Artiklar 0
7908
 
 

7908

 

System 9000 backplane

 

  • Provides safe, easy wiring between the backplane and non I.S. automation systems using standard prefabricated I/O cables
  • Direct, Redundant and Duplicate signalling - including HART I/O
  • Robust, compact high-end design solution for 8 system 9000 units
  • Digital output and LEDs indicate backplane system status
  1. Overview +

  2. Technical details +


Application

  • The 7908 backplane is a compact and robust solution that enables a safe and easy connection of PR system 9000 IS device signals into standard automation systems.
  • Standard automation system cables and connectors are used to link the backplane to the I/O cards.
  • The backplane can be used for Direct, Redundant, Duplicate signalling including HART I/O System connectivity (HART MUX).
  • The system 9000 devices isolate and convert AI, AO, DI and DO signals coming from, or going to the I.S. classified area, and routes those signals to a system automation I/O card.
  • The system 9000 units maintain a SIL2/SIL3 level of functional safety, even when mounted in the backplane solution.

Technical characteristics

  • Robust, compact high-end design that holds 8 system 9000 units.
  • Digital output indicates status of the 9000 devices and primary/back-up power supplies.
  • Flexible 24 VDC supply voltage and redundant power supply connection solution.

Mounting / installation / programming

  • Flexible horizontal/vertical panel or wall mounting in the Safe or Zone 2 / Div 2 areas.
  • System 9000 devices easily snap ON and OFF using piano keys, and devices can be hot-swapped.
  • Tag number and ID labels are easily mounted and read by using the dedicated piano key spacer.
  • Wide temperature operation range: -20...+60°C.
  • Backplane selection guide can be found at www.prelectronics.com/backplane

Environmental Conditions

Operating temperature -20°C to +60°C
Storage temperature -40°C to +85°C
Relative humidity < 95% RH (non-cond.)
Installation in Pollution degree 2 & meas. / overvoltage cat. II

Mechanical specifications

Dimensions (HxWxD) 144 x 247 x 141 mm
Wire size 2.5 mm2 / AWG 12 (Supply 1 / 2 and status relay connectors)

Common specifications

Supply

Supply voltage 20...31.2 VDC (24 DC nom.)
Max. required power ≤ 30 W

Isolation voltage

Isolation voltage, test / working 500 VAC / 50 VAC (Basic isolation between supply 1 & 2 and status relay)
Replaceable fuses Fuse F1 & F2: 1.6 A SB, 250 V, type TR5

Output specifications

Status relay

Max. voltage 32 V (Zone 2 / Div. 2 area) 42 V (Safe area)
Max. current 100 mA (Zone 2 / Div. 2 area) 100 mA (Safe area)

Observed authority requirements

EMC 2014/30/EU
EAC TR-CU 020/2011

Approvals

UL UL 508 / C22.2 no. 14
ATEX 2014/34/EU DEKRA 13ATEX0136X
IECEx DEK 13.0044X
FM 0003049918-C
Din förfrågan har skickats. - 0 Artiklar på din lista
Produktbeskrivning Antal
Vänligen ange artikelnummer och ev. variant (se datablad för mer info) – eller ange “Artikelnummer okänt”
Er kontaktinformation
Bläddra vidare
Inga produkter har lagts till i listan…
Du har inga produkter på listan…

När du ser dig omkring bland produkterna på vår hemsida har ni möjlighet att lägga till produkter i en lista och skicka denna lista till oss och därmed begära en offert. Du kan lägga till produkter i listan genom att klicka på ”Få en enkel offert”- knappen på de enskilda produktsidorna.

När du har skickat listan kommer vi att återkoppla till dig så snart som möjligt.

Om du inte skickar listan kommer den att vara synlig på webbplatsen i 7 dagar (vi kommer att använda oss av ”cookies” på din dator eller surfplatta)

Vi hoppas att ni finner denna funktion användbar. Gå till produktsidorna för att lägga till produkter i din lista.
Tack för din förfrågan.
Vi kommer att återkoppla till dig via telefon eller e-mail så snart som möjligt.