  • Universal driver for solenoids, acoustic alarms and LEDs
  • Extended self-diagnostics
  • 1 or 2 channels
  • Can be supplied separately or installed on power rail, PR 9400
  • SIL 2-certified via Full Assessment
  1. Overview + -

  2. Technical details + -

  3. Accessories + -


Advanced features

  • Universal driver for the control of solenoids etc.
  • Two hardware versions make it possible to choose either Low (35 mA) or High (60 mA) current output.
  • Configuration and monitoring by way of detachable display front (PR 4500).
  • Selection of direct or inverted function for each channel via PR 45xx and the possibility of reducing the output current to suit the application.
  • Optional monitoring of the output current by way of PR 4500.
  • Optional redundant supply via power rail and/or separate supply.

Application

  • The 9203A can be mounted in the safe area and in zone 2 / Class 1, Division 2, Group A, B, C, D.
  • Control of ON / OFF solenoids, acoustic alarms and LEDs.
  • The 9203A is controlled by an NPN/PNP signal or a switch signal.
  • Monitoring of internal error events via the individual status relay and/or a collective electronic signal via the power rail.
  • The 9203A has been designed, developed and certified for use in SIL 2 applications according to the requirements of IEC 61508.
  • Suitable for the use in systems up to Performance Level “d” according to ISO-13849.

Technical characteristics

  • 1 green and 2 yellow/red front LEDs indicate operation status and malfunction.
  • 2.6 kVAC galvanic isolation between input, output and supply.

Mounting

  • The devices can be mounted vertically or horizontally without distance between neighbouring units.

Supplementary documentation


Safety manual (SIL)

EU Declaration of Conformity

Modbus configuration manual

EMC data

Assessment report

FMEDA report

ISO 13849 declaration

SIL declaration

Approvals & Certificates


ATEX certificate

IECEx certificate

CCC certificate

FM certificate

UL certificate

DNV marine certificate

ClassNK cerfificate

SIL certificate

EAC declaration

EAC LVD declaration

EAC Ex certificate

Metrology Pattern Approval (MPA), Russia

Environmental Conditions

Operating temperature -20°C to +60°C
Storage temperature -20°C to +85°C
Calibration temperature 20...28°C
Relative humidity < 95% RH (non-cond.)
Protection degree IP20
Installation in Pollution degree 2 & meas. / overvoltage cat. II

Mechanical specifications

Dimensions (HxWxD) 109 x 23.5 x 104 mm
Dimensions (HxWxD) w/ 4501/451x 109 x 23.5 x 116 / 131 mm
Weight approx. 170 g
Weight incl. 4501 / 451x (approx.) 185 g / 200 g
DIN rail type DIN EN 60715/35 mm
Wire size 0.13...2.08 mm2 AWG 26...14 stranded wire
Screw terminal torque 0.5 Nm
Vibration IEC 60068-2-6
2...13.2 Hz ±1 mm
13.2...100 Hz ±0.7 g

Common specifications

Supply

Supply voltage 19.2...31.2 VDC
Fuse 1.25 A SB / 250 VAC
Max. required power ≤ 1.9 W / ≤ 3.1 W (1 / 2 ch.) - low current ≤ 2.5 W (1 ch.) - high current
Max. power dissipation, 1 / 2 ch. ≤ 1.1 W / ≤ 2.0 W (1 / 2 ch.) - low current
Max. power dissipation ≤ 1.7 W (1 ch.) - high current

Isolation voltage

Test /working: Input to any 2.6 kVAC / 300 VAC reinforced isolation
Output 1 to output 2 1.5 kVAC / 150 VAC reinforced isolation
Status relay to supply 1.5 kVAC / 150 VAC reinforced isolation
Programming PR 4500 communication interfaces
EMC immunity influence < ±0.5% of span
Extended EMC immunity: NAMUR NE21, A criterion, burst < ±1% of span

Input specifications

NPN and mechanical switch

Trig level LOW ≤ 2.0 VDC
Trig level HIGH ≥ 4.0 VDC
Max. external voltage 28 VDC
Input impedance 3.5 kΩ

PNP

Trig level LOW ≤ 8.0 VDC
Trig level HIGH ≥ 10.0 VDC
Max. external voltage 28 VDC
Input impedance 3.5 kΩ

Output specifications

Status relay

Max. voltage 125 VAC / 110 VDC
Max. current 0.5 AAC / 0.3 ADC
Max. AC power 62.5 VA / 32 W
Output ripple < 40 mVRMS

Observed authority requirements

EMC 2014/30/EU
LVD 2014/35/EU
ATEX 2014/34/EU
RoHS 2011/65/EU
EAC TR-CU 020/2011
EAC Ex TR-CU 012/2011
EAC LVD TR-CU 004/2011

Approvals

ATEX KEMA 07ATEX0147 X
IECEx KEM 09.0001X
c FM us FM19US0057X / FM19CA0030X
c UL us, UL 61010-1 E314307
CCC 2020322304003423
c UL us, UL 913 E233311 (only 9203xxxx-U9)
DNV Marine TAA00000JD
ClassNK TA18527M
EAC Ex RU C-DK.HA65.B.00355/19
SIL SIL 2 certified & fully assessed acc. to IEC 61508
 

Is this information helpful?

 

Rate us

Your request has been sent successfully. 0 items on your list
Your contact information
Please insert your last name
Please insert your last name
Please insert a valid email address
Please insert a valid phone number. Use only numbers.
Please insert your job title
Please insert your company name.
Please insert your company address
Please insert a valid zip code
Please insert a city
Please select country
Please read and agree with PR electronics’ Privacy Policy.
You have not added any products to your quote list
When browsing the website, you can add products to a quote list by simply clicking “Add to quote list" on the individual product pages. Once all relevant products are included, send the list to us and you will get a quotation within 24 hours. If you don't submit the list, it will be accessible on the website for 21 days. We hope you will find the functionality useful.
Thank you for requesting a quotation. We will get back to you by phone or email within 24 hours.

Need help?

If you need support, you are always welcome to contact us

Stay updated!

Register here to receive our newsletter