5337A
 

2-wire transmitter with HART protocol

 

5337A

 

  • RTD, TC, Ohm, and bipolar mV input
  • 2 analog inputs and 5 device variables with status available
  • HART protocol revision selectable from HART 5 or HART 7
  • Hardware assessed for use in SIL applications
  • Mounting in Safe area or Zone 2/22
  1. Översikt + -

  2. Tekniska data + -

  3. Tillbehör + -


Application

  • Linearized temperature measurement with TC and RTD sensors e.g. Pt100 and Ni100.
  • HART communication and 4...20 mA analog PV output for individual, difference or average temperature measurement of up to two RTD or TC input sensors.
  • Conversion of linear resistance to a standard analog current signal, e.g from valves or Ohmic level sensors.
  • Amplification of bipolar mV signals to standard 4...20 mA current signals.
  • Up to 63 transmitters (HART 7) can be connected in a multidrop communication setup.

Technical characteristics

  • HART protocol revision can be changed by user configuration to either HART 5 or HART 7 protocol.
  • The HART 7 protocol offers:
    ∙ Long Tag numbers of up to 32 characters.
    ∙ Enhanced Burst Mode and Event notification with time stamping.
    ∙ Device variable and status mapping to any dynamic variable PV, SV, TV or QV.
    ∙ Process signal trend measurement with logs and summary data.
    ∙ Automatic event notification with time stamps.
    ∙ Command aggregation for higher communication efficiency.
  • 5337A is designed according to strict safety requirements and is therefore suitable for applications in SIL installations.
  • Continuous check of vital stored data.
  • Meeting the NAMUR NE21 recommendations, the 5337 HART transmitter ensures top measurement performance in harsh EMC environments. Additionally, the 5337 meets NAMUR NE43 and NE89 recommendations.

Mounting / installation

  • For DIN form B sensor head or DIN rail mounting via the PR fitting type 8421.
  • Configuration via standard HART communication interfaces or by PR 5909 Loop Link.

Datablad & Manualer


Datablad

Manualer

Manualer på ryska

Godkännanden och certifikat


ATEX-certifikat

IECEx-certifikat

CSA-certifikat

INMETRO-certifikat

DNV-certifikat

EAC-försäkran

EAC Ex-certifikat

Metrology Pattern Approval (MPA)

Kompletterande dokumentation


EU försäkran om överensstämmelse

CCC-uttalande

FMEDA-rapport

SIL-försäkran

HART-certifikat

Säkerhetsanvisningar

Environmental Conditions

Operating temperature -40°C to +85°C
Calibration temperature 20...28°C
Relative humidity < 95% RH (non-cond.)
Protection degree (encl./terminal) IP68 / IP00

Mechanical specifications

Dimensions Ø 44 x 20.2 mm
Weight approx. 50 g
Wire size 1 x 1.5 mm2 stranded wire
Screw terminal torque 0.4 Nm
Vibration IEC 60068-2-6
2...25 Hz ±1.6 mm
25...100 Hz ±4 g

Common specifications

Supply

Supply voltage 8.0...35 VDC

Isolation voltage

Isolation voltage, test / working 1.5 kVAC / 50 VAC

Response time

Response time (programmable) 1...60 s
Voltage drop 8.0 VDC
Signal / noise ratio > 60 dB
Programming Loop Link & HART
Accuracy Better than 0.05% of selected range
Signal dynamics, input 22 bit
Signal dynamics, output 16 bit
EMC immunity influence < ±0.1% of span
Extended EMC immunity: NAMUR NE21, A criterion, burst < ±1% of span

Input specifications

Common input specifications

Max. offset 50% of selected max. value

RTD input

RTD type Pt50/100/200/500/1000; Ni50/100/120/1000
Cable resistance per wire 5 Ω (up to 50 Ω per wire is possible with reduced measurement accuracy)
Sensor current Nom. 0.2 mA

TC input

Thermocouple type B, E, J, K, L, N, R, S, T, U, W3, W5, LR
Cold junction compensation (CJC) Constant, internal or external via a Pt100 or Ni100 sensor

Voltage input

Measurement range -800...+800 mV
Min. measurement range (span) 2.5 mV
Input resistance 10 MΩ

Output specifications

Current output

Signal range 4…20 mA
Min. signal range 16 mA
Load (@ current output) ≤ (Vsupply - 8) / 0.023 [Ω]
Sensor error indication Programmable 3.5…23 mA
NAMUR NE43 Upscale/Downscale 23 mA / 3.5 mA

Common output specifications

Updating time 440 ms
HART protocol revisions HART 7 and HART 5

I.S. / Ex marking

ATEX II 3 G Ex nA [ic] IIC T4...T6 Gc, II 3 G Ex ic IIC T4...T6 Gc, II 3 D Ex ic IIIC Dc
IECEx Ex nA [ic] IIC T4...T6 Gc, Ex ic IIC T4...T6 Gc, Ex ic IIIC Dc
CSA Cl. I, Div. 2, Gp. A, B, C, D T6...T4, Ex nA[ic] IIC T6…T4 Gc
INMETRO Ex nA [ic] IIC T6...T4 Gc, Ex ic IIC T6...T4 Gc, Ex ic IIIC Dc

Observed authority requirements

EMC 2014/30/EU
ATEX 2014/34/EU
RoHS 2011/65/EU
EAC TR-CU 020/2011
EAC Ex TR-CU 012/2011

Approvals

DNV Marine TAA0000101
ATEX KEMA 03ATEX1508 X
IECEx KEM 10.0083X
CSA 1125003
INMETRO DEKRA 18.0002X
EAC Ex RU C-DK.HA65.B.00355/19
SIL Hardware assessed for use in SIL applications
 

Är denna information användbar?

 

Betygsätt oss

Din förfrågan har skickats. 0 artiklar på din lista
Er kontaktinformation
Vänligen ange ditt förnamn
Vänligen ange ditt efternamn
Vänligen ange en giltig e-postadress
Vänligen ange ett giltigt telefonnummer. Använd endast siffror.
Vänligen ange din jobbtitel
Vänligen ange ditt företagsnamn
Vänligen ange din företagsadress
Vänligen ange ett giltigt postnummer
Vänligen ange en stad
Välj land
Läs och godkänn PR electronics sekretesspolicy.
Du har inte lagt till några produkter i din offertlista
När du surfar på webbplatsen kan du lägga till produkter i en offertlista genom att helt enkelt klicka på "Lägg till offertlistan" på de enskilda produktsidorna. När alla relevanta produkter ingår, skicka listan till oss så får du en offert inom 24 timmar. Om du inte skickar listan kommer den att finnas tillgänglig på webbplatsen i 21 dagar. Vi hoppas att du finner funktionaliteten användbar.
Tack för att du begär en offert. Vi återkommer via telefon eller e-post inom 24 timmar.

Behövs hjälp?

Om du behöver support är du alltid välkommen att kontakta oss

Håll dig uppdaterad!

Registrera dig här för att få vårt nyhetsbrev