Prodotti 0
9116
 
 

9116B

 

Universal converter

 

  1. Overview +

  2. Technical details +

  3. Accessories +


Advanced features

  • Configuration and monitoring by way of detachable display front (PR 4501); process calibration, signal and relay simulation.
  • Advanced relay configuration, e.g. setpoint, window, delay, sensor error indication and power monitoring.
  • Copying of the configuration from one device to others of the same type via PR4501.
  • Reduced Uo Ex data < 8.3 V for active input signals.
  • TC inputs with internal CJC or external CJC for higher accuracy.
  • Active / passive mA output via the same two terminals.

Application

  • 9116B can be mounted in the safe area and in zone 2 / cl. 1 div. 2 and receive signals from zone 0, 1, 2 and zone 20, 21, 22 including M1 / Class I/II/III, Div. 1, Gr. A-G.
  • Conversion and scaling of temperature, voltage, potentiometer and linear resistance signals.
  • Power supply and signal isolator for 2-wire transmitters.
  • Monitoring of error events and cable breakage via the individual status relay and/or a collective electronic signal via the power rail.
  • The 9116 has been designed, developed and certified for use in SIL 2 applications according to the requirements of IEC 61508.

Technical characteristics

  • 1 green and 1 red front LED indicate operation status and malfunction. 1 yellow LED indicates relay status.
  • 2.6 kVAC galvanic isolation between input, output and supply.

Mounting

  • The devices can be mounted vertically or horizontally without distance between neighbouring units.

Data sheet


Safety manual (SIL)


Modbus configuration manual


4801 Gateway manual


UL certificate


FM certificate


DNV marine certificate


SIL certificate


SIL declaration


Assessment report


CCOE certificate


EAC declaration


EAC Ex certificate


Metrology Pattern Approval (MPA)


Environmental Conditions

  • Operating temperature

    -20°C to +60°C

  • Storage temperature

    -20°C to +85°C

  • Calibration temperature

    20...28°C

  • Relative humidity

    < 95% RH (non-cond.)

  • Protection degree

    IP20

  • Installation in

    Pollution degree 2 & meas. / overvoltage cat. II

Mechanical specifications

  • Dimensions (HxWxD)

    109 x 23.5 x 104 mm

  • Dimensions (HxWxD) w/ 4501/4511

    109 x 23.5 x 116 / 131 mm

  • Weight approx.

    185 g

  • Weight incl. 4501 / 4511 (approx.)

    200 g / 285 g

  • DIN rail type

    DIN EN 60715/35 mm

  • Wire size

    0.13...2.08 mm2 AWG 26...14 stranded wire

  • Screw terminal torque

    0.5 Nm

  • Vibration

    IEC 60068-2-6

  • 2...13.2 Hz

    ±1 mm

  • 13.2...100 Hz

    ±0.7 g

Common specifications

  • Supply

  • Supply voltage

    19.2...31.2 VDC

  • Fuse

    1.25 A SB / 250 VAC

  • Max. required power

    ≤ 2.1 W

  • Max. power dissipation

    ≤ 1.7 W

  • Isolation voltage

  • Test /working: Input to any

    2.6 kVAC / 300 VAC reinforced isolation

  • Analog output to supply

    2.6 kVAC / 300 VAC reinforced isolation

  • Status relay to supply

    1.5 kVAC / 150 VAC reinforced isolation

  • Response time

  • Temperature input, programmable (0...90%, 100...10%)

    1...60 s

  • mA / V input (programmable)

    0.4...60 s

  • Auxiliary supplies

  • 9116B1: 2-w. sup. (term. 54...52)

    28...16.5 VDC / 0...20 mA

  • 9116B2: 2-w. sup. (term. 54...52)

    21.4...16.5 VDC / 0...20 mA

  • Signal dynamics, input

    24 bit

  • Signal dynamics, output

    16 bit

  • Signal / noise ratio

    Min. 60 dB (0...100 kHz)

  • Accuracy

    Better than 0.1% of sel. range

Input specifications

  • RTD input

  • RTD type

    Pt10/20/50/100/200/250/300/Pt400/500/1000; Ni50/100/120/1000

  • Cable resistance per wire

    50 Ω (max.)

