2-wire transmitter with HART protocol
5337D
- RTD, TC, Ohm, and bipolar mV input
- 2 analog inputs and 5 device variables with status available
- HART protocol revision selectable from HART 5 or HART 7
- Hardware assessed for use in SIL applications
- Mounting in hazardous gas and dust area
Application
- Linearized temperature measurement with TC and RTD sensors e.g. Pt100 and Ni100.
- HART communication and 4...20 mA analog PV output for individual, difference or average temperature measurement of up to two RTD or TC input sensors.
- Conversion of linear resistance to a standard analog current signal, e.g from valves or Ohmic level sensors.
- Amplification of bipolar mV signals to standard 4...20 mA current signals.
- Up to 63 transmitters (HART 7) can be connected in a multidrop communication setup.
Technical characteristics
- HART protocol revision can be changed by user configuration to either HART 5 or HART 7 protocol.
- The HART 7 protocol offers:
∙ Long Tag numbers of up to 32 characters.
∙ Enhanced Burst Mode and Event notification with time stamping.
∙ Device variable and status mapping to any dynamic variable PV, SV, TV or QV.
∙ Process signal trend measurement with logs and summary data.
∙ Automatic event notification with time stamps.
∙ Command aggregation for higher communication efficiency. - 5337D is designed according to strict safety requirements and is therefore suitable for applications in SIL installations.
- Continuous check of vital stored data.
- Meeting the NAMUR NE 21 recommendations, the 5337 HART transmitter ensures top measurement performance in harsh EMC environments. Additionally, the 5337D meets NAMUR NE43 and NE89 recommendations.
Mounting / installation
- For DIN form B sensor head mounting.
- Configuration via standard HART communication interfaces or by PR 5909 Loop Link.
Data sheet & Manuals
Data sheet
- 5337D.pdf
- Latest version
Manuals
- 5337V109_UK.pdf
- 5337V108_UK.pdf
- 5337V107_UK.pdf
- 5337V106_UK.pdf
- 5337V105_UK.pdf
- 5337V104_UK.pdf
- 5337V103_UK.pdf
- 5337V102_UK.pdf
- 5337V100_UK.pdf
- Previous versions
- Latest version
Manuals in Russian
- 5337V109_RU.pdf
- 5337V108_RU.pdf
- 5337V107_RU.pdf
- 5337V106_RU.pdf
- 5337V105_RU.pdf
- 5337V104_RU.pdf
- 5337V103_RU.pdf
- 5337V102_RU.pdf
- Previous versions
- Latest version
Approvals & Certificates
ATEX certificate
- 5337D_20ATEX0108X_issue0.pdf
- 5337D_03ATEX1537_issue11.pdf
- 5337D_03ATEX1537_issue10.pdf
- 5337D_03ATEX1537_issue09.pdf
- Previous versions
- Latest version
IECEx certificate
- 5337DIEC_200063X_issue0.pdf
- 5337DIEC_100083X_issue04.pdf
- 5337DIEC_100083X_issue03.pdf
- 5337DIEC_100083X_issue02.pdf
- 5337DIEC_100083X_issue01.pdf
- Previous versions
- Latest version
CSA certificate
- 533x_633x_CSA.pdf
- Latest version
FM certificate
- 53xx_633x_FM17US0013X.pdf
- Latest version
INMETRO certificate
- INMETRO_5335_5337_6335_6337_230011X_issue0.pdf
- INMETRO_5335_5337_180002X_issue1.pdf
- INMETRO_5335_5337_180002X_issue0.pdf
- Previous versions
- Latest version
DNV marine certificate
- DNV_2231_41xx_51xx_53xx.pdf
- Latest version
EAC declaration
- EAC_EMC_declaration_Ex_3000_5000_6000_9000.pdf
- Latest version
EAC declaration
- EAC_Ex.pdf
- Latest version
Metrology Pattern Approval (MPA), Belarus
- MPA_Belarus.pdf
- Latest version
Metrology Pattern Approval (MPA), Kazakhstan
- MPA_Kazakhstan.pdf
- Latest version
Metrology Pattern Approval (MPA), Russia
- MPA_Russia.pdf
- Latest version
Supplementary documentation
EU Declaration of Conformity
- 5337DoC_EU_106_UK.pdf
- 5337DoC_EU_105_UK.pdf
- 5337DoC_EU_104_UK.pdf
- 5337DoC_EU_103_UK.pdf
- 5337DoC_EU_102_UK.pdf
- 5337DoC_EU_101_UK.pdf
- 5337DoC_EU_100_UK.pdf
- Previous versions
- Latest version
UKCA Declaration of Conformity
- 5337DoC_UKCA_100_UK.pdf
- Latest version
CCC statement
- 5000_6000_series_CCC_statement.pdf
- Latest version
FMEDA report
- FMEDA_5337_R026V3R2.pdf
- FMEDA_5337_R026V3R1.pdf
- FMEDA_5337_R026V1R0.pdf
- Previous versions
- Latest version
SIL declaration
- 5335_6335_5337_6337_7501_SIL1_declaration_Potmeter_V2.pdf
