Items 0
4116
 

4116

 

Universal transmitter

 

  • Input for RTD, TC, Ohm, potentiometer, mA and V
  • 2-wire supply > 16 V
  • FM-approved for installation in Div. 2
  • Output for current, voltage and 2 relays
  • Universal AC or DC supply
  1. Overview

  2. Technical details

  3. Accessories


Advanced features

  • Programmable via detachable display front (4501), process calibration, signal and relay simulation, password protection, error diagnostics and selection of help text in several languages.

Application

  • Linearized, electronic temperature measurement with RTD or TC sensor.
  • Conversion of linear resistance variation to a standard analog current / voltage signal, i.e. from solenoids and butterfly valves or linear movements with attached potentiometer.
  • Power supply and signal isolator for 2-wire transmitters.
  • Process control with 2 pairs of potential-free relay contacts and analog output.
  • Galvanic separation of analog signals and measurement of floating signals.
  • The 4116 is designed according to strict safety requirements and is therefore suitable for application in SIL 2 installations.

Technical characteristics

  • When 4116 is used in combination with the 4501 display / programming front, all operational parameters can be modified to suit any application. As the 4116 is designed with electronic hardware switches, it is not necessary to open the device for setting of DIP-switches.
  • A green / red front LED indicates normal operation and malfunction. A yellow LED is ON for each active output relay.
  • Continuous check of vital stored data for safety reasons.
  • 4-port 2.3 kVAC galvanic isolation.

Data sheet


Declaration of Conformity


Modbus configuration manual


4801 Gateway manual


Russian manual


UL certificate


FM certificate


DNV marine certificate


DNV EU-RO marine approval


SIL certificate


FMEDA report


EAC certificate


Environmental Conditions

Operating temperature -20°C to +60°C
Storage temperature -20°C to +85°C
Calibration temperature 20...28°C
Relative humidity < 95% RH (non-cond.)
Protection degree IP20

Mechanical specifications

Dimensions (HxWxD) 109 x 23.5 x 104 mm
Dimensions (HxWxD) w/ 4501 / 4511 109 x 23.5 x 116 / 131 mm
Weight approx. 170 g
Weight incl. 4501 / 4511 (approx.) 185 g / 270 g
Wire size 1 x 2.5 mm2 stranded wire
Screw terminal torque 0.5 Nm
Vibration IEC 60068-2-6
2...13.2 Hz ±1 mm
13.2...100 Hz ±0.7 g

Common specifications

Supply

Supply voltage, universal 21.6...253 VAC, 50...60 Hz or 19.2...300 VDC
Max. required power ≤ 2.5 W

Isolation voltage

Isolation voltage, test / working 2.3 kVAC / 250 VAC

Response time

Temperature input (0...90%, 100...10%) ≤ 1 s
mA / V input (0...90%, 100...10%) ≤ 400 ms

Auxiliary supplies

2-w. supply (term. 44...43) 25...16 VDC / 0...20 mA
Fuse 400 mA SB / 250 VAC
Programming Communication enabler 4511 / Programming front 4501
Signal / noise ratio Min. 60 dB (0...100 kHz)
Accuracy Better than 0.1% of selected range
EMC immunity influence < ±0.5% of span
Extended EMC immunity: NAMUR NE 21, A criterion, burst < ±1% of span

Input specifications

RTD input

RTD type Pt10, Pt20, Pt50, Pt100, Pt200, Pt250, Pt300, Pt400, Pt500, Pt1000 Ni50, Ni100, Ni120, Ni1000, Cu10, Cu20, Cu50, Cu100
Cable resistance per wire (max.) 50 Ω
Sensor current Nom. 0.2 mA
Effect of sensor cable resistance (3-/4-wire) < 0.002 Ω / Ω
Sensor error detection Yes
Short circuit detection < 15 Ω

Linear resistance input

Linear resistance min....max. 0 Ω...10000 Ω

Potentiometer input

Potentiometer min....max. 10 Ω...100 kΩ

TC input

Thermocouple type B, E, J, K, L, N, R, S, T, U, W3, W5, LR
Cold junction compensation (CJC) via ext. sensor in connector 5910 20...28°C ≤ ±1°C, -20...20°C / 28...70°C ≤ 2°C
CJC via internally mounted sensor ±(2.0°C + 0.4°C * Δt)
Δt = Internal temperature-ambient temperature
Sensor error detection Yes
Sensor error current: When detecting / else Nom. 2 μA / 0 μA

Current input

Measurement range 0...20 mA
Programmable measurement ranges 0...20 and 4...20 mA
Input resistance Nom. 20 Ω + PTC 50 Ω
Sensor error detection: Loop break 4...20 mA Yes

Voltage input

Measurement range 0...12 VDC
Programmable measurement ranges 0/0.2...1, 0/1...5, 0/2...10 VDC
Input resistance Nom. 10 MΩ

Output specifications

Current output

Signal range 0...20 mA
Programmable signal ranges 0...20 / 4...20 / 20...0 and 20...4 mA
Load (@ current output) ≤ 800 Ω
Load stability ≤ 0.01% of span / 100 Ω
Sensor error indication 0 / 3.5 / 23 mA / none
NAMUR NE 43 Upscale/Downscale 23 mA / 3.5 mA
Output limitation, on 4...20 and 20...4 mA signals 3.8...20.5 mA
Output limitation, on 0...20 and 20...0 mA signals 0...20.5 mA
Current limit ≤ 28 mA

Voltage output

Signal range 0...10 VDC
Programmable signal ranges 0/0.2...1; 0/1...5 ; 0/2...10; 1...0.2/0; 5...1/0; 10...2/0 V
Load (@ voltage output) ≥ 500 kΩ

Relay output

Relay functions Setpoint, Window, Sensor error, Latch, Power and Off
Max. voltage 250 VRMS
Max. current 2 AAC or 1 ADC
Max. AC power 500 VA

Observed authority requirements

EMC 2014/30/EU
LVD 2014/35/EU

Approvals

FM 3025177
UL UL 508
EAC TR-CU 020/2011
DNV-GL Marine Stand. f. Certific. No. 2.4
EU RO Mutual Recognition Type Approval MRA000000Z
SIL Hardware assessed for use in SIL applications
Your Request Has Been Sent Successfully. - 0 Items on your list
Product description Quantity
Please specify variant(s) (see data sheet) - or indicate ‘Variant unknown’
Your contact information
Continue browsing
No products added
You have no products on your list...

When browsing product pages on this website, you have the possibility to add products to a list - and send your list to us, thereby requesting a quotation.
You add products to the list by clicking the "GET A QUOTE" button on the individual product pages.

When you have submitted the list, we will get back to you as quickly as possible.

If you don't submit the list, it will be visible to you on the website for 7 days (we will place a so-called' cookie on your pc or tablet).

We hope you will find the functionality useful. Go to the product pages to add products to your list.
Thank you for your request for a quotation.
We will get back to you by phone or email as soon as possible.