Repeater / power supply
PR 5104A
- 1- or 2-channel version
- 3- / 5-port 3.75 kVAC galvanic isolation
- Loop supply > 17.1 V
- 20 programmable measurement ranges
- Universal supply by AC or DC
Application
- Power supply and signal isolator for 2-wire transmitters.
- Signal isolator for analog current / voltage signals.
- 1 : 1 or signal conversion of analog current / voltage signals.
Technical characteristics
- The 20 factory-calibrated measurement ranges in the 5104A can be selected by the internal DIP-switches without the need for recalibration. Special measurement ranges can be delivered.
- PR5104A is based on microprocessor technology for gain and offset. The analog signal is transmitted at a response time of less than 25 ms.
- Inputs, outputs, and supply are floating and galvanically separated.
- The output can be connected either as an active current / voltage transmitter or as a 2-wire transmitter.
Mounting / installation
- Mounted vertically or horizontally on a DIN rail. By way of the 2-channel version up to 84 channels per meter can be mounted.
Data sheet & Manuals
Data sheet
- 5104A.pdf
- Latest version
Manuals
- 5104V106_UK.pdf
- 5104V105_UK.pdf
- 5104V104_UK.pdf
- 5104V103.pdf
- Previous versions
- Latest version
Manuals in Russian
- 5104V106_RU.pdf
- 5104V105_RU.pdf
- 5104V104_RU.pdf
- Previous versions
- Latest version
Supplementary documentation
EU Declaration of Conformity
- 5104DoC_EU_103_UK.pdf
- 5104DoC_EU_102_UK.pdf
- 5104DoC_EU_101_UK.pdf
- 5104DoC_EU_100_UK.pdf
- Previous versions
- Latest version
PR default configurations
- PR_default_configurations.pdf
- Latest version
Safety note
Safety note
- SN5000-1-106-2602.pdf
- SN5000-1-105-2507.pdf
- SN5000-1-104-2340.pdf
- SN5000-1-103-1931.pdf
- SN5000-1-102-1613.pdf
- SN5000-101-1450.pdf
- Previous versions
- Latest version
Approvals & Certificates
UL certificate
- 5104A_5106A_UL.pdf
- Latest version
DNV marine certificate
- DNV_2231_41xx_51xx_53xx.pdf
- Latest version
EAC declaration
- EAC_LVD_EMC_Declaration.pdf
- Latest version
Metrology Pattern Approval (MPA), Russia
- MPA_Russia.pdf
- Latest version
View variants
Environmental Conditions
| Operating temperature | -20°C to +60°C |
| Calibration temperature | 20...28°C |
| Relative humidity | < 95% RH (non-cond.) |
| Protection degree | IP20 |
Mechanical specifications
| Dimensions (HxWxD) | 109 x 23.5 x 130 mm |
| Weight approx. | 225 g |
| DIN rail type | DIN EN 60715/35 mm |
| Wire size | 0.13...2.08 mm2 AWG 26...14 stranded wire |
| Screw terminal torque | 0.5 Nm |
Common specifications
Supply |
|
| Supply voltage, universal | 21.6...253 VAC, 50...60 Hz or 19.2...300 VDC |
| Fuse | 400 mA SB / 250 VAC |
| Max. required power | ≤ 3 W (2 channels) |
| Internal power dissipation | ≤ 2 W (2 channels) |
Isolation voltage |
|
| Isolation voltage, test / working | 3.75 kVAC / 250 VAC |
| PELV/SELV | IEC 61140 |
Response time |
|
| Response time (0...90%, 100...10%) | < 25 ms |
Auxiliary supplies |
|
| 2-wire supply (pin 44...42 and 54...52) | 28...17.1 VDC / 0...20 mA |
| Programming | DIP switches |
| Signal / noise ratio | Min. 60 dB (0...100 kHz) |
| EMC immunity influence | < ±0.5% of span |
| Extended EMC immunity: NAMUR NE21, A criterion, burst | < ±1% of span |
Input specifications
Common input specifications |
|
| Max. offset | 20% of max. value |
Current input |
|
| Measurement range | 0...23 mA |
| Min. measurement range (span) | 16 mA |
| Input resistance | Nom. 10 Ω + PTC 10 Ω |
Voltage input |
|
| Measurement range | 0...10 VDC |
| Min. measurement range (span) | 8 VDC |
| Input resistance | > 2 MΩ |
Output specifications
Current output |
|
| Signal range | 0...23 mA |
| Min. signal range | 16 mA |
| Load (@ current output) | ≤ 600 Ω |
| Load stability | ≤ 0.01% of span / 100 Ω |
| Current limit | ≤ 28 mA |
Passive 2-wire mA output |
|
| Max. external 2-wire supply | 29 VDC |
| Effect of external 2-wire supply voltage variation | < 0.005% of span / V |
Voltage output |
|
| Signal range | 0...1 VDC / 0...10 VDC |
| Min. signal range | 0.8 VDC / 8 VDC |
| Load (@ voltage output) | ≥ 500 kΩ |
| of span | = of the presently selected range |
Observed authority requirements
| EMC | 2014/30/EU |
| LVD | 2014/35/EU |
| EAC | TR-CU 020/2011 |
| EAC LVD | TR-CU 004/2011 |
Approvals
| c UL us, UL 508 | E231911 |
| DNV Marine | TAA0000101 |