2-wire transmitter with HART protocol
PR 5337A
- RTD, TC, Ohm, and bipolar mV input
- 2 analog inputs and 5 device variables with status available
- HART protocol revision selectable from HART 5 or HART 7
- Hardware assessed for use in SIL applications
- Mounting in Safe area or Zone 2/22
Application
- Linearized temperature measurement with TC and RTD sensors e.g. Pt100 and Ni100.
- HART communication and 4...20 mA analog PV output for individual, difference or average temperature measurement of up to two RTD or TC input sensors.
- Conversion of linear resistance to a standard analog current signal, e.g from valves or Ohmic level sensors.
- Amplification of bipolar mV signals to standard 4...20 mA current signals.
- Up to 63 transmitters (HART 7) can be connected in a multidrop communication setup.
Technical characteristics
- HART protocol revision can be changed by user configuration to either HART 5 or HART 7 protocol.
- The HART 7 protocol offers:
∙ Long Tag numbers of up to 32 characters.
∙ Enhanced Burst Mode and Event notification with time stamping.
∙ Device variable and status mapping to any dynamic variable PV, SV, TV or QV.
∙ Process signal trend measurement with logs and summary data.
∙ Automatic event notification with time stamps.
∙ Command aggregation for higher communication efficiency. - The 5337A provides the required failure data (SFF and PFDAVG) for SIL 2 applications as per IEC 61508 / IEC 61511.
- Continuous check of vital stored data.
- Meeting the NAMUR NE21 recommendations, the 5337 HART transmitter ensures top measurement performance in harsh EMC environments. Additionally, the 5337 meets NAMUR NE43 and NE89 recommendations.
Mounting / installation
- For DIN form B sensor head or DIN rail mounting via the PR fitting type 8421.
- Configuration via standard HART communication interfaces or by PR 5909 Loop Link.
Data sheet & Manuals
Data sheet
- 5337A.pdf
- Latest version
Manuals
- 5337V112_UK.pdf
- 5337V111_UK.pdf
- 5337V110_UK.pdf
- 5337V109_UK.pdf
- 5337V108_UK.pdf
- 5337V107_UK.pdf
- 5337V106_UK.pdf
- 5337V105_UK.pdf
- 5337V104_UK.pdf
- 5337V103_UK.pdf
- 5337V102_UK.pdf
- 5337V100_UK.pdf
- Previous versions
- Latest version
Manuals in Russian
- 5337V112_RU.pdf
- 5337V111_RU.pdf
- 5337V110_RU.pdf
- 5337V109_RU.pdf
- 5337V108_RU.pdf
- 5337V107_RU.pdf
- 5337V106_RU.pdf
- 5337V105_RU.pdf
- 5337V104_RU.pdf
- 5337V103_RU.pdf
- 5337V102_RU.pdf
- Previous versions
- Latest version
Approvals & Certificates
ATEX certificate
- 5337A_20ATEX0109X_issue1.pdf
- 5337A_20ATEX0109X_issue0.pdf
- 5337A_03ATEX1508X_issue6.pdf
- 5337A_03ATEX1508X_issue5.pdf
- 5337A_03ATEX1508X_issue4.pdf
- Previous versions
- Latest version
IECEx certificate
- 5337AIEC_200063X_issue1.pdf
- 5337AIEC_200063X_issue0.pdf
- 5337AIEC_100083X_issue4.pdf
- 5337AIEC_100083X_issue3.pdf
- 5337AIEC_100083X_issue2.pdf
- 5337AIEC_100083X_issue1.pdf
- Previous versions
- Latest version
CSA certificate
- 533x_633x_CSA.pdf
- Latest version
INMETRO certificate
- INMETRO_5335_5337_6335_6337_230011X_issue1.pdf
- INMETRO_5335_5337_6335_6337_230011X_issue0.pdf
- INMETRO_5335_5337_180002X_issue1.pdf
- INMETRO_5335_5337_180002X_issue0.pdf
- Previous versions
- Latest version
DNV marine certificate
- DNV_2231_41xx_51xx_53xx.pdf
- Latest version
EAC declaration
- EAC_EMC_declaration_Ex_3000_5000_6000_9000.pdf
- Latest version
EAC declaration
- EAC_Ex.pdf
- Latest version
Metrology Pattern Approval (MPA), Belarus
- MPA_Belarus.pdf
- Latest version
Metrology Pattern Approval (MPA), Kazakhstan
- MPA_Kazakhstan.pdf
- Latest version
Metrology Pattern Approval (MPA), Russia
- MPA_Russia.pdf
- Latest version
Supplementary documentation
EU Declaration of Conformity
- 5337DoC_EU_106_UK.pdf
- 5337DoC_EU_105_UK.pdf
- 5337DoC_EU_104_UK.pdf
- 5337DoC_EU_103_UK.pdf
