Universal trip amplifier
4131
- Input for RTD, TC, Ohm, potentiometer, mA and V
- 2 adjustable alarm limits
- FM-approved for installation in Div. 2
- 2 relay outputs
- Universal AC or DC supply
Advanced features
- Programmable via detachable display front (PR 4500 series), process calibration, relay simulation, password protection, error diagnostics and selection of help text in several languages.
Application
- Process control with 2 pairs of potential-free relay contacts which can be configured to suit any application.
- Trip amplifier with window function defined by a high and a low setpoint. The relay changes state outside the window.
- Relay latch function, where the relay is activated and can only be reset manually.
- Sophisticated sensor error surveillance, where one relay holds the state immediately prior to the sensor error, while allowing the process to continue. The other relay can be set for sensor error alarm so that the defect sensor can be replaced immediately.
Technical characteristics
- When 4131 is used with the PR 4500 display series, all operational parameters can be modified to suit any application. As the 4131 is designed with electronic hardware switches, it is not necessary to open the device for setting of DIP-switches.
- A green front LED indicates normal operation and malfunction. A yellow LED is ON for each active output relay.
- Continuous check of vital stored data for safety reasons.
- 3-port 2.3 kVAC galvanic isolation.
Data sheet & Manuals
Data sheet
- 4131.pdf
- Latest version
Manuals
- 4131V106_UK.pdf
- 4131V105_UK.pdf
- 4131V104_UK.pdf
- 4131V103_UK.pdf
- 4131V102_UK.pdf
- 4131V101_UK.pdf
- 4131V100_UK.pdf
- Previous versions
- Latest version
Manuals in Russian
- 4131V106_RU.pdf
- 4131V105_RU.pdf
- 4131V104_RU.pdf
- 4131V103_RU.pdf
- 4131L102_RU.pdf
- Previous versions
- Latest version
Supplementary documentation
EU Declaration of Conformity
- 4131DoC_EU_103_UK.pdf
- 4131DoC_EU_102_UK.pdf
- 4131DoC_EU_101_UK.pdf
- 4131DoC_EU_100_UK.pdf
- Previous versions
- Latest version
UKCA Declaration of Conformity
- 4131DoC_UKCA_100_UK.pdf
- 4131DoC_UKCA_100.pdf
- Previous versions
- Latest version
Modbus configuration manual
- 4131_MCM_103.pdf
- 4131_MCM_102.pdf
- 4131_MCM_101.pdf
- 4131_MCM_100.pdf
- Previous versions
- Latest version
EMC data
- 4000_EMC_data.pdf
- Latest version
Safety note
Safety note
- SN4000_1_107_2150.pdf
- SN4000_1_106_2109.pdf
- SN4000_105_2001.pdf
- SN4000_104_1741.pdf
- SN4000_103_1613.pdf
- SN4000_102_1506.pdf
- Previous versions
- Latest version
Approvals & Certificates
FM certificate
- 4104_14_16_31_4222_FM.pdf
- Latest version
UL certificate
- 4114_4116_4131_4222_UL.pdf
- Latest version
DNV marine certificate
- DNV_2231_41xx_51xx_53xx.pdf
- Latest version
DNV EU-RO marine certificate
- DNV_GL_EU_RO_4114_4116_4131_5714_5725.pdf
- Latest version
EAC declaration
- EAC-Declaration.pdf
- Latest version
EAC LVD declaration
- EAC_LVD-Declaration.pdf
- Latest version
Metrology Pattern Approval (MPA), Russia
- MPA_Russia.pdf
- Latest version
Environmental Conditions
Operating temperature | -20°C to +60°C |
Calibration temperature | 20...28°C |
Relative humidity | < 95% RH (non-cond.) |
Protection degree | IP20 |
Mechanical specifications
Dimensions (HxWxD) | 109 x 23.5 x 104 mm |
Dimensions (HxWxD) w/ 4501/451x | 109 x 23.5 x 116 / 131 mm |
Weight approx. | 170 g |
Weight incl. 4501 / 451x (approx.) | 185 g / 200 g |
Wire size | 0.13...2.08 mm2 AWG 26...14 stranded wire |
