentiometer min....max. | 10 Ω...100 kΩ |
TC input |
|
| Thermocouple type | B, E, J, K, L, N, R, S, T, U, W3, W5, LR |
| CJC via int. mounted sensor | ±(2.0°C + 0.4°C * Δt) |
| Δt = | Internal temp.-ambient temp. |
| Sensor error detection | Yes |
| Sensor error current: When detecting / else | Nom. 2 μA / 0 μA |
Current input |
|
| Measurement range | 0...23 mA |
| Programmable measurement ranges | 0...20 and 4...20 mA |
| Input resistance | Nom. 20 Ω + PTC 50 Ω |
Voltage input |
|
| Measurement range | 0...12 VDC |
| Programmable measurement ranges | 0/0.2...1, 0/1...5, 0/2...10 VDC |
| Input resistance | Nom. 10 MΩ |
| 2-wire transmitter supply | > 15 V / 20 mA |
Output specifications
Current output |
|
| Signal range | 0...23 mA |
| Programmable signal ranges | 0...20/4...20/20...0/20...4 mA |
| Load (@ current output) | ≤ 600 Ω |
| Load stability | ≤ 0.01% of span / 100 Ω |
| Sensor error indication | 0 / 3.5 / 23 mA / none |
| NAMUR NE43 Upscale/Downscale | 23 mA / 3.5 mA |
| Current limit | ≤ 28 mA |
Voltage output |
|
| Signal range | 0...10 VDC |
| Programmable signal ranges | 0/0.2...1; 0/1...5 ; 0/2...10; 1...0.2/0; 5...1/0; 10...2/0 V |
| Load (@ voltage output) | ≥ 10 kΩ |
| of span | = of the currently selected measurement range |
I.S. / Ex marking
| ATEX | II 3 G Ex nA IIC T4 Gc |
| IECEx | Ex nA IIC T4 Gc |
| FM, US | Cl. I, Div. 2, Gp. A, B, C, D T4 or Cl. I, Zone 2, AEx nA IIC T4 |
| FM, CA | Cl. I, Div. 2, Gp. A, B, C, D T4 or Cl. I, Zone 2, Ex nA IIC T4 |
Observed authority requirements
| EMC | 2014/30/EU |
| LVD | 2014/35/EU |
| RoHS | 2011/65/EU |
| EAC | TR-CU 020/2011 |
Approvals
| ATEX 2014/34/EU | KEMA 10ATEX0147 X |
| IECEx | KEM 10.0068X |
| FM | FM17US0004X / FM17CA0003X |
| DNV-GL Marine | Stand. f. Certific. No. 2.4 |
| UL | UL 61010-1 |
| EAC Ex TR-CU 012/2011 | RU C-DK.GB08.V.00410 |
3405
Power connector unit
4501
Display / programming front
4590
ConfigMate
7423
Ceramic socket for Pt100 sensor
7430B
Pt100 cable sensor
7430C
Pt100 cable sensor
7440
Thermowell for PR 7400 Pt100 sensor
9400_1
Power rail 15 mm profile
9400_2
Power rail 7.5 mm profile
9402
Extra end covers for power rail
9404
Module stop
9410
Power control unit