5223B
Programmable f/I-f/f converter
- Pulse calculator / frequency generator
- Galvanic isolation
- ATEX I.S. version
- Analog current and voltage output
- PNP / NPN output, optional relays
- Universal supply
Advanced features
- The 5223 transmitter can be configured with a standard PC and the Loop Link communications unit, or delivered fully configured.
Application
- The f/I function performs frequency to current and voltage conversion.
- The f/f function can be used for pulse division or multiplication and as a buffer collecting fast pulse trains.
- A scale factor may be entered in all functions. Using both digital inputs, pulse addition or subtraction are possible.
- The frequency generator function is used as e.g. a time base or clock generator.
- Input and supply polarity reversal protection.
- Current and voltage output signals galvanically separated from the supply and the inputs.
- Programmable digital outputs including NPN, PNP or relay options.
- ATEX units have input for mechanical contact and NAMUR inductive proximity sensor.
Technical characteristics
- 5 front LEDs, indicating f1 and f2 active inputs (not NPN), Dig.out.1 and 2 active outputs, and a programmable error signal.
- Analog current output can be configured to any current within 0...20 mA range.
- Voltage output range is selectable between 0...10 VDC and 0...1 VDC by use of internal jumpers.
- Input range:
Frequency: 0...20,000 Hz
Sensor types: NAMUR, tacho, NPN, PNP, TTL, S0
- Output range:
Current and voltage output: 0...20 mA / 0...10 V
Relay outputs: 0...20 Hz
NPN and PNP output as f/f: 0...1000 Hz
NPN and PNP output as generator: 0...20,000 Hz
Environmental Conditions
Operating temperature | -20°C to +60°C |
Calibration temperature | 20...28°C |
Relative humidity | < 95% RH (non-cond.) |
Protection degree | IP20 |
Mechanical specifications
Dimensions (HxWxD) | 109 x 23.5 x 130 mm |
Weight approx. | 240 g |
DIN rail type | DIN 46277 |
Wire size | 1 x 2.5 mm2 stranded wire |
Screw terminal torque | 0.5 Nm |
Common specifications
Supply |
|
Supply voltage, universal | 21.6...253 VAC, 50...60 Hz or 19.2...300 VDC |
Fuse | 400 mA SB / 250 VAC |
Max. required power | 3.5 W |
Internal power dissipation | 3 W |
Isolation voltage |
|
Isolation voltage, test / working | 3.75 kVAC / 250 VAC |
PELV/SELV | IEC 61140 |
Power-up delay | 0...999 s |
Warm-up time | 1 min. |
Programming | Loop Link |
Signal / noise ratio | Min. 60 dB |
Response time, analog | < 60 ms + period |
Response time, digital output | < 50 ms + period |
Effect of supply voltage change | < 0.005% of span / VDC |
Temperature coefficient | < ±0.01% of span / °C |
Linearity error | < 0.1% of span |
NAMUR supply I.S. / Ex | 8.9 VDC ±0.5 VDC / 8 mA |
EMC immunity influence | < ±0.5% |
Input specifications
Common input specifications |
|
Max. offset | 90% of selected max. frequency |
Measurement range | 0...20 kHz |
Min. measurement range | 0.001 Hz |
Min. pulse length | 25 μs |
Input types | NAMUR acc. to DIN 19234 |
Output specifications
Common output specifications |
|
Updating time | 20 ms |
Current output |
|
Signal range | 0...20 mA |
Min. signal range | 5 mA |
Load (@ current output) | ≤ 600 Ω |
Load stability | ≤ 0.01% of span / 100 Ω |
Current limit | < 23 mA |
Voltage output |
|
Signal range | 0...10 VDC |
Min. signal range | 250 mV |
Load (@ voltage output) | ≥ 500 kΩ |
Relay output |
|
Max. switching frequency | 20 Hz |
Max. voltage | 250 VRMS |
Max. current | 2 AAC |
Max. AC power | 100 VA (I.S. version 5223B) |
Max. load at 24 VDC | 1 A |
Other output types |
Active outputs (NPN / PNP)
f/f converter output Frequency generator |
of span | = of the presently selected range |
Observed authority requirements
EMC | 2014/30/EU |
LVD | 2014/35/EU |
EAC | TR-CU 020/2011 |
Approvals
ATEX | KEMA 04ATEX1001 |
EAC Ex | RU C-DK.GB08.V.00410 |