Items 0
6350B
 
 

6350B

 

Profibus PA / Foundation Fieldbus transmitter

 

  • PROFIBUS PA ver. 3.0
  • FOUNDATION Fieldbus ver. ITK 4.6
  • Automatic switch between protocols
  • FISCO-certified
  • Basic or LAS capability with F.F.
  1. Overview +

  2. Technical details +

  3. Accessories +


Application

  • Linearized temperature measurement with RTD or TC sensor.
  • Converts analog mA signals into digital values on the bus communication.
  • Difference, average or redundancy temperature measurement with RTD or TC sensor.
  • Linear resistance, potentiometer and bipolar mV measurement.

Technical characteristics

  • Bus transmitter with both PROFIBUS PA and FOUNDATION™ Fieldbus communication. A unique switch function ensures automatic shift between the two protocols.
  • Set-up for PROFIBUS PA can be done via Siemens Simatic® PDM®, ABB Melody / Harmony and Metso DNA software and for FOUNDATION Fieldbus via Emerson DeltaV, Yokogawa CS 1000 / CS 3000, ABB Melody / Harmony and Honeywell Experion software.
  • Built-in simulation mode function.
  • Polarity-independent bus connection.
  • 24 bit A/D converter ensures high resolution.
  • PROFIBUS PA function blocks:
    2 analog.
  • FOUNDATION Fieldbus function blocks:
    2 analog and 1 PID.
  • FOUNDATION Fieldbus capability:
    Basic or LAS.

Mounting / installation

  • Mounted vertically or horizontally on a DIN rail. Using the 2-channel version up to 84 channels per meter can be mounted.

Environmental Conditions

  • Operating temperature

    -40°C to +85°C

  • Storage temperature

    -40°C to +85°C

  • Calibration temperature

    20...28°C

  • Relative humidity

    < 95% RH (non-cond.)

  • Protection degree

    IP20

Mechanical specifications

  • Dimensions (HxWxD)

    109 x 23.5 x 104 mm

  • Weight (1 / 2 channels)

    145 / 185 g

  • DIN rail type

    DIN EN 60715/35 mm

  • Wire size

    0.13...2.08 mm2 AWG 26...14 stranded wire

  • Screw terminal torque

    0.5 Nm

Common specifications

  • Supply

  • Supply voltage

    9.0...30 VDC

  • Power dissipation, per channel

    < 11 mA

  • Isolation voltage

  • Test voltage

    1.5 kVAC for 60 s

  • Working voltage

    50 VRMS / 75 VDC

  • Response time

  • Response time (programmable)

    1...60 s

  • Warm-up time

    30 s

  • Signal / noise ratio

    Min. 60 dB

  • Accuracy

    Better than 0.05% of selected range

  • Updating time

    < 400 ms

  • Execution time, PID controller

    < 200 ms

  • Execution time, analog input

    < 50 ms

  • Signal dynamics, input

    24 bit

  • EMC immunity influence

    < ±0.1% of reading

  • Extended EMC immunity: NAMUR NE21, A criterion, burst

    < ±1% of reading

Input specifications

  • RTD input

  • RTD type

    Pt25…1000, Ni25…1000, Cu10…1000, lin. R, potentiometer

  • Cable resistance per wire

    50 Ω (max.)

  • Sensor current

    Nom. 0.2 mA

  • Effect of sensor cable resistance (3-/4-wire)

    < 0.002 Ω / Ω

  • Sensor error detection

    Yes

  • Short circuit detection

    < 15 Ω

  • Linear resistance input

  • Linear resistance min....max.

    0 Ω...10000 Ω

  • Potentiometer input

  • Potentiometer min....max.

    10 Ω...100 kΩ

  • TC input

  • Thermocouple type

    B, E, J, K, L, N, R, S, T, U, W3, W5

  • Cold junction compensation (CJC)

    < ±0.5°C

  • Sensor error detection

    Yes

  • Sensor error current: When detecting / else

    Nom. 2 μA / 0 μA

  • Short circuit detection

    < 3 mV

  • Bipolar current input

  • Measurement range

    -100…+100 mA

  • Input resistance

    10 Ω + PTC < 20 Ω

  • Cable breakage detection (4...20 mA)

    < 0.3 mA

  • Bipolar mV input

  • Measurement range

    -800…+800 mV

  • Min. measurement range (span)

    2.5 mV

  • Input resistance

    10 MΩ

  • Short circuit detection

    < 3 mV

Output specifications

  • PROFIBUS PA connection

  • PROFIBUS PA protocol

    Profile A&B, ver. 3.0

  • PROFIBUS PA protocol standard

    EN 50170 vol. 2

  • PROFIBUS PA address (at delivery)

    126

  • PROFIBUS PA function blocks

    2 analog

  • FOUNDATION Fieldbus connection

  • FOUNDATION Fieldbus protocol

    FF protocol

  • FOUNDATION Fieldbus protocol standard

    FF design specifications

  • FOUNDATION Fieldbus version

    ITK 4.6

  • FOUNDATION Fieldbus capability

    Basic or LAS

  • FOUNDATION Fieldbus function blocks

    2 analog and 1 PID

Approvals

  • ATEX 2014/34/EU

    KEMA 03ATEX1013 X

  • IECEx

    DEK 14.0071X

  • FM

    3015609

  • CSA

    1418937

  • EAC Ex TR-CU 012/2011

    RU C-DK.GB08.V.00410

Your request has been sent successfully. - 0 Items on your list
Product description Quantity
Please specify variant(s) (see data sheet) - or indicate ‘Variant unknown’
Your contact information
Continue browsing
No products added
You have no products on your list...

When browsing product pages on this website, you have the possibility to add products to a list - and send your list to us, thereby requesting a quotation.
You add products to the list by clicking the "GET A QUOTE" button on the individual product pages.

When you have submitted the list, we will get back to you as quickly as possible.

If you don't submit the list, it will be visible to you on the website for 7 days (we will place a so-called' cookie on your pc or tablet).

We hope you will find the functionality useful. Go to the product pages to add products to your list.
Thank you for your request for a quotation.
We will get back to you by phone or email as soon as possible.