- 5337DoC_EU_102_UK.pdf
- 5337DoC_EU_101_UK.pdf
- 5337DoC_EU_100_UK.pdf
- Previous versions
- Latest version
CCC statement
- 5000_6000_series_CCC_statement.pdf
- Latest version
FMEDA report
- FMEDA_5337_R026V3R2.pdf
- FMEDA_5337_R026V3R1.pdf
- FMEDA_5337_R026V1R0.pdf
- Previous versions
- Latest version
SIL certificate
- 5335_6335_5337_6337_7501_SIL1_declaration_Potmeter_V2.pdf
- 5335_6335_5337_6337_7501_SIL2_declaration_V2.pdf
HART certificate
- 5337_HART.pdf
- Latest version
PR default configurations
- PR_default_configurations.pdf
- Latest version
Safety note
Safety note
- SN5300-3-118-2624.pdf
- SN5300-3-117-2605.pdf
- SN5300-3-116-2450.pdf
- SN5300-3-115-2418.pdf
- SN5300-3-114-2245.pdf
- SN5300-3-113-2202.pdf
- SN5300-3-112-2139.pdf
- SN5300-3-111-2016.pdf
- SN5300-3-110-1911.pdf
- SN5300-3-109-1838.pdf
- SN5300-3-108-1803.pdf
- SN5300-3-107-1616.pdf
- SN5300-106-1509.pdf
- Previous versions
- Latest version
View variants
Environmental Conditions
| Operating temperature | -40°C to +85°C |
| Calibration temperature | 20...28°C |
| Relative humidity | < 95% RH (non-cond.) |
| Protection degree (encl./terminal) | IP68 / IP00 |
Mechanical specifications
| Dimensions | Ø 44 x 20.2 mm |
| Weight approx. | 50 g |
| Wire size | 1 x 1.5 mm2 stranded wire |
| Screw terminal torque | 0.4 Nm |
| Vibration | IEC 60068-2-6 |
| 2...25 Hz | ±1.6 mm |
| 25...100 Hz | ±4 g |
Common specifications
Supply |
|
| Supply voltage | 8.0...35 VDC |
Isolation voltage |
|
| Isolation voltage, test / working | 1.5 kVAC / 50 VAC |
Response time |
|
| Response time (programmable) | 1...60 s |
| Voltage drop | 8.0 VDC |
| Signal / noise ratio | > 60 dB |
| Programming | HART & PR 5909 Loop Link communications interface |
| Accuracy | Better than 0.05% of selected range |
| Signal dynamics, input | 22 bit |
| Signal dynamics, output | 16 bit |
| EMC immunity influence | < ±0.1% of span |
| Extended EMC immunity: NAMUR NE21, A criterion, burst | < ±1% of span |
Input specifications
Common input specifications |
|
| Max. offset | 50% of selected max. value |
RTD input |
|
| RTD type | Pt50/100/200/500/1000; Ni50/100/120/1000 |
| Cable resistance per wire | 5 Ω (up to 50 Ω per wire is possible with reduced measurement accuracy) |
| Sensor current | Nom. 0.2 mA |
| Effect of sensor cable resistance (3-/4-wire) | < 0.002 Ω / Ω |
TC input |
|
| Thermocouple type | B, E, J, K, L, N, R, S, T, U, W3, W5, LR |
| Cold junction compensation (CJC) | Constant, internal or external via a Pt100 or Ni100 sensor |
Voltage input |
|
| Measurement range | -800...+800 mV |
| Min. measurement range (span) | 2.5 mV |
| Input resistance | 10 MΩ |
Output specifications
Current output |
|
| Signal range | 4…20 mA |
| Min. signal range | 16 mA |
| Load (@ current output) | ≤ (Vsupply - 8) / 0.023 [Ω] |
| Sensor error indication | Programmable 3.5…23 mA |
| NAMUR NE43 Upscale/Downscale | 23 mA / 3.5 mA |
Common output specifications |
|
| Updating time | 440 ms |
| HART protocol revisions | HART 7 and HART 5 |
I.S. / Ex marking
| ATEX | II 3 G Ex nA [ic] IIC T6...T4 Gc, II 3 G Ex ec [ic] IIC T6...T4 Gc, II 3 G Ex ic IIC T6...T4 Gc, II 3 D Ex ic IIIC Dc |
| IECEx | Ex nA [ic] IIC T6…T4 Gc, Ex ec [ic] IIC T6…T4 Gc, Ex ic IIC T6…T4 Gc, Ex ic IIIC Dc |
| CSA | Cl. I, Div. 2, Gp. A, B, C, D T6...T4, Ex nA[ic] IIC T6…T4 Gc |
| INMETRO | Ex ec [ic] IIC T6...T4 Gc, Ex ic IIC T6...T4 Gc, Ex ic IIIC Dc |
Observed authority requirements
| EMC | 2014/30/EU |
| ATEX | 2014/34/EU |
| RoHS | 2011/65/EU |
| EAC | TR-CU 020/2011 |
| EAC Ex | TR-CU 012/2011 |
Approvals
| ATEX | DEKRA 20ATEX0109X |
| IECEx | DEK 20.0063X |
| CSA | 1125003 |
| INMETRO | DEKRA 23.0011X |
| EAC Ex | EAEU KZ 7500361.01.01.08756 |
| DNV Marine | TAA0000101 |
| SIL | Hardware assessed for use in SIL applications |