Universal uni-/bipolar signal transmitter
PR 4104
- Measures and outputs uni-/bipolar voltage and current signals
- Works with both passive and active inputs and outputs
- Uses the PR 4500 display series for programming and process monitoring
- Fast < 20 ms response time and excellent < 0.05% accuracy
- Universally powered by 21.6…253 VAC / 19.2...300 VDC
Application
- Fast < 20 ms response time for measuring signals produced by torque, position, current & acceleration sensors.
- User configurable bipolar or unipolar I/O means the 4104 is suitable for nearly any voltage or current conversion.
- The excitation source enables measurement of two or three wire transmitters.
- The active or passive I/O makes the 4104 perfect for power matching current loops.
- Converts narrow bipolar inputs to wide bipolar or unipolar outputs, e.g., ±1 volt input = ±10 volt or 4...20 mA output.
- Selectable direct or inverse I/O makes the 4104 suitable for proportional control applications.
- The ”V-curve” function outputs 100% – 0 – 100% when a 0 – 100% input signal is present.
Technical characteristics
- The latest analog and digital techniques are used to obtain maximum accuracy and immunity to interference.
- The current output can drive up to 800 Ohms, with an adjustable response time of 0.0…60.0 seconds.
- Exceptional mA output load stability of < 0.001% of span/100 Ohm.
- Meets the NAMUR NE21 recommendations, ensuring high accuracy in harsh EMC environments.
- Meets the NAMUR NE43 recommendations, allowing the control system to easily detect a sensor error.
- Each unit is tested to a high 2.3 kVAC, 3-port galvanic isolation level.
- Excellent signal to noise ratio of > 60 dB.
Mounting / installation / programming
- Very low power consumption means units can be mounted side by side without an air gap – even at 60°C ambient temperature.
- Approved for marine applications.
- Configuration, monitoring, 2-point process calibration and more are accomplished using PR's 4500 series of detachable displays.
- All programming can be password protected.
Note
- If you need an installation instruction in hard copy, you can order it for free when placing your order.
Data sheet & Manuals
Data sheet
- 4104.pdf
- Latest version
Manuals
- 4104V103_UK.pdf
- 4104V102_UK.pdf
- 4104V101_UK.pdf
- 4104V100_UK.pdf
- Previous versions
- Latest version
Manuals in Russian
- 4104V103_RU.pdf
- 4104V102_RU.pdf
- 4104V101_RU.pdf
- Previous versions
- Latest version
Supplementary documentation
EU Declaration of Conformity
- 4104DoC_EU_103_UK.pdf
- 4104DoC_EU_102_UK.pdf
- 4104DoC_EU_101_UK.pdf
- 4104DoC_EU_100_UK.pdf
- Previous versions
- Latest version
UKCA Declaration of Conformity
- 4104DoC_UKCA_100_UK.pdf
- Latest version
Modbus configuration manual
- 4104_MCM_101.pdf
- 4104_MCM_100.pdf
- Previous versions
- Latest version
EAC LVD declaration
- 4000_EMC_data.pdf
- Latest version
PR default configurations
- PR_default_configurations.pdf
- Latest version
China RoHS
- China_RoHS.pdf
- Latest version
Approvals & Certificates
FM certificate
- 4104_14_16_31_4222_FM.pdf
- Latest version
UL certificate
- 4104_4179_4179B_4184_UL.pdf
- Latest version
DNV marine certificate
- DNV_2231_41xx_51xx_53xx.pdf
- Latest version
EAC declaration
- EAC-Declaration.pdf
- Latest version
Metrology Pattern Approval (MPA), Russia
- MPA_Russia.pdf
- Latest version
View variants
Environmental Conditions
| Operating temperature | -20°C to +60°C |
| Storage temperature | -20°C to +85°C |
| Calibration temperature | 20...28°C |
| Relative humidity | < 95% RH (non-cond.) |
