3104
 

Isolated converter

 

3104

 

  • Isolation and conversion of standard DC signals
  • Slimline housing of 6 mm
  • Power supply and signal isolator for 2-wire transmitter
  • Loop supply >17 V
  • DIP-switch configured
  1. Overview + -

  2. Technical details + -

  3. Accessories + -


Application

  • Isolation and conversion of standard DC signals.
  • Galvanic separation of analog current and voltage signals.
  • Elimination of ground loops and measurement of floating signals.
  • A competitive choice in terms of both price and technology for galvanic isolation of current and voltage signals to SCADA systems or PLC equipment.
  • Installation in ATEX Ex zone 2 / IECEx zone 2 / FM division 2.
  • Suitable for environments with high vibration stress, e.g. ships.

Technical characteristics

  • Easy configuration via DIP-switches.
  • The input is protected against overvoltage and polarity error.
  • Factory-calibrated measurement ranges.
  • Inputs and outputs are floating and galvanically separated.

Data sheet & Manuals


Data sheet

Manuals

Manuals in Russian

Approvals & Certificates


ATEX certificate

IECEx certificate

CCC certificate

FM certificate

UL certificate

DNV marine certificate

EAC declaration

EAC Ex certificate

Metrology Pattern Approval (MPA), Russia

Supplementary documentation


EU Declaration of Conformity

EMC data


EMC data

Environmental Conditions

Operating temperature -25°C to +70°C
Storage temperature -40°C to +85°C
Calibration temperature 20...28°C
Relative humidity < 95% RH (non-cond.)
Protection degree IP20
Installation in Pollution degree 2 & meas. / overvoltage cat. II

Mechanical specifications

Dimensions (HxWxD) 113 x 6.1 x 115 mm
Weight approx. 70 g
DIN rail type DIN EN 60715/35 mm
Wire size 0.13...2.5 mm2 / AWG 26...12 stranded wire
Screw terminal torque 0.5 Nm
Vibration IEC 60068-2-6
2...25 Hz ±1.6 mm
25...100 Hz ±4 g

Common specifications

Supply

Supply voltage 16.8...31.2 VDC
Max. required power ≤ 1.2 W
Max. power dissipation 0.55 W

Isolation voltage

Isolation voltage, test / working 2.5 kVAC / 300 VAC (reinforced)
Zone 2 / Div. 2 250 VAC

Response time

Response time (0...90%, 100...10%) < 7 ms
Programming DIP-switches
Signal / noise ratio > 60 dB
Cut-off frequency (3 dB) > 100 Hz
Signal dynamics, input Analog signal chain
Signal dynamics, output Analog signal chain
Accuracy Better than 0.05% of selected range
Temperature coefficient < ±0.01% of span / °C
EMC immunity influence < ±0.5% of span
Extended EMC immunity: NAMUR NE21, A criterion, burst < ±1% of span

Input specifications

Current input

Measurement range 0...23 mA
Programmable measurement ranges 0...20 and 4...20 mA
Input voltage drop < 1.5 VDC

Voltage input

Measurement range 0...10.25 V 0...11.5 V / 0...5.75 V
Programmable measurement ranges 0/1...5 and 0/2...10 V
Input resistance ≥ 500 kΩ
2-wire transmitter supply > 17 V / 20 mA

Output specifications

Current output

Signal range 0...23 mA
Programmable signal ranges 0 / 4...20 mA
Load (@ current output) ≤ 600 Ω
Load stability ≤ 0.002% of span / 100 Ω
Current limit ≤ 28 mA

Voltage output

Signal range 0...10 VDC
Programmable signal ranges 0/1...5 and 0/2...10 V
Load (@ voltage output) ≥ 10 kΩ
of span = of the DIP-switch selected output range

I.S. / Ex marking

ATEX II 3 G Ex ec IIC T4 Gc
IECEx Ex ec IIC T4 Gc
FM, US Cl. I, Div. 2, Gp. A, B, C, D T4 or Cl. I, Zone 2, AEx nA IIC T4
FM, CA Cl. I, Div. 2, Gp. A, B, C, D T4 or Cl. I, Zone 2, Ex nA IIC T4
EAC Ex 2Ex nA IIC T4 Gc X

Observed authority requirements

EMC 2014/30/EU
LVD 2014/35/EU
ATEX 2014/34/EU
RoHS 2011/65/EU
EAC TR-CU 020/2011
EAC Ex TR-CU 012/2011

Approvals

ATEX KEMA 10ATEX0147 X
IECEx KEM 10.0068X
c FM us FM17US0004X / FM17CA0003X
c UL us, UL 61010-1 E314307
CCC 2020322310003554
EAC Ex RU C-DK.HA65.B.00355/19
DNV Marine TAA00001RW
 

Is this information helpful?

 

Rate us

Your request has been sent successfully. 0 items on your list
Your contact information
Please insert your last name
Please insert your last name
Please insert a valid email address
Please insert a valid phone number. Use only numbers.
Please insert your job title
Please insert your company name.
Please insert your company address
Please insert a valid zip code
Please insert a city
Please select country
Please read and agree with PR electronics’ Privacy Policy.
You have not added any products to your quote list
When browsing the website, you can add products to a quote list by simply clicking “Add to quote list" on the individual product pages. Once all relevant products are included, send the list to us and you will get a quotation within 24 hours. If you don't submit the list, it will be accessible on the website for 21 days. We hope you will find the functionality useful.
Thank you for requesting a quotation. We will get back to you by phone or email within 24 hours.

Need help?

If you need support, you are always welcome to contact us

Stay updated!

Register here to receive our newsletter