  • Sensor current

    Nom. 0.2 mA

  • Effect of sensor cable resistance (3-/4-wire)

    < 0.002 Ω / Ω

  • Sensor error detection

    Programmable ON / OFF

  • Short circuit detection

    Yes

  • TC input

  • Thermocouple type

    B, E, J, K, L, N, R, S, T, U, W3, W5, LR

  • Cold junction compensation (CJC) via ext. sensor in 5910

    20...28°C ≤ ±1°C, -20...20°C / 28...70°C ≤ 2°C

  • CJC via int. mounted sensor

    ±(2.0°C + 0.4°C * Δt)

  • Δt =

    Internal temp.-ambient temp.

  • Current input

  • Measurement range

    0...23 mA

  • Programmable measurement ranges

    0...20 and 4...20 mA

  • Input resistance

    Nom. 20 Ω + PTC 50 Ω

  • Sensor error detection

    Loop break 4...20 mA

  • Voltage input

  • Measurement range

    0...12 VDC

  • Programmable measurement ranges

    0/0.2...1, 0/1...5, 0/2...10 VDC

  • Input resistance

    Nom. >10 MΩ

Output specifications

  • Current output

  • Signal range

    0...23 mA

  • Programmable signal ranges

    0...20/4...20/20...0/20...4 mA

  • Load (@ current output)

    ≤ 600 Ω

  • Load stability

    ≤ 0.01% of span / 100 Ω

  • Sensor error indication

    0 / 3.5 / 23 mA / none

  • NAMUR NE43 Upscale/Downscale

    23 mA / 3.5 mA

  • Current limit

    ≤ 28 mA

  • Passive 2-wire mA output

  • Max. external 2-wire supply

    26 VDC

  • Max. load resistance [Ω]

    (Vsupply-3.5)/0.023 A

  • Effect of external 2-wire supply voltage variation

    < 0.005% of span / V

  • Relay output

  • Relay functions

    Setpoint, Window, Sensor error, Power and Off

  • Max. voltage

    250 VAC / VDC

  • Max. current

    2 A

  • Max. AC power

    500 VA

  • Max. DC current, resistive load ≤ 30 VDC

    2 ADC

  • Max. DC current, resistive load > 30 VDC

    See manual for details

  • Status relay

  • Max. voltage

    110 VDC / 125 VAC

  • Max. current

    0.3 ADC / 0.5 AAC

  • Max. AC power

    62.5 VA / 32 W

Observed authority requirements

  • EMC

    2014/30/EU

  • LVD

    2014/35/EU

  • RoHS

    2011/65/EU

  • EAC

    TR-CU 020/2011

Approvals

  • ATEX 2014/34/EU

    KEMA 10ATEX0053 X

  • IECEx

    KEM 10.0022X

  • FM

    3038267-C

  • INMETRO

    DEKRA 16.0004 X

  • UL

    UL 61010-1

  • EAC Ex TR-CU 012/2011

    RU C-DK.GB08.V.00410

  • CCOE

    P337349/4

  • DNV-GL Marine

    Stand. f. Certific. No. 2.4

  • ClassNK

    TA18527M

  • SIL

    SIL 2 certified & fully assessed acc. to IEC 61508

La vostra richiesta è stata inviata con successo - 0 Prodotti nella tua lista
Descrizione del prodotto Quantità
Si prega di specificare la variante (si veda il datasheet) – oppure indicare “variante sconosciuta”
I vostri contatti
Continua a navigare
Nessun prodotto aggiunto alla vostra lista…
Nessun prodotto nella vostra lista…

Mentre consultate le pagine sui prodotti presenti sul nostro sito web, avete la possibilità di aggiungere i nostri prodotti alla lista – ed inviarci tale lista per richiedere una quotazione. Per aggiungere i prodotti alla lista, cliccate sul pulsante “RICHIEDI UN PREVENTIVO” presente su ciascuna delle pagine sui prodotti.

Una volta inoltrata la lista, provvederemo a ricontattarvi quanto prima.

Se non desiderate inoltrare tale lista, essa rimarrà comunque visibile alla vostra attenzione sul sito web per 7 giorni (tramite “cookie” sul vostro PC o tablet)




Ci auguriamo troviate utili tali funzionalità. Si prega di andare alle pagine sui prodotti per aggiungere i nostri prodotti alla lista
Grazie per la vostra richiesta
Provvederemo quanto prima a ricontattarvi telefonicamente o via e-mail.