5531A
 

Loop-powered LCD indicator

 

5531A

 

  • 4 digit 1/8 DIN (48 x 96 mm) loop-powered LCD display
  • Easy push-button configuration
  • Backlit LCD display is readable in low light conditions
  • Display can be mounted in the safe area or in I.S. / Ex zone 2
  1. Overview + -

  2. Tekniske data + -

  3. Tilbehør + -


Application

  • The 5531 indicator is powered by the 4 to 20 mA current loop and is easily scaled to display the correct process value.
  • Because it does not require separate power wiring, the 5531 is perfect for remote display of process loops.
  • The 5531A display can be panel mounted in the safe area or I.S. / Ex Zone 2 (gas).

Technical characteristics

  • With a full measurement range of 3.6 to 23 mA, the 5531 is NAMUR NE43 compliant.
  • The display can be push-button scaled to any range between -9999 to 9999, and reverse display action is possible.
  • The LCD backlight can be set to half or full intensity for easy viewing in low light conditions.
  • The display only requires 1.5 VDC, (75 Ω loop load), with the backlight turned off.
  • The input is HART transparent.
  • The front push-buttons can be disabled to prevent unauthorized adjustment.

Mounting / installation

  • Once panel mounted with the included gasket, the 5531 provides IP65 ingress protection.

Datablad & manualer


Datablad

Manualer

Manualer på russisk

Godkendelser & certifikater


ATEX-certifikat

EAC-erklæring

Metrology Pattern Approval (MPA)

Yderligere dokumentation


EU-overensstemmelseserklæring

Sikkerhedsanvisninger


Sikkerhedsanvisninger

Environmental Conditions

Operating temperature -20°C to +60°C
Storage temperature -20°C to +60°C
Calibration temperature 20...28°C
Relative humidity < 95% RH (non-cond.)
Protection degree IP65, from front

Mechanical specifications

Dimensions (HxWxD) 48 x 96 x 120 mm
Cut out dimensions 44.5 x 91.5 mm
Weight approx. 200 g
Wire size, connector terminal 1 - 4 0.13...2.08 mm2 / AWG 26...14 stranded wire
Screw terminal torque 0.5 Nm
Cable glands and cable diameter M16 x 1.5 / Ø 5...8 mm

Common specifications

Supply

Supply voltage Input loop-powered

Response time

Response time (0...90%, 100...10%) < 1 s
Signal / noise ratio > 60 dB
Updating time 500 ms
EMC immunity influence < ±0.5% of span

Input specifications

Current input

Loop error detection, 4...20 mA: Low ~ < 3 mA
Loop error detection, 4...20 mA: High ~ > 24 mA
Input range 4...20 mA
Measurement range 3.6...23 mA
Input voltage drop, without backlight < 1.5 V @ 20 mA
Input voltage drop, with half backlight < 6.5 V @ 20 mA
Input voltage drop, with full backlight < 10.5 V @ 20 mA

Observed authority requirements

LVD 2014/35/EU
EMC 2014/30/EU
RoHS 2011/65/EU
EAC TR-CU 020/2011

Output specifications

Display

Display readout ± 9999 (4 digits)
Digit height 16 mm

Approvals

ATEX KEMA 05ATEX1044 X (5531A/B1)
 

Er disse oplysninger nyttige?

 

Bedøm os

Din anmodning om et tilbud er nu sendt til os. 0 produkter på din liste
Din kontaktinformation
Indtast fornavn
Indtast efternavn
Indtast en gyldig email-adresse
Indtast telefonnummer. Brug kun tal.
Indtast jobtitel
Indtast firmanavn
Indtast firmaadresse
Indtast postnummer
Indtast bynavn
Vælg land
Du har ikke tilføjet nogen produkter til din tilbudsliste
Når du søger på hjemmesiden, kan du på hver enkelt produktside føje produkter til en tilbudsliste ved at klikke på "Føj til tilbudsliste". Send listen til os, når du har tilføjet alle relevante produkter, så vil du få et tilbud inden for 24 timer. Hvis du ikke sender listen, vil den være tilgængelig på hjemmesiden i 21 dage. Vi håber, at du finder denne funktion nyttig.
Tak for din forespørgsel. Vi vender tilbage inden for 24 timer enten via telefon eller e-mail.

Brug for hjælp?

Hvis du har brug for support, er du altid velkommen til at kontakte os

Hold dig opdateret!

Tilmeld dig her for at modtage vores nyhedsbrev