5531B
 

Loop-powered LCD indicator

 

5531B

 

  • 4 digit 1/8 DIN (48 x 96 mm) loop-powered LCD display
  • Easy push-button configuration
  • Backlit LCD display is readable in low light conditions
  • Display can be mounted in the safe area or in I.S. / Ex zone
  1. Overview + -

  2. Technical details + -

  3. Accessories + -


Application

  • The 5531 indicator is powered by the 4 to 20 mA current loop and is easily scaled to display the correct process value.
  • Because it does not require separate power wiring, the 5531 is perfect for remote display of process loops.
  • The 5531B can be mounted in Ex Zone 1.
  • The 5531B1 Ex display includes the 8501 enclosure and can be mounted in Ex Zone 2 or 22 (gas or dust).
  • The 5531B2 includes the 8501 enclosure and can be mounted in Ex Zone 1, 2, 21 or 22 (gas or dust).

Technical characteristics

  • With a full measurement range of 3.6 to 23 mA, the 5531 is NAMUR NE43 compliant.
  • The display can be push-button scaled to any range between -9999 to 9999, and reverse display action is possible.
  • The LCD backlight can be set to half or full intensity for easy viewing in low light conditions.
  • The display only requires 1.5 VDC, (75 Ω loop load), with the backlight turned off.
  • The input is HART transparent.
  • The front push-buttons can be disabled to prevent unauthorized adjustment.

Mounting / installation

  • Once panel mounted with the included gasket, the 5531 provides IP65 ingress protection.

Data sheet & Manuals


Data sheet

Manuals

Manuals in Russian

Approvals & Certificates


ATEX certificate

EAC declaration

EAC Ex certificate

Metrology Pattern Approval (MPA)

Supplementary documentation


Declaration of Conformity

Safety note


Safety note

Environmental Conditions

Operating temperature -20°C to +60°C
Storage temperature -20°C to +60°C
Calibration temperature 20...28°C
Relative humidity < 95% RH (non-cond.)
Protection degree IP65, from front

Mechanical specifications

Dimensions (HxWxD) 48 x 96 x 120 mm
Cut out dimensions 44.5 x 91.5 mm
Weight approx. 200 g
Cable glands and cable diameter M16 x 1.5 / Ø 5...8 mm
Wire size, connector terminal 1 - 4 0.13...2.08 mm2 / AWG 26...14 stranded wire

Common specifications

Supply

Supply voltage Input loop-powered

Response time

Response time (0...90%, 100...10%) < 1 s
EMC immunity influence < ±0.5% of span
Signal / noise ratio > 60 dB
Updating time 500 ms

Input specifications

Current input

Measurement range 3.6...23 mA
Loop error detection, 4...20 mA: Low ~ < 3 mA
Loop error detection, 4...20 mA: High ~ > 24 mA
Input voltage drop, without backlight < 1.5 V @ 20 mA
Input voltage drop, with half backlight < 6.5 V @ 20 mA
Input voltage drop, with full backlight < 10.5 V @ 20 mA

Output specifications

Display

Display readout ± 9999 (4 digits)
Digit height 16 mm

Observed authority requirements

EMC 2014/30/EU
RoHS 2011/65/EU
EAC TR-CU 020/2011

Approvals

ATEX KEMA 05ATEX1044 X (5531A/B1) KEMA 05ATEX1105 X (5531B/B2)
EAC Ex RU C-DK.HA65.B.00355/19
 

Is this information helpful?

 

Rate us

Your request has been sent successfully. 0 items on your list
Your contact information
Please insert your last name
Please insert your last name
Please insert a valid email address
Please insert a valid phone number. Use only numbers.
Please insert your job title
Please insert your company name.
Please insert your company address
Please insert a valid zip code
Please insert a city
Please select country
Please read and agree with PR electronics’ Privacy Policy.
You have not added any products to your quote list
When browsing the website, you can add products to a quote list by simply clicking “Add to quote list" on the individual product pages. Once all relevant products are included, send the list to us and you will get a quotation within 24 hours. If you don't submit the list, it will be accessible on the website for 21 days. We hope you will find the functionality useful.
Thank you for requesting a quotation. We will get back to you by phone or email within 24 hours.

Need help?

If you need support, you are always welcome to contact us

Stay updated!

Register here to receive our newsletter