Items 0
6350A
 

6350A

 

Profibus PA / Foundation Fieldbus transmitter

 

  • PROFIBUS PA ver. 3.0
  • FOUNDATION Fieldbus ver. ITK 4.6
  • Automatic switch between protocols
  • Basic or LAS capability with F.F.
  • 1- or 2-channel version
  1. Overview

  2. Technical details

  3. Accessories


Application

  • Linearized temperature measurement with RTD or TC sensor.
  • Difference, average or redundancy temperature measurement with RTD or TC sensor.
  • Converts analog mA signals into digital values on the bus communication.
  • Linear resistance, potentiometer and bipolar mV measurement.

Technical characteristics

  • Bus transmitter with both PROFIBUS PA and FOUNDATION Fieldbus communication. A unique switch function ensures automatic shift between the two protocols.
  • Set-up for PROFIBUS PA can be done via Siemens Simatic® PDM®, ABB Melody / Harmony and Metso DNA software and for FOUNDATION Fieldbus via Emerson DeltaV, Yokogawa CS 1000 / CS 3000, ABB Melody / Harmony and Honeywell Experion software.
  • Built-in simulation mode function.
  • Polarity-independent bus connection.
  • 24 bit A/D converter ensures high resolution.
  • PROFIBUS PA function blocks:
    2 analog.
  • FOUNDATION Fieldbus function blocks:
    2 analog and 1 PID.
  • FOUNDATION Fieldbus capability:
    Basic or LAS.

Mounting / installation

  • Mounted vertically or horizontally on a DIN rail. Using the 2-channel version up to 84 channels per meter can be mounted.

Environmental Conditions

Operating temperature -40°C to +85°C
Storage temperature -40°C to +85°C
Calibration temperature 20...28°C
Relative humidity < 95% RH (non-cond.)
Protection degree IP20

Mechanical specifications

Dimensions (HxWxD) 109 x 23.5 x 104 mm
Weight (1 / 2 channels) 145 / 185 g
DIN rail type DIN EN 60715/35 mm
Wire size 0.13...2.08 mm2 AWG 26...14 stranded wire
Screw terminal torque 0.5 Nm

Common specifications

Supply

Supply voltage 9.0...32 VDC
Power dissipation, per channel < 11 mA

Isolation voltage

Test voltage 1.5 kVAC for 60 s
Working voltage 50 VRMS / 75 VDC

Response time

Response time (programmable) 1...60 s
Warm-up time 30 s
Signal / noise ratio Min. 60 dB
Accuracy Better than 0.05% of selected range
Updating time < 400 ms
Execution time, PID controller < 200 ms
Execution time, analog input < 50 ms
Signal dynamics, input 24 bit
EMC immunity influence < ±0.1% of reading
Extended EMC immunity: NAMUR NE21, A criterion, burst < ±1% of reading

Input specifications

RTD input

RTD type Pt25…1000, Ni25…1000, Cu10…1000, lin. R, potentiometer
Cable resistance per wire 50 Ω (max.)
Sensor current Nom. 0.2 mA
Effect of sensor cable resistance (3-/4-wire) < 0.002 Ω / Ω
Sensor error detection Yes
Short circuit detection < 15 Ω

Linear resistance input

Linear resistance min....max. 0 Ω...10000 Ω

Potentiometer input

Potentiometer min....max. 10 Ω...100 kΩ

TC input

Thermocouple type B, E, J, K, L, N, R, S, T, U, W3, W5
Cold junction compensation (CJC) < ±0.5°C
Sensor error detection Yes
Sensor error current: When detecting / else Nom. 2 μA / 0 μA
Short circuit detection < 3 mV

Bipolar current input

Measurement range -100…+100 mA
Input resistance 10 Ω + PTC < 20 Ω
Cable breakage detection (4...20 mA) < 0.3 mA

Bipolar mV input

Measurement range -800…+800 mV
Min. measurement range (span) 2.5 mV
Input resistance 10 MΩ
Short circuit detection < 3 mV

Output specifications

PROFIBUS PA connection

PROFIBUS PA protocol Profile A&B, ver. 3.0
PROFIBUS PA protocol standard EN 50170 vol. 2
PROFIBUS PA address (at delivery) 126
PROFIBUS PA function blocks 2 analog

FOUNDATION Fieldbus connection

FOUNDATION Fieldbus protocol FF protocol
FOUNDATION Fieldbus protocol standard FF design specifications
FOUNDATION Fieldbus version ITK 4.6
FOUNDATION Fieldbus capability Basic or LAS
FOUNDATION Fieldbus function blocks 2 analog and 1 PID

Observed authority requirements

EMC 2014/30/EU
EAC TR-CU 020/2011

Approvals

ATEX 2014/34/EU KEMA 03ATEX1013 X
IECEx DEK 14.0071X
FM 3015609
CSA 1418937
Your request has been sent successfully. - 0 Items on your list
Product description Quantity
Please specify variant(s) (see data sheet) - or indicate ‘Variant unknown’
Your contact information
Continue browsing
No products added
You have no products on your list...

When browsing product pages on this website, you have the possibility to add products to a list - and send your list to us, thereby requesting a quotation.
You add products to the list by clicking the "GET A QUOTE" button on the individual product pages.

When you have submitted the list, we will get back to you as quickly as possible.

If you don't submit the list, it will be visible to you on the website for 7 days (we will place a so-called' cookie on your pc or tablet).

We hope you will find the functionality useful. Go to the product pages to add products to your list.
Thank you for your request for a quotation.
We will get back to you by phone or email as soon as possible.