Prodotti 0
9113A
 
 

9113A

 

Temperature / mA converter

 

  • Input for RTD, TC and mA
  • Active / passive mA output via the same two terminals
  • 1 or 2 channels
  • Can be supplied separately or installed on power rail, PR type 9400
  • SIL 2-certified via Full Assessment
  1. Overview +

  2. Technical details +

  3. Accessories +


Advanced features

  • Configuration and monitoring by way of detachable display front (PR 4511/4501); process calibration and signal simulation.
  • Copying of the configuration from one device to others of the same type via the display front.
  • TC inputs can use either the internal CJC or a terminal with a built-in Pt100 sensor (PR 5910, channel 1 / PR 5913, channel 2) for higher accuracy.
  • Advanced monitoring of internal communication and stored data.
  • SIL 2 functionality is optional and must be activated in a menu point.

Application

  • The device can be mounted in and receive signals from non-classified area and zone 2.
  • Conversion and scaling of temperature (Pt, Ni and TC) and active current signals.
  • 9113A has been designed, developed and certified for use in SIL 2 applications according to the requirements of IEC 61508.

Technical characteristics

  • 1 green and 2 red front LEDs indicate operation status and malfunction.
  • 2.6 kVAC galvanic isolation between input, output and supply.

Mounting

  • The devices can be mounted vertically or horizontally without distance between neighbouring units.

Environmental Conditions

Operating temperature -20°C to +60°C
Storage temperature -20°C to +85°C
Calibration temperature 20...28°C
Relative humidity < 95% RH (non-cond.)
Protection degree IP20
Installation in Pollution degree 2 & meas. / overvoltage cat. II

Mechanical specifications

Dimensions (HxWxD) 109 x 23.5 x 104 mm
Dimensions (HxWxD) w/ 4501/4511 109 x 23.5 x 116 / 131 mm
Weight approx. 250 g
Weight incl. 4501 / 4511 (approx.) 265 g / 280 g
DIN rail type DIN EN 60715/35 mm
Wire size 0.13...2.08 mm2 AWG 26...14 stranded wire
Screw terminal torque 0.5 Nm
Vibration IEC 60068-2-6
2...13.2 Hz ±1 mm
13.2...100 Hz ±0.7 g

Common specifications

Supply

Supply voltage 19.2...31.2 VDC
Max. required power ≤ 0.8 W/≤ 1.4 W (1 ch./2 ch.)
Max. power dissipation, 1 / 2 ch. ≤ 0.8 W / ≤ 1.4 W
Fuse 400 mA SB / 250 VAC

Isolation voltage

Test /working: Input to any 2.6 kVAC / 300 VAC reinforced isolation
Analog output to supply 2.6 kVAC / 300 VAC reinforced isolation
Status relay to supply 1.5 kVAC / 150 VAC reinforced isolation

Response time

Temperature input, programmable (0...90%, 100...10%) 1...60 s
mA / V input (programmable) 0.4...60 s
Programming PR 45xx
Signal / noise ratio Min. 60 dB (0...100 kHz)
Signal dynamics, input 24 bit
Signal dynamics, output 16 bit
Accuracy Better than 0.1% of sel. range
EMC immunity influence < ±0.5% of span
Extended EMC immunity: NAMUR NE21, A criterion, burst < ±1% of span

Input specifications

RTD input

RTD type Pt10/20/50/100/200/250/300/Pt400/500/1000; Ni50/100/120/1000
Cable resistance per wire 50 Ω (max.)
Sensor current Nom. 0.2 mA
Effect of sensor cable resistance (3-/4-wire) < 0.002 Ω / Ω
Sensor error detection Programmable ON / OFF

TC input

Thermocouple type B, E, J, K, L, N, R, S, T, U, W3, W5, LR
Cold junction compensation (CJC) via ext. sensor in 5910 20...28°C ≤ ±1°C, -20...20°C / 28...70°C ≤ 2°C
CJC via int. mounted sensor ±(2.0°C + 0.4°C * Δt)
Δt = Internal temp.-ambient temp.
Sensor error detection Programmable ON or OFF (only wire breakage)
Sensor error current: When detecting / else Nom. 2 μA / 0 μA

Current input

Measurement range 0...23 mA
Programmable measurement ranges 0...20 and 4...20 mA
Input resistance Nom. 20 Ω + PTC 50 Ω
Sensor error detection Programmable ON / OFF

Output specifications

Current output

Signal range 0...23 mA
Programmable signal ranges 0...20/4...20/20...0/20...4 mA
Load (@ current output) ≤ 600 Ω
Load stability ≤ 0.01% of span / 100 Ω
Sensor error indication 0 / 3.5 / 23 mA / none
NAMUR NE43 Upscale/Downscale 23 mA / 3.5 mA
Output limitation, on 4...20 and 20...4 mA signals 3.8...20.5 mA
Output limitation, on 0...20 and 20...0 mA signals 0...20.5 mA
Current limit ≤ 28 mA

Passive 2-wire mA output

Max. external 2-wire supply 26 VDC
Max. load resistance [Ω] (Vsupply-3.5)/0.023 A
Effect of external 2-wire supply voltage variation < 0.005% of span / V

Status relay

Max. voltage 110 VDC / 125 VAC
Max. current 0.3 ADC / 0.5 AAC
Max. AC power 62.5 VA / 32 W
of span = of the currently selected measurement range

Observed authority requirements

EMC 2014/30/EU
LVD 2014/35/EU
RoHS 2011/65/EU
EAC TR-CU 020/2011

Approvals

ATEX 2014/34/EU KEMA 07ATEX0148 X
IECEx KEM 09.0052X
UL UL 61010-1
DNV-GL Marine Stand. f. Certific. No. 2.4
ClassNK TA18527M
SIL SIL 2 certified & fully assessed acc. to IEC 61508
La vostra richiesta è stata inviata con successo - 0 Prodotti nella tua lista
Descrizione del prodotto Quantità
Si prega di specificare la variante (si veda il datasheet) – oppure indicare “variante sconosciuta”
I vostri contatti
Continua a navigare
Nessun prodotto aggiunto alla vostra lista…
Nessun prodotto nella vostra lista…

Mentre consultate le pagine sui prodotti presenti sul nostro sito web, avete la possibilità di aggiungere i nostri prodotti alla lista – ed inviarci tale lista per richiedere una quotazione. Per aggiungere i prodotti alla lista, cliccate sul pulsante “RICHIEDI UN PREVENTIVO” presente su ciascuna delle pagine sui prodotti.

Una volta inoltrata la lista, provvederemo a ricontattarvi quanto prima.

Se non desiderate inoltrare tale lista, essa rimarrà comunque visibile alla vostra attenzione sul sito web per 7 giorni (tramite “cookie” sul vostro PC o tablet)




Ci auguriamo troviate utili tali funzionalità. Si prega di andare alle pagine sui prodotti per aggiungere i nostri prodotti alla lista
Grazie per la vostra richiesta
Provvederemo quanto prima a ricontattarvi telefonicamente o via e-mail.