- 5335_6335_5337_6337_7501_SIL2_declaration_V2.pdf
HART certificate
- 5337_HART.pdf
- Latest version
PR default configurations
- PR_default_configurations.pdf
- Latest version
Safety note
Safety note
Order form
Environmental Conditions
Operating temperature | -40°C to +85°C |
Calibration temperature | 20...28°C |
Relative humidity | < 95% RH (non-cond.) |
Protection degree (encl./terminal) | IP68 / IP00 |
Mechanical specifications
Dimensions | Ø 44 x 20.2 mm |
Weight approx. | 50 g |
Wire size | 1 x 1.5 mm2 stranded wire |
Screw terminal torque | 0.4 Nm |
Vibration | IEC 60068-2-6 |
2...25 Hz | ±1.6 mm |
25...100 Hz | ±4 g |
Common specifications
Supply |
|
Supply voltage | 8.0...30 VDC |
Isolation voltage |
|
Isolation voltage, test / working | 1.5 kVAC / 50 VAC |
Response time |
|
Response time (programmable) | 1...60 s |
Voltage drop | 8.0 VDC |
Programming | Loop Link & HART |
Signal / noise ratio | > 60 dB |
Accuracy | Better than 0.05% of selected range |
Signal dynamics, input | 22 bit |
Signal dynamics, output | 16 bit |
EMC immunity influence | < ±0.1% of span |
Extended EMC immunity: NAMUR NE21, A criterion, burst | < ±1% of span |
Input specifications
Common input specifications |
|
Max. offset | 50% of selected max. value |
RTD input |
|
RTD type | Pt50/100/200/500/1000; Ni50/100/120/1000 |
Cable resistance per wire | 5 Ω (up to 50 Ω per wire is possible with reduced measurement accuracy) |
Sensor current | Nom. 0.2 mA |
TC input |
|
Thermocouple type | B, E, J, K, L, N, R, S, T, U, W3, W5, LR |
Cold junction compensation (CJC) | Constant, internal or external via a Pt100 or Ni100 sensor |
Voltage input |
|
Measurement range | -800...+800 mV |
Min. measurement range (span) | 2.5 mV |
Input resistance | 10 MΩ |
Output specifications
Current output |
|
Signal range | 4…20 mA |
Min. signal range | 16 mA |
Load (@ current output) | ≤ (Vsupply - 8) / 0.023 [Ω] |
Sensor error indication | Programmable 3.5…23 mA |
NAMUR NE43 Upscale/Downscale | 23 mA / 3.5 mA |
Common output specifications |
|
Updating time | 440 ms |
HART protocol revisions | HART 7 and HART 5 |
I.S. / Ex marking
ATEX | II 1 G Ex ia IIC T6...T4 Ga, II 2 D Ex ia IIIC Db, I M1 Ex ia I Ma |
IECEx | Ex ia IIC T6...T4 Ga, Ex ia IIIC Db, Ex ia I Ma |
FM, US | Cl. I, Div. 1, Gp. A, B, C, D T4/T6; Cl. I Zone 0, AEx ia IIC T4/T6; Cl. 1, Div. 2, Gp. A, B, C, D, T4/T6 |
CSA | Cl. I, Div. 1, Gp. A, B, C, D Ex ia IIC, Ga |
INMETRO | Ex ia IIC T6...T4 Ga, Ex ia IIIC Db, Ex ia I Ma |
Observed authority requirements
EMC | 2014/30/EU & UK SI 2016/1091 |
ATEX | 2014/34/EU & UK SI 2016/1107 |
RoHS | 2011/65/EU & UK SI 2012/3032 |
EAC | TR-CU 020/2011 |
EAC Ex | TR-CU 012/2011 |
Approvals
DNV Marine | TAA0000101 |
ATEX | DEKRA 20ATEX0108X |
IECEx | DEK 20.0063X |
FM | FM17US0013X |
CSA | 1125003 |
INMETRO | DEKRA 23.0011X |
EAC Ex | EAEU KZ 7500361.01.01.08756 |
SIL | Hardware assessed for use in SIL applications |
Need support to select the right product for your application?
Our sales engineers are ready to help specify the right device to meet your needs.
Reach out by phone to get in touch with us straight away – or use the contact form or quick quote function to send your RFQ directly from the website. You’ll get a response within 24 hours on normal business days.
You can expect to get a confirmed delivery date via email within 2 days after we have received your order.
As soon as your package leaves our warehouse, you’ll receive tracking details via email. And if you have any questions along the way we’re just a phone call or email away.
State-of-the-art manufacturing Our 8,500 sqm integrated and automated manufacturing campus in Denmark covers the entire value-chain from design and development to manufacturing. It allows us to design and optimize for testing and manufacturing thereby constantly driving quality up and costs down. |
Dedicated Presale / Aftersales
|
Product reliability |
Product deployment
|
Smart products
Check out our range of communication interfaces
|