Screw terminal torque | 0.5 Nm |
Vibration | IEC 60068-2-6 |
2...13.2 Hz | ±1 mm |
13.2...100 Hz | ±0.7 g |
Common specifications
Supply |
|
Supply voltage, universal | 21.6...253 VAC, 50...60 Hz or 19.2...300 VDC |
Fuse | 400 mA SB / 250 VAC |
Max. required power | ≤ 2.0 W |
Max. power dissipation | ≤ 2.0 W |
Isolation voltage |
|
Isolation voltage, test / working | 2.3 kVAC / 250 VAC |
Response time |
|
Temperature input (0...90%, 100...10%) | ≤ 1 s |
mA / V input (0...90%, 100...10%) | ≤ 400 ms |
Auxiliary supplies |
|
2-w. supply (term. 44...43) | 25...16 VDC / 0...20 mA |
Programming | PR 4500 communication interfaces |
Signal / noise ratio | Min. 60 dB (0...100 kHz) |
Accuracy | Better than 0.1% of sel. range |
EMC immunity influence | < ±0.5% of span |
Extended EMC immunity: NAMUR NE21, A criterion, burst | < ±1% of span |
Input specifications
RTD input |
|
RTD type | Pt10/20/50/100/200/250; Pt300/400/500/1000; Ni50/100/120/1000; Cu10/20/50/100 |
Cable resistance per wire | 50 Ω (max.) |
Sensor current | Nom. 0.2 mA |
Effect of sensor cable resistance (3-/4-wire) | < 0.002 Ω / Ω |
Sensor error detection | Yes |
Short circuit detection | < 15 Ω |
Linear resistance input |
|
Linear resistance min....max. | 0 Ω...10000 Ω |
Potentiometer input |
|
Potentiometer min....max. | 10 Ω...100 kΩ |
TC input |
|
Thermocouple type | B, E, J, K, L, N, R, S, T, U, W3, W5, LR |
Cold junction compensation (CJC) via ext. sensor in 5910 | 20...28°C ≤ ±1°C, -20...20°C / 28...70°C ≤ 2°C |
CJC via int. mounted sensor | ±(2.0°C + 0.4°C * Δt) |
Sensor error detection | Yes |
Sensor error current: When detecting / else | Nom. 2 μA / 0 μA |
Current input |
|
Measurement range | 0...23 mA |
Programmable measurement ranges | 0...20 and 4...20 mA |
Input resistance | Nom. 20 Ω + PTC 50 Ω |
Voltage input |
|
Measurement range | 0...12 VDC |
Programmable measurement ranges | 0/0.2...1, 0/1...5, 0/2...10 VDC |
Input resistance | Nom. 10 MΩ |
Output specifications
Relay output |
|
Relay functions | Setpoint, Window, Sensor error, Latch, Power and Off |
Hysteresis | 0...100% |
ON and OFF delay | 0...3600 s |
Max. voltage | 250 VRMS |
Max. current | 2 AAC or 1 ADC |
Max. AC power | 500 VA |
Sensor error reaction | Break / Make / Hold |
of span | = of the presently selected range |
Observed authority requirements
EMC | 2014/30/EU & UK SI 2016/1091 |
LVD | 2014/35/EU & UK SI 2016/1101 |
RoHS | 2011/65/EU & UK SI 2012/3032 |
EAC | TR-CU 020/2011 |
EAC LVD | TR-CU 004/2011 |
Approvals
c UL us, UL 508 | E231911 |
FM | 3025177 |
DNV Marine | TAA0000101 |
EU RO MR Type Approval | MRA000000Z |

7423
Ceramic socket for Pt100 sensor
7430B
Pt100 cable sensor
7430C
Pt100 cable sensor
7440
Thermowell for PR 7400 Pt100 sensor
4510
Display / programming front
4511
Communication enabler
4512
Bluetooth communication enabler
4590
ConfigMate
5910
CJC connector
7007
2-digit digital potentiometer
7008
3-digit digital potentiometer
7009
10-turn potentiometer, 200 Ω
7010
10-turn potentiometer, 20 kΩ
7011
Dial for 10-turn potentiometer
7012
1-turn potentiometer, 1 kΩ
7015
1-turn potentiometer, 10 kΩ
7016
1-turn potentiometer, 100 kΩ
7020
Knob for 1-turn potentiometer
7020A
Knob for 10-turn potentiometer
7028
10-turn potentiometer, 2 kΩ
8510
8 unit 4511 Modbus cable
8511
4511 Y-splitter Modbus cable
8513
RJ45 Modbus termination
8514
3 X RJ45 female Y-splitter
8515
RJ45 female to female cable adapter
8516
RJ45 female to female shielded cable adabter