2-wire HART transmitter

 

  • 1- or 2-channel converter for RTD, TC, Ohm, and bipolar mV signals
  • 2 analogue inputs and 5 device variables with status available
  • HART protocol revision selectable from HART 5 or HART 7
  • Hardware assessed for use in SIL applications
  • Mounting on a DIN rail in Safe Area or Zone 2/22
  1. Overview +

  2. Technical details +

  3. Accessories +


Application

  • Linearized temperature measurement with TC and RTD sensors e.g. Pt100 and Ni100.
  • HART communication and 4...20 mA analog PV output for individual, difference or average temperature measurement of up to two RTD or TC input sensors.
  • Conversion of linear resistance to a standard analog current signal, e.g from valves or Ohmic level sensors.
  • Amplification of bipolar mV signals to standard 4...20 mA current signals.
  • Up to 63 transmitters (HART 7) can be connected in a multidrop communication setup.

Technical characteristics

  • HART protocol revision can be changed by user configuration to either HART 5 or HART 7 protocol.
  • The HART 7 protocol offers:
    ∙ Long Tag numbers of up to 32 characters.
    ∙ Enhanced Burst Mode and Event notification with time stamping.
    ∙ Device variable and status mapping to any dynamic variable PV, SV, TV or QV.
    ∙ Process signal trend measurement with logs and summary data.
    ∙ Automatic event notification with time stamps.
    ∙ Command aggregation for higher communication efficiency.
  • 6337A is designed according to strict safety requirements and is therefore suitable for applications in SIL installations.
  • Continuous check of vital stored data.
  • Meeting the NAMUR NE21 recommendations, the 6337A HART transmitter ensures top measurement performance in harsh EMC environments. Additionally, the 6337A meets NAMUR NE43 and NE89 recommendations.

Mounting / installation

  • DIN rail mounting with up to 84 channels per meter.
  • Configuration via standard HART communication interfaces or by PR 5909 Loop Link.

Environmental Conditions

  • Operating temperature

    -40°C to +85°C

  • Storage temperature

    -40°C to +85°C

  • Calibration temperature

    20...28°C

  • Relative humidity

    < 95% RH (non-cond.)

  • Protection degree

    IP20

Mechanical specifications

  • Dimensions (HxWxD)

    109 x 23.5 x 104 mm

  • Weight (1 / 2 channels)

    150 / 200 g

  • DIN rail type

    DIN EN 60715/35 mm

  • Wire size

    0.13...2.08 mm2 AWG 26...14 stranded wire

  • Screw terminal torque

    0.5 Nm

Common specifications

  • Supply

  • Supply voltage

    8.0...35 VDC

  • Isolation voltage

  • Isolation voltage, test / working

    1.5 kVAC / 50 VAC

  • Response time

  • Response time (programmable)

    1...60 s

  • Voltage drop

    8.0 VDC

  • Signal / noise ratio

    > 60 dB

  • Accuracy

    Better than 0.05% of selected range

  • EMC immunity influence

    < ±0.1% of span

  • Extended EMC immunity: NAMUR NE21, A criterion, burst

    < ±1% of span

Input specifications

  • Common input specifications

  • Max. offset

    50% of selected max. value

  • RTD input

  • RTD type

    Pt50/100/200/500/1000; Ni50/100/120/1000

  • Cable resistance per wire

    5 Ω (up to 50 Ω per wire is possible with reduced measurement accuracy)

  • Sensor current

    Nom. 0.2 mA

  • Linear resistance input

  • Linear resistance min....max.

    0 Ω...7000 Ω

  • TC input

  • Thermocouple type

    B, E, J, K, L, N, R, S, T, U, W3, W5

  • Cold junction compensation (CJC)

    Constant, internal or external via a Pt100 or Ni100 sensor

  • Voltage input

  • Measurement range

    -800...+800 mV

  • Min. measurement range (span)

    2.5 mV

  • Input resistance

    10 MΩ

Output specifications

  • Current output

  • Signal range

    4…20 mA

  • Min. signal range

    16 mA

  • Load (@ current output)

    ≤ (Vsupply - 8) / 0.023 [Ω]

  • Sensor error indication

    Programmable 3.5…23 mA

  • NAMUR NE43 Upscale/Downscale

    23 mA / 3.5 mA

  • Common output specifications

  • Updating time

    440 ms

  • HART protocol revisions

    HART 7 and HART 5

Observed authority requirements

  • EMC

    2014/30/EU

  • EAC

    TR-CU 020/2011

Approvals

  • ATEX 2014/34/EU

    KEMA 10ATEX0006 X

  • IECEx

    KEM 10.0084X

  • SIL

    Hardware assessed for use in SIL applications

Your request has been sent successfully. - 0 Items on your list
Product description Quantity
Please specify variant(s) (see data sheet) - or indicate ‘Variant unknown’
Your contact information
Continue browsing
No products added
You have no products on your list...

When browsing product pages on this website, you have the possibility to add products to a list - and send your list to us, thereby requesting a quotation.
You add products to the list by clicking the "GET A QUOTE" button on the individual product pages.

When you have submitted the list, we will get back to you as quickly as possible.

If you don't submit the list, it will be visible to you on the website for 7 days (we will place a so-called' cookie on your pc or tablet).

We hope you will find the functionality useful. Go to the product pages to add products to your list.
Thank you for your request for a quotation.
We will get back to you by phone or email as soon as possible.