Items 0
9113A
 

9113A

 

Temperature / mA converter

 

  • Input for RTD, TC and mA
  • Active / passive mA output via the same two terminals
  • 1 or 2 channels
  • Can be supplied separately or installed on power rail, PR type 9400
  • SIL 2-certified via Full Assessment
  1. Overview

  2. Technical details

  3. Accessories


Advanced features

  • Configuration and monitoring by way of detachable display front (PR 4511/4501); process calibration and signal simulation.
  • Copying of the configuration from one device to others of the same type via the display front.
  • TC inputs can use either the internal CJC or a terminal with a built-in Pt100 sensor (PR 5910, channel 1 / PR 5913, channel 2) for higher accuracy.
  • Advanced monitoring of internal communication and stored data.
  • SIL 2 functionality is optional and must be activated in a menu point.

Application

  • The device can be mounted in and receive signals from non-classified area and zone 2.
  • Conversion and scaling of temperature (Pt, Ni and TC) and active current signals.
  • 9113A has been designed, developed and certified for use in SIL 2 applications according to the requirements of IEC 61508.

Technical characteristics

  • 1 green and 2 red front LEDs indicate operation status and malfunction.
  • 2.6 kVAC galvanic isolation between input, output and supply.

Mounting

  • The devices can be mounted vertically or horizontally without distance between neighbouring units.

Environmental Conditions

Operating temperature -20°C to +60°C
Storage temperature -20°C to +85°C
Calibration temperature 20...28°C
Relative humidity < 95% RH (non-cond.)
Protection degree IP20
Installation in Pollution degree 2 & measurement / overvoltage cat. II

Mechanical specifications

Dimensions (HxWxD) 109 x 23.5 x 104 mm
Dimensions (HxWxD) w/ 4501 / 4511 109 x 23.5 x 116 / 131 mm
Weight approx. 250 g
Weight incl. 4501 / 4511 (approx.) 265 g / 350 g
DIN rail type DIN EN 60715/35 mm
Wire size 0.13...2.08 mm2 AWG 26...14 stranded wire
Screw terminal torque 0.5 Nm
Vibration IEC 60068-2-6
2...13.2 Hz ±1 mm
13.2...100 Hz ±0.7 g

Common specifications

Supply

Supply voltage 19.2...31.2 VDC
Max. required power ≤ 0.8 W / ≤ 1.4 W (1 ch. / 2 ch.)
Max. power dissipation, 1 / 2 ch. ≤ 0.8 W / ≤ 1.4 W
Fuse 400 mA SB / 250 VAC

Isolation voltage

Test /working: Input to any 2.6 kVAC / 300 VAC reinforced isolation
Analog output to supply 2.6 kVAC / 300 VAC reinforced isolation
Status relay to supply 1.5 kVAC / 150 VAC reinforced isolation

Response time

Temperature input, programmable (0...90%, 100...10%) 1...60 s
mA / V input (programmable) 0.4...60 s
Programming Communication enabler 4511 / Programming front 4501
Signal / noise ratio Min. 60 dB (0...100 kHz)
Signal dynamics, input 24 bit
Signal dynamics, output 16 bit
Accuracy Better than 0.1% of selected range
EMC immunity influence < ±0.5% of span
Extended EMC immunity: NAMUR NE21, A criterion, burst < ±1% of span

Input specifications

RTD input

RTD type Pt10/20/50/100/200/250/300/Pt400/500/1000; Ni50/100/120/1000
Cable resistance per wire (max.) 50 Ω
Sensor current Nom. 0.2 mA
Effect of sensor cable resistance (3-/4-wire) < 0.002 Ω / Ω
Sensor error detection Programmable ON / OFF

TC input

Thermocouple type B, E, J, K, L, N, R, S, T, U, W3, W5, LR
Cold junction compensation (CJC) via ext. sensor in connector 5910 20...28°C ≤ ±1°C, -20...20°C / 28...70°C ≤ 2°C
CJC via internally mounted sensor ±(2.0°C + 0.4°C * Δt)
Δt = Internal temp.-ambient temp.
Sensor error detection Programmable ON or OFF (only wire breakage)
Sensor error current: When detecting / else Nom. 2 μA / 0 μA

Current input

Measurement range 0...23 mA
Programmable measurement ranges 0...20 and 4...20 mA
Input resistance Nom. 20 Ω + PTC 50 Ω
Sensor error detection Programmable ON / OFF

Output specifications

Current output

Signal range 0...23 mA
Programmable signal ranges 0...20/4...20/20...0/20...4 mA
Load (@ current output) ≤ 600 Ω
Load stability ≤ 0.01% of span / 100 Ω
Sensor error indication 0 / 3.5 / 23 mA / none
NAMUR NE43 Upscale/Downscale 23 mA / 3.5 mA
Output limitation, on 4...20 and 20...4 mA signals 3.8...20.5 mA
Output limitation, on 0...20 and 20...0 mA signals 0...20.5 mA
Current limit ≤ 28 mA

Passive 2-wire mA output

Max. external 2-wire supply 26 VDC
Max. load resistance [Ω] (Vsupply-3.5)/0.023 A
Effect of external 2-wire supply voltage variation < 0.005% of span / V

Status relay

Max. voltage 110 VDC / 125 VAC
Max. current 0.3 ADC / 0.5 AAC
Max. AC power 62.5 VA / 32 W
*of span = of the currently selected measurement range

Observed authority requirements

EMC 2014/30/EU
LVD 2014/35/EU
RoHS 2011/65/EU
EAC TR-CU 020/2011

Approvals

UL UL 61010-1
DNV-GL Marine Stand. f. Certific. No. 2.4
SIL SIL 2 certified & fully assessed acc. to IEC 61508
Your request has been sent successfully. - 0 Items on your list
Product description Quantity
Please specify variant(s) (see data sheet) - or indicate ‘Variant unknown’
Your contact information
Continue browsing
No products added
You have no products on your list...

When browsing product pages on this website, you have the possibility to add products to a list - and send your list to us, thereby requesting a quotation.
You add products to the list by clicking the "GET A QUOTE" button on the individual product pages.

When you have submitted the list, we will get back to you as quickly as possible.

If you don't submit the list, it will be visible to you on the website for 7 days (we will place a so-called' cookie on your pc or tablet).

We hope you will find the functionality useful. Go to the product pages to add products to your list.
Thank you for your request for a quotation.
We will get back to you by phone or email as soon as possible.