2231
 

Trip amplifier

 

2231

 

  • AC/DC trip amplifier
  • 2 adjustable alarm limits
  • Galvanically isolated 3.75 kVAC
  • Front-programmable
  • 3-digit LED display
  • 24 VDC or universal supply
  1. Überblick + -

  2. Technische Merkmale + -

  3. Zubehör + -


Advanced features

  • The front-operated push buttons are used for programming the different standard functions.
  • A password can prevent access for changing parameters.

Application

  • Alarm detector in connection with measurement of AC/DC current or voltage signals.
  • The unit is used where accurate setpoint setting and different alarm functions are required.
  • The unit can be used as a single or dual trip amplifier.
  • Used in applications where programmable parameters such as hysteresis, setpoint, reset, active relay for increasing or decreasing signal, delay and input signal need to be set.

Technical characteristics

  • 3-digit display showing the input signal in %.
  • Two LED indicating relay status.
  • 3 pushbuttons for programming.
  • Standard DC current input signals in the range 0...20 mA.
  • DC voltage signals in the range 0...250 VDC.
  • AC current signals up to 1 A.
  • True RMS measurement of AC voltage signals in the range 0...250 VAC.
  • Mounting for a standard 11-pole socket which can be adapted for DIN rail or plate use with PR’s 7023 adaptor and 7024 mounting keying.

Datenblatt & Handbücher


Datenblatt

Handbuch

Handbücher in Russisch

Unterstützende Dokumentation


EU-Konformitätserklärung

Sicherheitshinweise


Sicherheitshinweise

Zulassungen & Zertifikate


DNV Marine-Zertifikat

EAC-Erklärung

Metrology Pattern Approval (MPA), Russia

Environmental Conditions

Operating temperature -20°C to +60°C
Calibration temperature 20...28°C
Relative humidity < 95% RH (non-cond.)
Protection degree IP50

Mechanical specifications

Dimensions (HxWxD) 80.5 x 35.5 x 84.5 mm (D is without pins)
Weight DC / universally supplied 125 g / 175 g

Common specifications

Supply

Supply voltage 19.2...28.8 VDC
Supply voltage, universal 21.6...253 VAC, 50...60 Hz or 19.2...300 VDC
Internal power dissipation 1.5 W (2231D) 2 W (2231P)

Isolation voltage

Isolation voltage, test / working 3.75 kVAC / 250 VAC
PELV/SELV IEC 61140

Response time

Response time (programmable) 0.25...60 s (DC) 0.75...60 s (AC)
Updating time 100 ms
Accuracy Better than 0.1% of sel. range
Signal dynamics, input 16 bit
Effect of supply voltage change < ±0.002% of span / %V
Temperature coefficient < ±0.01% of span /°C (DC signals) < ±0.02% of span /°C (AC signals)
Linearity error < 0.1% of span < ±0.35% of span 50...1000 Hz (AC sine wave signals)
EMC immunity influence < ±0.5%

Input specifications

Common input specifications

Max. offset 50% of selected max. value

Current input

Measurement range 0...20 mA
Min. measurement range (span) 10 mA
Input resistance 50 Ω

AC current input

Measurement range 0...1 ARMS
Min. measurement range (span) 0.5 ARMS
Input resistance 1 Ω / 2 W

Voltage input

Measurement range 0...250 VDC
Min. measurement range (span) 0.5 VDC
Input resistance Nom. 5 MΩ

AC voltage input

AC voltage input 0...250 VRMS
Min. measurement range (span) 0.5 VRMS
Input resistance Nom. 5 MΩ

Output specifications

Relay output

Hysteresis 0...99.9% of span
ON and OFF delay 0.0...99.9 s
Max. voltage 250 VRMS
Max. current 2 AAC
Max. AC power 500 VA
Max. load at 24 VDC 1 A

Common output specifications

Updating time 100 ms
Relay outputs: Setpoint setting 0...99.9% of span
of span = of the presently selected range

Observed authority requirements

EMC 2014/30/EU
LVD 2014/35/EU
RoHS 2011/65/EU
EAC TR-CU 020/2011

Approvals

DNV Marine TAA0000101
 

War diese Information hilfreich?

 

Bewerten Sie uns

Ihre Anfrage wurde erfolgreich versendet 0 Artikel in Ihrer Liste
Ihre Kontaktdaten
Bitte geben Sie Ihren Vornamen ein
Bitte geben Sie Ihren Nachnamen ein
Bitte geben Sie eine gültige E-Mail-Adresse ein
Bitte geben Sie eine gültige Telefonnummer ein. Bitte verwenden Sie nur Ziffern.
Bitte geben Sie Ihre Berufsbezeichnung ein
Bitte geben Sie Ihren Unternehmensnamen ein.
Bitte geben Sie die Firmenadresse ein.
Bitte geben Sie eine gültige Postleitzahl ein
Bitte geben Sie die Stadt ein
Bitte wählen Sie ein Land aus
Bitte lesen Sie sich die Datenschutzrichtlinien durch und stimmen Sie diesen zu.
Sie haben Ihrer Anfrageliste keine Produkte hinzugefügt
Wenn Sie auf der Website surfen, können Sie Produkte zu einer Anfrageliste hinzufügen, indem Sie einfach auf den einzelnen Produktseiten auf "Zur Anfrageliste hinzufügen" klicken. Wenn alle relevanten Produkte enthalten sind, senden Sie die Liste an uns und Sie erhalten innerhalb von 24 Stunden ein Angebot. Wenn Sie die Liste nicht einreichen, ist sie 21 Tage lang auf der Website verfügbar. Wir hoffen, dass Sie die Funktionalität nützlich finden.
Vielen Dank für Ihre Anfrage. Wir werden uns innerhalb von 24 Stunden telefonisch oder per E-Mail bei Ihnen melden.

Brauchen Sie Hilfe?

Wenn Sie Support benötigen, können Sie sich jederzeit an uns wenden

Bleiben Sie auf dem Laufenden!

Hier für den Newsletter registrieren