2914
 

2-wire room temperature transmitter

 

2914

 

  • Room temperature measurement
  • Complete with sensor and transmitter
  • 4...20 mA output in 2-wire connection
  • Easy mounting
  • Measurement range 0...70°C
  • Supply 8...35 VDC
  1. Panoramica + -

  2. Dati tecnici + -

  3. Accessori + -


Application

  • Electronic temperature measurement in for instance control rooms, offices, heating plants, factories, living rooms, and similar dry rooms.
  • Suitable as a transmitter for controllers, trip amplifiers, displays, or superior SCADA systems.

Technical characteristics

  • A precision Pt100 sensor with a small mass is mounted on the transmitter input thereby achieving a fast response time.
  • The 2-wire output signal of 4...20 mA is proportional and linear to the temperature value that influences the built-in sensor.
  • A reversed output signal of 20...4 mA may be ordered.
  • A number of different sensor error detection options may be ordered.
  • Protected against polarity reversal.
  • The bottom of the cabinet can be attached to a wall by two screws.
  • Visible or hidden cable access.

Scheda tecnica & manuali


Scheda tecnica

Manuali

Documentazione supplementare


Dichiarazione UE di conformità

Note di sicurezza


Note di sicurezza

Approvazioni & certificati


Dichiarazione EAC

Metrology Pattern Approval (MPA), Russia

Environmental Conditions

Operating temperature 0°C to +70°C
Calibration temperature 20...28°C
Relative humidity < 95% RH (non-cond.)
Protection degree IP30

Mechanical specifications

Dimensions (HxWxD) 70 x 121 x 25 mm
Weight approx. 95 g
Wire size 1 x 1.5 mm

Common specifications

Supply

Supply voltage 8.0...35 VDC
Internal power dissipation 25 mW…0.8 W

Response time

Response time 10 s (@ 0.5 m/s)
Voltage drop 8.0 VDC
Warm-up time 5 min.
Signal / noise ratio Min. 60 dB
Accuracy Better than 0.3°C
Signal dynamics, input 17 bit
Signal dynamics, output 16 bit
Effect of supply voltage change < 0.005% of span / VDC
Temperature coefficient < ±0.01% of span / °C
Linearity error < 0.1% of span
EMC immunity influence < ±0.5%

Input specifications

Common input specifications

Max. offset 50% of max.°C

RTD input

Sensor current > 0.2 mA, < 0.4 mA
Measurement range 0...70°C
Min. measurement range 25°C (span)

Output specifications

Current output

Signal range 4…20 mA
Min. signal range 16 mA
Load (@ current output) ≤ (Vsupply - 8) / 0.023 [Ω]
Load stability ≤ 0.01% of span / 100 Ω
NAMUR NE43 Upscale/Downscale 23 mA / 3.5 mA

Common output specifications

Updating time 135 ms
of span = of the presently selected range

Observed authority requirements

EMC 2014/30/EU
EAC TR-CU 020/2011
 

Hai trovato utili queste informazioni?

 

Dai una valutazione

La vostra richiesta è stata inviata con successo 0 prodotti nella tua lista
I vostri contatti
Inserisci il tuo nome
Inserisci il tuo cognome
Inserisci un indirizzo di posta elettronica valido
Inserisci un numero di telefono valido. Usa solo numeri.
Inserisci la posizione lavorativa
Inserisci il nome della tua azienda
Inserisci il tuo indirizzo aziendale
Inserisci un Cap valido
Inserisci la città
Selezionare il paese
Leggi e accetta la politica sulla Privacy di PR electronics.
Non hai aggiunto alcun prodotto al tuo elenco di preventivi
Durante la visita del nostro sito Web, sarà possibile aggiungere prodotti a un elenco di preventivi semplicemente facendo clic su "Aggiungi all'elenco dei preventivi" nelle singole pagine dei prodotti. Una volta inclusi tutti i prodotti pertinenti, inviaci l'elenco e otterrai un preventivo entro 24 ore. Se non invii l'elenco, sarà accessibile sul sito Web per 21 giorni. Speriamo che troverai utile la funzionalità.
Grazie per aver richiesto un preventivo. Ti risponderemo telefonicamente o via e-mail entro 24 ore.

Bisogno di aiuto?

Se hai bisogno di assistenza, contattaci sarai sempre il benvenuto

Resta aggiornato!

Registrati qui per ricevere la nostra newsletter