4104
 

Universal uni-/bipolar signal transmitter

 

4104

 

  • Measures and outputs uni-/bipolar voltage and current signals
  • Works with both passive and active inputs and outputs
  • Uses the PR 45xx display for programming and process monitoring
  • Fast < 20 ms response time and excellent < 0.05% accuracy
  • Universally powered by 21.6…253 VAC / 19.2...300 VDC
  1. Översikt + -

  2. Tekniska data + -

  3. Tillbehör + -


Application

  • Fast < 20 ms response time for measuring signals produced by torque, position, current & acceleration sensors.
  • User configurable bipolar or unipolar I/O means the 4104 is suitable for nearly any voltage or current conversion.
  • The excitation source enables measurement of two or three wire transmitters.
  • The active or passive I/O makes the 4104 perfect for power matching current loops.
  • Converts narrow bipolar inputs to wide bipolar or unipolar outputs, e.g., ±1 volt input = ±10 volt or 4...20 mA output.
  • Selectable direct or inverse I/O makes the 4104 suitable for proportional control applications.
  • The ”V-curve” function outputs 100% – 0 – 100% when a 0 – 100% input signal is present.

Technical characteristics

  • The latest analog and digital techniques are used to obtain maximum accuracy and immunity to interference.
  • The current output can drive up to 800 Ohms, with an adjustable response time of 0.0…60.0 seconds.
  • Exceptional mA output load stability of < 0.001% of span/100 Ohm.
  • Meets the NAMUR NE21 recommendations, ensuring high accuracy in harsh EMC environments.
  • Meets the NAMUR NE43 recommendations, allowing the control system to easily detect a sensor error.
  • Each unit is tested to a high 2.3 kVAC, 3-port galvanic isolation level.
  • Excellent signal to noise ratio of > 60 dB.

Mounting / installation / programming

  • Very low power consumption means units can be mounted side by side without an air gap – even at 60°C ambient temperature.
  • Approved for marine applications.
  • Configuration, monitoring, 2-point process calibration and more are accomplished using PR's 45xx detachable displays.
  • All programming can be password protected.

Datablad & Manualer


Datablad

Manualer

Manualer på ryska

Kompletterande dokumentation


EU försäkran om överensstämmelse

UKCA försäkran om överensstämmelse

Modbus konfigurationsmanual

EMC-data

Säkerhetsanvisningar


Säkerhetsanvisningar

Godkännanden och certifikat


FM-certifikat

UL-certifikat

DNV-certifikat

EAC-försäkran

Metrology Pattern Approval (MPA), Russia

Environmental Conditions

Operating temperature -20°C to +60°C
Storage temperature -20°C to +85°C
Calibration temperature 20...28°C
Relative humidity < 95% RH (non-cond.)
Protection degree IP20
Installation in Pollution degree 2 & meas. / overvoltage cat. II

Mechanical specifications

Dimensions (HxWxD) 109 x 23.5 x 104 mm
Dimensions (HxWxD) w/ 4501/451x 109 x 23.5 x 116 / 131 mm
Weight approx. 155 g
Weight incl. 4501 / 451x (approx.) 170 g / 185 g
DIN rail type DIN EN 60715/35 mm
Wire size 0.13...2.08 mm2 AWG 26...14 stranded wire
Screw terminal torque 0.5 Nm
Vibration IEC 60068-2-6
2...13.2 Hz ±1 mm
13.2...100 Hz ±0.7 g

Common specifications

Supply

Supply voltage, universal 21.6...253 VAC, 50...60 Hz or 19.2...300 VDC
Max. required power ≤ 2.5 W
Max. power dissipation ≤ 2.5 W

Isolation voltage

Isolation voltage, test / working 2.3 kVAC / 250 VAC

Response time

Response time (0...90%, 100...10%) < 20 ms

Auxiliary supplies

2-wire loop supply > 16 V / 20 mA
3-wire loop supply > 18 V / 20 mA
Loop supply limitation 30 mA
Programming PR 4500 communication interfaces
Signal / noise ratio > 60 dB
Cut-off frequency (3 dB) > 40 Hz
Accuracy Better than 0.05% of selected range
EMC immunity influence < ±0.5% of span
Extended EMC immunity: NAMUR NE21, A criterion, burst < ±1% of span

