9203
 

Solenoid / alarm driver

 

9203B

 

  • Universal Ex driver for solenoids, acoustic alarms and LEDs
  • Extended self-diagnostics
  • 1 or 2 channels
  • Can be supplied separately or installed on power rail, PR 9400
  • SIL 2-certified via Full Assessment
  1. Panoramica + -

  2. Dati tecnici + -

  3. Accessori + -


Advanced features

  • Universal I.S. driver for the control of solenoids etc. with various I.S. data by way of three built-in I.S. barriers.
  • Two hardware versions make it possible to choose either Low (35 mA) or High (60 mA) current output.
  • Configuration and monitoring by way of detachable display front (PR 4500).
  • Selection of direct or inverted function for each channel via PR 4500 and the possibility of reducing the output current to the hazardous area to suit the application.
  • Optional monitoring of the output current to the hazardous area by way of PR 4500.
  • Optional redundant supply via power rail and/or separate supply.

Application

  • 9203B can be mounted in the safe area or in zone 2 / Class 1, Division 2 and transmit signals to zone 0, 1, 2 and zone 20, 21, 22 including M1 mining / Class I/II/III, Div. 1, Gr. A-G.
  • Driver for the control of ON / OFF solenoids, acustic alarms and LEDs mounted in safe or hazardous area.
  • The 9203B is controlled by an NPN/PNP signal or a switch signal.
  • Monitoring of internal error events via the individual status relay and/or a collective electronic signal via the power rail.
  • The 9203B has been designed, developed and certified for use in SIL 2 applications according to the requirements of IEC 61508.
  • Suitable for the use in systems up to Performance Level “d” according to ISO-13849.

Technical characteristics

  • 1 green and 2 yellow/red front LEDs indicate operation status and malfunction.
  • 2.6 kVAC galvanic isolation between input, output and supply.

Mounting

  • The devices can be mounted vertically or horizontally without distance between neighbouring units.

Documentazione supplementare


Safety manual (SIL)

Dichiarazione UE di conformità

Manuale di configurazione Modbus

Rapporto di valutazione

Rapporto FMEDA

Dichiarazione ISO 13849

Dichiarazione SIL

Dati EMC

Approvazioni & certificati


Certificato ATEX

Certificato IECEx

Certificato CCC

Certificato FM

Certificato INMETRO

Certificato SIL

Certificato UL

Certificato marina DNV

Certificato ClassNK

Dichiarazione EAC

Certificato EAC Ex

Metrology Pattern Approval (MPA), Russia

Note di sicurezza

Environmental Conditions

Operating temperature -20°C to +60°C
Storage temperature -20°C to +85°C
Calibration temperature 20...28°C
Relative humidity < 95% RH (non-cond.)
Protection degree IP20
Installation in Pollution degree 2 & meas. / overvoltage cat. II

Mechanical specifications

Dimensions (HxWxD) 109 x 23.5 x 104 mm
Dimensions (HxWxD) w/ 4501/451x 109 x 23.5 x 116 / 131 mm
Weight approx. 170 g
Weight incl. 4501 / 451x (approx.) 185 g / 200 g
DIN rail type DIN EN 60715/35 mm
Wire size 0.13...2.08 mm2 AWG 26...14 stranded wire
Screw terminal torque 0.5 Nm
Vibration IEC 60068-2-6
2...13.2 Hz ±1 mm
13.2...100 Hz ±0.7 g

Common specifications

Supply

Supply voltage 19.2...31.2 VDC
Fuse 1.25 A SB / 250 VAC
Max. required power ≤ 1.9 W / ≤ 3.1 W (1 / 2 ch.) - low current ≤ 2.5 W (1 ch.) - high current
Max. power dissipation, 1 / 2 ch. ≤ 1.1 W / ≤ 2.0 W (1 / 2 ch.) - low current
Max. power dissipation ≤ 1.7 W (1 ch.) - high current

Isolation voltage

Test /working: Input to any 2.6 kVAC / 300 VAC reinforced isolation
Output 1 to output 2 1.5 kVAC / 150 VAC reinforced isolation
Status relay to supply 1.5 kVAC / 150 VAC reinforced isolation
Programming PR 4500 communication interfaces
EMC immunity influence < ±0.5% of span
Extended EMC immunity: NAMUR NE21, A criterion, burst < ±1% of span

Input specifications

NPN and mechanical switch

Trig level LOW ≤ 2.0 VDC
Trig level HIGH ≥ 4.0 VDC
Max. external voltage 28 VDC
Input impedance 3.5 kΩ

PNP

Trig level LOW ≤ 8.0 VDC
Trig level HIGH ≥ 10.0 VDC
Max. external voltage 28 VDC
Input impedance 3.5 kΩ

Output specifications

Status relay

Max. voltage 125 VAC / 110 VDC
Max. current 0.5 AAC / 0.3 ADC
Max. AC power 62.5 VA / 32 W
Output ripple < 40 mVRMS

Observed authority requirements

EMC 2014/30/EU
LVD 2014/35/EU
ATEX 2014/34/EU
RoHS 2011/65/EU
EAC TR-CU 020/2011
EAC Ex TR-CU 012/2011

Approvals

ATEX KEMA 07ATEX0147 X
IECEx KEM 09.0001X
c FM us FM19US0057X / FM19CA0030X
INMETRO DEKRA 16.0006 X
c UL us, UL 61010-1 E314307
c UL us, UL 913 E233311 (only 9203xxxx-U9)
CCC 2020322304003423
EAC Ex RU C-DK.HA65.B.00355/19
DNV Marine TAA00000JD
ClassNK TA18527M
SIL SIL 2 certified & fully assessed acc. to IEC 61508
 

Hai trovato utili queste informazioni?

 

Dai una valutazione

La vostra richiesta è stata inviata con successo 0 prodotti nella tua lista
I vostri contatti
Inserisci il tuo nome
Inserisci il tuo cognome
Inserisci un indirizzo di posta elettronica valido
Inserisci un numero di telefono valido. Usa solo numeri.
Inserisci la posizione lavorativa
Inserisci il nome della tua azienda
Inserisci il tuo indirizzo aziendale
Inserisci un Cap valido
Inserisci la città
Selezionare il paese
Leggi e accetta la politica sulla Privacy di PR electronics.
Non hai aggiunto alcun prodotto al tuo elenco di preventivi
Durante la visita del nostro sito Web, sarà possibile aggiungere prodotti a un elenco di preventivi semplicemente facendo clic su "Aggiungi all'elenco dei preventivi" nelle singole pagine dei prodotti. Una volta inclusi tutti i prodotti pertinenti, inviaci l'elenco e otterrai un preventivo entro 24 ore. Se non invii l'elenco, sarà accessibile sul sito Web per 21 giorni. Speriamo che troverai utile la funzionalità.
Grazie per aver richiesto un preventivo. Ti risponderemo telefonicamente o via e-mail entro 24 ore.

Bisogno di aiuto?

Se hai bisogno di assistenza, contattaci sarai sempre il benvenuto

Resta aggiornato!

Registrati qui per ricevere la nostra newsletter