Ex repeater / power supply
5104B
- 1- or 2-channel version
- 3- / 5-port 3.75 kVAC galvanic isolation
- Loop supply > 17.1 V in hazardous area
- 20 programmable measurement ranges
- Universal supply by AC or DC
Application
- Supply voltage and safety barrier for 2-wire transmitters mounted in a hazardous area.
- Safety barrier for analog current / voltage signals from a hazardous area.
- 1 : 1 or signal conversion of analog current / voltage signals.
Technical characteristics
- The 20 factory-calibrated measurement ranges in the 5104B can be selected by the internal DIP-switches without the need for recalibration. Special measurement ranges can be delivered.
- PR5104B is based on microprocessor technology for gain and offset. The analog signal is transmitted at a response time of less than 25 ms.
- Inputs, outputs, and supply are floating and galvanically separated.
- The output can be connected either as an active current / voltage transmitter or as a 2-wire transmitter.
Mounting / installation
- Mounted vertically or horizontally on a DIN rail. By way of the 2-channel version up to 84 channels per meter can be mounted.
- NB: 5104B is recommended as I.S. barrier for 5331D, 5333D, 5334B, 5343B, 6331B, 6333B, and 6334B.
Data sheet & Manuals
Data sheet
- 5104B.pdf
- Latest version
Manuals
- 5104V104_UK.pdf
- 5104V103.pdf
- Previous versions
- Latest version
Manuals in Russian
- 5104V104_RU.pdf
- Latest version
Approvals & Certificates
Ex certificate
- 5104Q501.pdf
- 5104B.pdf
- Previous versions
- Latest version
UL certificate
- 5104B-07B_UL.pdf
- Latest version
DNV marine certificate
- DNV_2231_41xx_51xx_53xx.pdf
- Latest version
EAC declaration
- EAC-Declaration.pdf
- Latest version
EAC Ex certificate
- EAC_Ex.pdf
- Latest version
Metrology Pattern Approval (MPA), Russia
- MPA_Russia.pdf
- Latest version
Supplementary documentation
EU Declaration of Conformity
- 5104DoC_EU_102_UK.pdf
- 5104DoC_EU_101_UK.pdf
- 5104DoC_EU_100_UK.pdf
- Previous versions
- Latest version
Safety note
Safety note
- SN5000-1_103_1931.pdf
- SN5000-1_102_1613.pdf
- SN5000_101_1450.pdf
- Previous versions
- Latest version
Environmental Conditions
Operating temperature | -20°C to +60°C |
Calibration temperature | 20...28°C |
Relative humidity | < 95% RH (non-cond.) |
Protection degree | IP20 |
Mechanical specifications
Dimensions (HxWxD) | 109 x 23.5 x 130 mm |
DIN rail type | DIN 46277 |
Weight approx. | 225 g |
Wire size | 1 x 2.5 mm2 stranded wire |
Screw terminal torque | 0.5 Nm |
Vibration | IEC 60068-2-6 |
2...13.2 Hz | ±1 mm |
13.2...100 Hz | ±0.7 g |
Common specifications
Supply |
|
Supply voltage, universal | 21.6...253 VAC, 50...60 Hz or 19.2...300 VDC |
Fuse | 400 mA SB / 250 VAC |
Max. required power | ≤ 3 W (2 channels) |
Internal power dissipation | ≤ 2 W (2 channels) |
Isolation voltage |
|
Isolation voltage, test / working | 3.75 kVAC / 250 VAC |
PELV/SELV | IEC 61140 |
Auxiliary supplies |
|
2-wire supply (pin 44...42 and 54...52) | 28...17.1 VDC / 0...20 mA |
Response time |
|
Response time (0...90%, 100...10%) | < 25 ms |
Signal / noise ratio | Min. 60 dB (0...100 kHz) |
Accuracy | Better than 0.1% of sel. range |
EMC immunity influence | < ±0.5% of span |
Extended EMC immunity: NAMUR NE21, A criterion, burst | < ±1% of span |
Input specifications
Common input specifications |
|
Max. offset | 20% of max. value |
Current input |
|
Measurement range | 0...20 mA |
Min. measurement range (span) | 16 mA |
Input resistance | Nom. 10 Ω + PTC 10 Ω |
Voltage input |
|
Measurement range | 0...10 VDC |
Min. measurement range (span) | 8 VDC |
Input resistance | > 2 MΩ |
Output specifications
Current output |
|
Signal range | 0...20 mA |
Min. signal range | 16 mA |
Load (@ current output) | ≤ 600 Ω |
Load stability | ≤ 0.01% of span / 100 Ω |
Current limit | ≤ 28 mA |
Passive 2-wire mA output |
|
Effect of external 2-wire supply voltage variation | < 0.005% of span / V |
Voltage output |
|
Signal range | 0...1 VDC / 0...10 VDC |
Min. signal range | 0.8 VDC / 8 VDC |
Load (@ voltage output) | ≥ 500 kΩ |
External loop supply | 29 VDC |
of span | = of the presently selected range |
Observed authority requirements
EMC | 2014/30/EU |
LVD | 2014/35/EU |
EAC | TR-CU 020/2011 |
Approvals
ATEX | DEMKO 99ATEX126013, II (1) GD [EEx ia] IIC |
UL | UL 913, UL 508 |
EAC Ex | RU C-DK.GB08.V.00410 |
DNV Marine | Stand. f. Certific. No. 2.4 |