| Protection degree | IP20 |
| Installation in | Pollution degree 2 & meas. / overvoltage cat. II |
Mechanical specifications
| Dimensions (HxWxD) | 109 x 23.5 x 104 mm |
| Weight approx. | 155 g |
| Weight incl. 4501 / 451x (approx.) | 170 g / 185 g |
| DIN rail type | DIN EN 60715/35 mm |
| Wire size | 0.13...2.08 mm2 AWG 26...14 stranded wire |
| Screw terminal torque | 0.5 Nm |
| Vibration | IEC 60068-2-6 |
| 2...13.2 Hz | ±1 mm |
| 13.2...100 Hz | ±0.7 g |
Common specifications
Supply |
|
| Supply voltage, universal | 21.6...253 VAC, 50...60 Hz or 19.2...300 VDC |
| Max. required power | ≤ 2.5 W |
| Max. power dissipation | ≤ 2.5 W |
Isolation voltage |
|
| Isolation voltage, test / working | 2.3 kVAC / 250 VAC |
Response time |
|
| Response time (0...90%, 100...10%) | < 20 ms |
Auxiliary supplies |
|
| 2-wire loop supply | > 16 V / 20 mA |
| 3-wire loop supply | > 18 V / 20 mA |
| Loop supply limitation | 30 mA |
| Programming | PR 4500 communication interfaces |
| Signal / noise ratio | > 60 dB |
| Cut-off frequency (3 dB) | > 40 Hz |
| Accuracy | Better than 0.05% of selected range |
| EMC immunity influence | < ±0.5% of span |
| Extended EMC immunity: NAMUR NE21, A criterion, burst | < ±1% of span |
Input specifications
Current input |
|
| Signal range | ±23 mA |
| Programmable measurement ranges |
0...20 and 4...20 mA
± 10 and ± 20 mA |
| Input voltage drop | 1.4 V @ 20 mA |
| Loop error detection, 4...20 mA: Low | < 3.6 mA |
| Loop error detection, 4...20 mA: High | > 21 mA |
Voltage input |
|
| Signal range | ±12 V |
| Programmable measurement ranges |
0/0.2...1, 0/1...5, 0/2...10 VDC
±1, ±5 and ±10 V |
| Input resistance | > 2 MΩ |
Output specifications
Current output |
|
| Signal range |
0...23 mA (unipolar)
-23...+23 mA (bipolar) |
| Current limit |
≤ 28 mA (unipolar)
± 28 mA (bipolar) |
| Load stability | ≤ 0.001% of span / 100 Ω |
| Response time, programmable | 0.0...60.0 s |
| Output limitation, on 4...20 and 20...4 mA signals | 3.8...20.5 mA |
| Output limitation, on other unipolar mA signals | 0 and 115% of max. value |
| Output limitation, on bipolar mA signals | ±115% of min. & max. values |
| Sensor error indication, at 4...20 mA input: selectable | Low, High, Zero, None |
Active unipolar and bipolar mA output |
|
| Programmable ranges |
0...20 and 4...20 mA
±10 and ±20 mA Direct or Inverted Action |
| V-curve function, active signals, 100-0-100% | 20-0-20 mA |
| Load (@ current output) | ≤ 800 Ω |
Passive 2-wire mA output |
|
| Programmable ranges |
0...20 and 4...20 mA
Direct or Inverted action |
| V-curve function, 100-0-100% | 20-0-20 mA |
| External loop supply | 3.5 - 26 V |
Voltage output |
|
| Programmable signal ranges |
0/0.2...1; 0/1...5 ; 0/2...10 V
±1, ±5 and ±10 V Direct or Inverted action |
| V-curve function, 100-0-100% | 1-0-1, 5-0-5 and 10-0-10 V |
| Load (@ voltage output) | ≥ 500 kΩ |
| Response time, programmable | 0.0...60.0 s |
| Output limitation - outside range: on unipolar V signals starting from 0 | 0 and 115% of max. value |
| Output limitation - outside range: on unipolar V signals with offset | -5% of min. value and 115% of max. value |
| Output limitation - outside range: on bipolar V signals | ±115% of min. & max. values |
| Sensor error indication, at 4...20 mA input: selectable | Low, High, Zero, None |
Observed authority requirements
| EMC | 2014/30/EU & UK SI 2016/1091 |
| LVD | 2014/35/EU & UK SI 2016/1101 |
| RoHS | 2011/65/EU & UK SI 2012/3032 |
| EAC | TR-CU 020/2011 |
Approvals
| c UL us, UL 508 | E248256 |
| FM | 3025177 |
| DNV Marine | TAA0000101 |