2-wire programmable transmitter
PR 5131A
- Input for RTD, TC, mV, linear resistance, mA, and V
- 3.75 kVAC galvanic isolation
- 4...20 mA loop output
- 1- or 2-channel version
- DIN rail mounting
Advanced features
- The 5131A transmitter can be configured with the software program PReset using a standard PC and the Loop Link communications unit.
Application
- Independent channel jumper selectable inputs for current/voltage or temperature.
- Current input programmable in range 0...100 mA and voltage inputs in range 0...250 VDC.
- Linearized, electronic temperature measurement with RTD or TC sensor.
- Conversion of linear resistance variation to a standard analog current / voltage signal, for example from solenoids and butterfly valves or linear movements with attached potentiometer.
- 4- or 3-wire connection automatic cable compensation or 2-wire connection with programmable cable compensation.
- Configurable sensor error detection including NAMUR NE43.
Technical characteristics
- The 2-channel version has full galvanic isolation between the channels.
- Separation of circuits in PELV/SELV installations.
Data sheet & Manuals
Data sheet
- 5131A.pdf
- Latest version
Manuals
- 5131V107_UK.pdf
- 5131V106_UK.pdf
- 5131V105_UK.pdf
- 5131V104_UK.pdf
- 5131V103.pdf
- Previous versions
- Latest version
Manuals in Russian
- 5131V107_RU.pdf
- 5131V106_RU.pdf
- 5131V105_RU.pdf
- 5131V104_RU.pdf
- Previous versions
- Latest version
Supplementary documentation
EU Declaration of Conformity
- 5131DoC_EU_104_UK.pdf
- 5131DoC_EU_103_UK.pdf
- 5131DoC_EU_102_UK.pdf
- 5131DoC_EU_101_UK.pdf
- 5131DoC_EU_100_UK.pdf
- Previous versions
- Latest version
PR default configurations
- PR_default_configurations.pdf
- Latest version
Safety note
Safety note
Approvals & Certificates
EAC declaration
- EAC_LVD_EMC_5131A_5202A.pdf
- Latest version
Metrology Pattern Approval (MPA), Russia
- MPA_Russia.pdf
- Latest version
View variants
Environmental Conditions
| Operating temperature | -20°C to +60°C |
| Calibration temperature | 20...28°C |
| Relative humidity | < 95% RH (non-cond.) |
| Protection degree | IP20 |
Mechanical specifications
| Dimensions (HxWxD) | 109 x 23.5 x 130 mm |
| Weight approx. | 195 g |
| DIN rail type | DIN EN 60715/35 mm |
| Wire size | 0.13...2.08 mm2 AWG 26...14 stranded wire |
| Screw terminal torque | 0.5 Nm |
Common specifications
Supply |
|
| Supply voltage | 7.5...35 VDC |
| Fuse | 50 mA SB / 250 VAC |
Isolation voltage |
|
| Isolation voltage, test / working | 3.75 kVAC / 250 VAC |
| PELV/SELV | IEC 61140 |
Response time |
|
| Temperature input, programmable (0...90%, 100...10%) | 400 ms...60 s |
| mA / V input (programmable) | 250 ms...60 s |
| Programming | PR 5909 Loop Link communications interface |
| Signal / noise ratio | Min. 60 dB (0...100 kHz) |
| Signal dynamics, input | 22 bit |
| Signal dynamics, output | 16 bit |
| Updating time |
115 ms (temperature input)
75 ms (mA / V / mV input) |
| EMC immunity influence | < ±0.5% of span |
| Extended EMC immunity: NAMUR NE21, A criterion, burst | < ±1% of span |
| Effect of supply voltage change | < 0.005% of span / VDC |
Input specifications
Common input specifications |
|
| Max. offset | 50% of selected max. value |
RTD input |
|
| RTD type | Pt100…1000, Ni100...1000, lin. R |
| Cable resistance per wire | 10 Ω (max.) |
| Sensor current | Nom. 0.2 mA |
| Effect of sensor cable resistance (3-/4-wire) | < 0.002 Ω / Ω |
| Sensor error detection | Yes |
TC input |
|
| Thermocouple type | B, E, J, K, L, N, R, S, T, U, W3, W5, LR |
| Cold junction compensation (CJC) | < ±1.0°C |
| Sensor error current | Nom. 30 μA |
| Sensor error detection | Yes |
Current input |
|
| Measurement range | 0...100 mA |
| Min. measurement range (span) | 4 mA |
| Input resistance: Supplied unit | Nom. 10 Ω + PTC 10 Ω |
| Input resistance: Non-supplied unit | RSHUNT = ∞, VDROP < 6 V |
mV input |
|
| Measurement range | -150...+150 mV |
Voltage input |
|
| Measurement range | 0...250 VDC |
| Min. measurement range (span) | 5 mV |
| Input resistance |
Nom. 10 MΩ (≤ 2.5 VDC) (1)
Nom. 5 MΩ (> 2.5 VDC) |
Output specifications
Current output |
|
| Signal range | 4…20 mA |
| Min. signal range | 10 mA |
| Load (@ current output) | ≤ (Vsupply - 7.5) / 0.023 [Ω] |
| Load stability | ≤ 0.01% of span / 100 Ω |
| Current limit | ≤ 28 mA |
| Sensor error indication | Programmable 3.5…23 mA |
| NAMUR NE43 Upscale/Downscale | 23 mA / 3.5 mA |
| of span | = of the presently selected range |
Observed authority requirements
| EMC | 2014/30/EU |
| LVD | 2014/35/EU |
| RoHS | 2011/65/EU |
| EAC | TR-CU 020/2011 |