2-wire programmable transmitter
6333B
- RTD or Ohm input
- High measurement accuracy
- 3-wire connection
- Can be installed in Ex zone 0
- 1- or 2-channel version
Application
- Linearized temperature measurement with Pt100...Pt1000 or Ni100...Ni1000 sensor.
- Conversion of linear resistance variation to a standard analog current signal, for instance from valves or Ohmic level sensors.
Technical characteristics
- Within a few seconds the user can program PR6333B to measure temperatures within all RTD ranges defined by the norms.
- The RTD and resistance inputs have cable compensation for 3-wire connection.
- A limit can be programmed on the output signal.
Mounting / installation
- Mounted vertically or horizontally on a DIN rail. Using the 2-channel version, up to 84 channels can be mounted per meter.
- The 6333B can be mounted in zone 0, 1, 2 and zone 20, 21, 22 including M1 / Class I, Division 1, Groups A, B, C, D.
Data sheet & Manuals
Data sheet
- 6333B.pdf
- Latest version
Manuals
- 6333V105_UK.pdf
- 6333V104_UK.pdf
- 6333V103_UK.pdf
- 6333V102.pdf
- Previous versions
- Latest version
Manuals in Russian
- 6333V105_RU.pdf
- 6333V104_RU.pdf
- 6333V103_RU.pdf
- Previous versions
- Latest version
Approvals & Certificates
ATEX certificate
- 6333B_issue04.pdf
- 6333B_issue03.pdf
- 6333B_issue02.pdf
- 6333B_issue01.pdf
- Previous versions
- Latest version
IECEx certificate
- 6333BIEC_issue02.pdf
- 6333BIEC_issue01.pdf
- 6333BIEC_issue0.pdf
- Previous versions
- Latest version
CSA certificate
- 533x_633x_CSA.pdf
- Latest version
FM certificate
- 53xx_633x_FM17US0013X.pdf
- 53xx_633x_FM_2D5A7.pdf
- Previous versions
- Latest version
EAC declaration
- EAC-Declaration.pdf
- Latest version
EAC Ex certificate
- EAC_Ex.pdf
- Latest version
Metrology Pattern Approval (MPA), Belarus
- MPA_Belarus.pdf
- Latest version
Metrology Pattern Approval (MPA), Kazakhstan
- MPA_Kazakhstan.pdf
- Latest version
Metrology Pattern Approval (MPA), Russia
- MPA_Russia.pdf
- Latest version
Supplementary documentation
EU Declaration of Conformity
- 6333DoC_EU_102_UK.pdf
- 6333DoC_EU_101_UK.pdf
- 6333DoC_EU_100_UK.pdf
- Previous versions
- Latest version
CCC statement
- 5000_6000_series_CCC_statement.pdf
- Latest version
Safety note
Safety note
- SN6333_106_2026.pdf
- SN6333_105_1749.pdf
- SN6333_104_1650.pdf
- SN6333_103_1614.pdf
- SN6300_102_1506.pdf
- Previous versions
- Latest version
Environmental Conditions
Operating temperature | -40°C to +85°C |
Storage temperature | -40°C to +85°C |
Calibration temperature | 20...28°C |
Relative humidity | < 95% RH (non-cond.) |
Protection degree | IP20 |
Mechanical specifications
Dimensions (HxWxD) | 109 x 23.5 x 104 mm |
Weight (1 / 2 channels) | 145 / 185 g |
DIN rail type | DIN EN 60715/35 mm |
Wire size | 0.13...2.08 mm2 AWG 26...14 stranded wire |
Screw terminal torque | 0.5 Nm |
Common specifications
Supply |
|
Supply voltage | 8.0...30 VDC |
Max. required power | ≤ 0.8 W/≤ 1.6 W (1 ch./2 ch.) |
Internal power dissipation | 0.19...0.8 W |
Response time |
|
Response time (programmable) | 0.33...60 s |
Voltage drop | 8.0 VDC |
Warm-up time | 5 min. |
Programming | Loop Link |
Signal / noise ratio | Min. 60 dB |
Accuracy | Better than 0.1% of sel. range |
Signal dynamics, input | 19 bit |
Signal dynamics, output | 16 bit |
Effect of supply voltage change | < 0.005% of span / VDC |
Input specifications
Common input specifications |
|
Max. offset | 50% of selected max. value |
RTD input |
|
RTD type | Pt100, Ni100, lin. R |
Cable resistance per wire | 10 Ω (max.) |
Sensor current | > 0.2 mA, < 0.4 mA |
Effect of sensor cable resistance (3-wire) | < 0.002 Ω / Ω |
Sensor error detection | Yes |
Linear resistance input |
|
Linear resistance min....max. | 0 Ω...10000 Ω |
Output specifications
Current output |
|
Signal range | 4…20 mA |
Min. signal range | 16 mA |
Load (@ current output) | ≤ (Vsupply - 8) / 0.023 [Ω] |
Load stability | ≤ 0.01% of span / 100 Ω |
Sensor error indication | Programmable 3.5…23 mA |
NAMUR NE43 Upscale/Downscale | 23 mA / 3.5 mA |
Common output specifications |
|
Updating time | 135 ms |
of span | = of the presently selected range |
Observed authority requirements
EMC | 2014/30/EU |
ATEX | 2014/34/EU |
RoHS | 2011/65/EU |
EAC | TR-CU 020/2011 |
EAC Ex | TR-CU 012/2011 |
Approvals
ATEX | KEMA 09ATEX0147 X |
IECEx | DEK 14.0049 X |
CSA | 1125003 |
c FM us | FM17US0013X |
EAC Ex | RU C-DK.HA65.B.00355/19 |

7423
Ceramic socket for Pt100 sensor
7430B
Pt100 cable sensor
7430C
Pt100 cable sensor
7440
Thermowell for PR 7400 Pt100 sensor
5909
Loop Link communications interface
7007
2-digit digital potentiometer
7008
3-digit digital potentiometer
7009
10-turn potentiometer, 200 Ω
7011
Dial for 10-turn potentiometer
7012
1-turn potentiometer, 1 kΩ
7015
1-turn potentiometer, 10 kΩ
7020
Knob for 1-turn potentiometer
7020A
Knob for 10-turn potentiometer