Input specifications

Current input

Signal range ±23 mA
Programmable measurement ranges 0...20 and 4...20 mA ± 10 and ± 20 mA
Input voltage drop 1.4 V @ 20 mA
Loop error detection, 4...20 mA: Low < 3.6 mA
Loop error detection, 4...20 mA: High > 21 mA

Voltage input

Signal range ±12 V
Programmable measurement ranges 0/0.2...1, 0/1...5, 0/2...10 VDC ±1, ±5 and ±10 V
Input resistance > 2 MΩ

Output specifications

Current output

Signal range 0...23 mA (unipolar) -23...+23 mA (bipolar)
Current limit ≤ 28 mA (unipolar) ± 28 mA (bipolar)
Load stability ≤ 0.001% of span / 100 Ω
Response time, programmable 0.0...60.0 s
Output limitation, on 4...20 and 20...4 mA signals 3.8...20.5 mA
Output limitation, on other unipolar mA signals 0 and 115% of max. value
Output limitation, on bipolar mA signals ±115% of min. & max. values
Sensor error indication, at 4...20 mA input: selectable Low, High, Zero, None

Active unipolar and bipolar mA output

Programmable ranges 0...20 and 4...20 mA ±10 and ±20 mA
Direct or Inverted Action
V-curve function, active signals, 100-0-100% 20-0-20 mA
Load (@ current output) ≤ 800 Ω

Passive 2-wire mA output

Programmable ranges 0...20 and 4...20 mA Direct or Inverted action
V-curve function, 100-0-100% 20-0-20 mA
External loop supply 3.5 - 26 V

Voltage output

Programmable signal ranges 0/0.2...1; 0/1...5 ; 0/2...10 V ±1, ±5 and ±10 V
Direct or Inverted action
V-curve function, 100-0-100% 1-0-1, 5-0-5 and 10-0-10 V
Load (@ voltage output) ≥ 500 kΩ
Response time, programmable 0.0...60.0 s
Output limitation - outside range: on unipolar V signals starting from 0 0 and 115% of max. value
Output limitation - outside range: on unipolar V signals with offset -5% of min. value and 115% of max. value
Output limitation - outside range: on bipolar V signals ±115% of min. & max. values
Sensor error indication, at 4...20 mA input: selectable Low, High, Zero, None

Observed authority requirements

EMC 2014/30/EU
LVD 2014/35/EU
RoHS 2011/65/EU
EAC TR-CU 020/2011

Approvals

c UL us, UL 508 E248256
FM 3025177
DNV Marine TAA0000101
 

Är denna information användbar?

 

Betygsätt oss

Din förfrågan har skickats. 0 artiklar på din lista
Er kontaktinformation
Vänligen ange ditt förnamn
Vänligen ange ditt efternamn
Vänligen ange en giltig e-postadress
Vänligen ange ett giltigt telefonnummer. Använd endast siffror.
Vänligen ange din jobbtitel
Vänligen ange ditt företagsnamn
Vänligen ange din företagsadress
Vänligen ange ett giltigt postnummer
Vänligen ange en stad
Välj land
Läs och godkänn PR electronics sekretesspolicy.
Du har inte lagt till några produkter i din offertlista
När du surfar på webbplatsen kan du lägga till produkter i en offertlista genom att helt enkelt klicka på "Lägg till offertlistan" på de enskilda produktsidorna. När alla relevanta produkter ingår, skicka listan till oss så får du en offert inom 24 timmar. Om du inte skickar listan kommer den att finnas tillgänglig på webbplatsen i 21 dagar. Vi hoppas att du finner funktionaliteten användbar.
Tack för att du begär en offert. Vi återkommer via telefon eller e-post inom 24 timmar.

Behövs hjälp?

Om du behöver support är du alltid välkommen att kontakta oss

Håll dig uppdaterad!

Registrera dig här för att få vårt nyhetsbrev