2-wire programmable transmitter
5131B
- Input for RTD, TC, mV, linear resistance, mA, and V
- 3.75 kVAC galvanic isolation
- 4...20 mA loop output
- 1- and 2-channel versions
- ATEX Ex / I.S. version
- DIN rail mounting
Advanced features
- The 5131 transmitter can be configured with a standard PC and the Loop Link communications unit.
Application
- Independent channel jumper selectable inputs for current/voltage or temperature.
- Current input programmable in range the 0...100 mA and voltage inputs in the range 0...250 VDC.
- Linearized, electronic temperature measurement with RTD or TC sensor.
- Conversion of linear resistance variation to a standard analog current / voltage signal, for example from solenoids and butterfly valves or linear movements with attached potentiometer.
- 4- or 3-wire connection with automatic cable compensation or 2-wire connection with programmable cable compensation.
- Configurable sensor error detection including NAMUR NE43.
Technical characteristics
- The 2-channel version has full galvanic isolation between the channels.
- Separation of circuits in PELV/SELV installations.
- I.S. barrier for temperature sensors, potentiometers and current / voltage signals.
Datablad & Manualer
Datablad
- 5131B.pdf
- Senaste versionen
Manualer
- 5131V105_UK.pdf
- 5131V104_UK.pdf
- 5131V103.pdf
- Tidigare versioner
- Senaste versionen
Manualer på ryska
- 5131V105_RU.pdf
- 5131V104_RU.pdf
- Tidigare versioner
- Senaste versionen
Godkännanden och certifikat
Ex-certifikat
- 5131B.pdf
- Senaste versionen
EAC-försäkran
- EAC-Declaration.pdf
- Senaste versionen
EAC Ex-certifikat
- EAC_Ex.pdf
- Senaste versionen
Metrology Pattern Approval (MPA), Russia
- MPA_Russia.pdf
- Senaste versionen
Kompletterande dokumentation
EU försäkran om överensstämmelse
- 5131DoC_EU_103_UK.pdf
- 5131DoC_EU_102_UK.pdf
- 5131DoC_EU_101_UK.pdf
- 5131DoC_EU_100_UK.pdf
- Tidigare versioner
- Senaste versionen
Säkerhetsanvisningar
Säkerhetsanvisningar
- SN5000-2_109_2220.pdf
- SN5000-2_107_1924.pdf
- SN5000-2_106_1825.pdf
- SN5000-2_105_1811.pdf
- SN5000-2_104_1725.pdf
- SN5000-2_103_1625.pdf
- SN5000-2_102_1613.pdf
- SN5000_101_1450.pdf
- Tidigare versioner
- Senaste versionen
Environmental Conditions
Operating temperature | -20°C to +60°C |
Calibration temperature | 20...28°C |
Relative humidity | < 95% RH (non-cond.) |
Protection degree | IP20 |
Mechanical specifications
Dimensions (HxWxD) | 109 x 23.5 x 130 mm |
Weight approx. | 195 g |
DIN rail type | DIN EN 60715/35 mm |
Wire size | 0.13...2.08 mm2 AWG 26...14 stranded wire |
Screw terminal torque | 0.5 Nm |
Common specifications
Supply |
|
Supply voltage | 7.5...35 VDC |
Fuse | 50 mA SB / 250 VAC |
Isolation voltage |
|
Isolation voltage, test / working | 3.75 kVAC / 250 VAC |
PELV/SELV | IEC 61140 |
Response time |
|
Temperature input, programmable (0...90%, 100...10%) | 400 ms...60 s |
mA / V input (programmable) | 250 ms...60 s |
Programming | Loop Link |
Signal / noise ratio | Min. 60 dB (0...100 kHz) |
Updating time |
115 ms (temperature input)
75 ms (mA / V / mV input) |
Signal dynamics, input | 22 bit |
Signal dynamics, output | 16 bit |
Effect of supply voltage change | < 0.005% of span / VDC |
EMC immunity influence | < ±0.5% of span |
Extended EMC immunity: NAMUR NE21, A criterion, burst | < ±1% of span |
Input specifications
Common input specifications |
|
Max. offset | 50% of selected max. value |
RTD input |
|
RTD type | Pt100, Ni100, lin. R |
Cable resistance per wire | 10 Ω (max.) |
Sensor current | Nom. 0.2 mA |
Effect of sensor cable resistance (3-/4-wire) | < 0.002 Ω / Ω |
Sensor error detection | Yes |
TC input |
|
Thermocouple type | B, E, J, K, L, N, R, S, T, U, W3, W5, LR |
Cold junction compensation (CJC) | < ±1.0°C |
Sensor error current | Nom. 30 μA |
Sensor error detection | Yes |
Current input |
|
Measurement range | 0...100 mA |
Min. measurement range (span) | 4 mA |
Input resistance: Supplied unit | Nom. 10 Ω + PTC 10 Ω |
Input resistance: Non-supplied unit | RSHUNT = ∞, VDROP < 6 V |
mV input |
|
Measurement range | -150...+150 mV |
Voltage input |
|
Measurement range | 0...250 VDC |
Min. measurement range (span) | 5 mV |
Input resistance |
Nom. 10 MΩ (≤ 2.5 VDC)
Nom. 5 MΩ (> 2.5 VDC) Nom. 10 MΩ (mV input) |
Output specifications
Current output |
|
Signal range | 4…20 mA |
Min. signal range | 10 mA |
Load (@ current output) | ≤ (Vsupply -7.5)/0.023 [Ω] |
Load stability | ≤ 0.01% of span / 100 Ω |
Current limit | ≤ 28 mA |
Sensor error indication | Programmable 3.5…23 mA |
NAMUR NE43 Upscale/Downscale | 23 mA / 3.5 mA |
of span | = of the presently selected range |
Observed authority requirements
EMC | 2014/30/EU |
LVD | 2014/35/EU |
ATEX | 2014/34/EU |
RoHS | 2011/65/EU |
EAC | TR-CU 020/2011 |
EAC Ex | TR-CU 012/2011 |
Approvals
ATEX | DEMKO 99ATEX124572, II (1) GD [EEx ia] IIC |
EAC Ex | RU C-DK.HA65.B.00355/19 |

7423
Ceramic socket for Pt100 sensor
7430B
Pt100 cable sensor
7430C
Pt100 cable sensor
7440
Thermowell for PR 7400 Pt100 sensor
5909
Loop Link communications interface
5910Ex
CJC connector
5913Ex
CJC connector
7007
2-digit digital potentiometer
7008
3-digit digital potentiometer
7009
10-turn potentiometer, 200 Ω
7011
Dial for 10-turn potentiometer
7012
1-turn potentiometer, 1 kΩ
7020
Knob for 1-turn potentiometer
7020A
Knob for 10-turn potentiometer