Ex power supply
PR 5420B
- 2 channels
- 5-port 3.75 kVAC galvanic isolation
- Output voltage > 18 V to I.S. area
- Active current loop detection
- Universal supply by AC or DC
Application
- Voltage supply with safety barrier for the supply of equipment mounted in hazardous area.
- Voltage supply with failsafe detection of active current loop from 2-wire transmitters mounted in hazardous area.
Technical characteristics
- PR5420B has a relay with change-over contacts available in the safe area. When the loop current is within the defined limit, the relay is ON.
- Supply and outputs are floating and galvanically separated.
Mounting / installation
- Mounted vertically or horizontally on a DIN rail. Up to 84 channels per meter can be mounted.
Note
- Not suitable for new installations requiring certification to the latest ATEX standards - see ATEX certificate DEMKO 99ATEX126256 and EU Declaration of Conformity for details.
Ficha técnica y manuales
Nota de seguridad
Nota de seguridad
- SN5000-3-103-1933.pdf
- SN5000-3-102-1613.pdf
- SN5000-101-1450.pdf
- Versiones anteriores
- Última versión
Homologaciones y certificados
Declaración EAC
- EAC_EMC_declaration_Ex_3000_5000_6000_9000.pdf
- Última versión
Certificado EAC
- EAC_Ex.pdf
- Última versión
Metrology Pattern Approval (MPA), Russia
- MPA_Russia.pdf
- Última versión
Formulario de pedido
Environmental Conditions
Operating temperature | -20°C to +60°C |
Calibration temperature | 20...28°C |
Relative humidity | < 95% RH (non-cond.) |
Protection degree | IP20 |
Mechanical specifications
Dimensions (HxWxD) | 109 x 23.5 x 130 mm |
Weight approx. | 215 g |
DIN rail type | DIN EN 60715/35 mm |
Wire size | 0.13...2.08 mm2 AWG 26...14 stranded wire |
Screw terminal torque | 0.5 Nm |
Common specifications
Supply |
|
Supply voltage, universal | 21.6...253 VAC, 50...60 Hz or 19.2...300 VDC |
Max. required power | ≤ 4 W (2 channels) |
Internal power dissipation | ≤ 2 W (2 channels) |
Fuse | 400 mA SB / 250 VAC |
Isolation voltage |
|
Isolation voltage, test / working | 3.75 kVAC / 250 VAC |
PELV/SELV | IEC 61140 |
EMC immunity influence | < ±0.5% |
Extended EMC immunity: NAMUR NE21, A criterion, burst | < ±1% |
Output specifications
Relay output |
|
Max. voltage | 250 VRMS |
Max. current | 2 ARMS |
Max. AC power | 100 VA |
Max. load at 24 VDC | 1 A |
Output voltage | > 18 VDC at 20 mA |
Output current | 28 mA per channel (max.) |
Relay outputs: On within limit | > 3.8...< 20.5 mA |
Observed authority requirements
EMC | 2014/30/EU |
LVD | 2014/35/EU |
EAC | TR-CU 020/2011 |
Approvals
ATEX | DEMKO 99ATEX126256, II (1) GD [EEx ia] IIC |
EAC Ex | EAEU KZ 7500361.01.01.08756 |
Do you need help choosing the right device?Our sales engineers are ready to guide you to the device that best fits your application. How to contact us?You can use our quote function or contact form with no obligation. With the quote function, you simply add the devices you are interested in and receive a quote. We will get back to you within 24 hours on business days.
After you orderWhen your order is placed, you will receive a confirmed delivery date within two business days. As soon as your package has been shipped, you will receive an email with tracking details, so you always know where your delivery is. |
![]() |
State-of-the-art manufacturing Our 8,500 sqm integrated and automated manufacturing campus in Denmark covers the entire value-chain from design and development to manufacturing. It allows us to design and optimize for testing and manufacturing thereby constantly driving quality up and costs down. |
![]() |
Dedicated Presale / Aftersales
|
![]() |
Product reliability |
![]() |
Product deployment
|
![]() |
Smart products |