Universal converter
9116A
- Input for RTD, TC, Ohm, potentiometer, mA and V
- Supply for 2-wire transmitters
- Active / passive mA output and relay output
- Can be supplied separately or installed on power rail, PR type 9400
- SIL 2-certified via Full Assessment
Advanced features
- Configuration and monitoring by way of detachable display front (PR 45xx); process calibration, signal and relay simulation.
- Advanced relay configuration, e.g. setpoint, window, delay, sensor error indication and power monitoring.
- Copying of the configuration from one device to others of the same type via the display front.
- TC inputs with internal CJC or external CJC for higher accuracy.
- Active / passive mA output via the same two terminals.
Application
- 9116A can be mounted in the safe area or in zone 2 / Class I, Division 2, Groups A, B, C, D.
- Conversion and scaling of temperature, voltage, potentiometer and linear resistance signals.
- Power supply and signal isolator for 2-wire transmitters.
- Monitoring of error events and cable breakage via the individual status relay and/or a collective electronic signal via the power rail.
- 9116A has been designed, developed and certified for use in SIL 2 applications according to the requirements of IEC 61508.
- Suitable for the use in systems up to Performance Level “d” according to ISO-13849.
Technical characteristics
- 1 green and 1 red front LED indicate operation status and malfunction. 1 yellow LED indicates relay status.
- 2.6 kVAC galvanic isolation between input, output and supply.
Mounting
- The devices can be mounted vertically or horizontally without distance between neighbouring units.
Data sheet & Manuals
Data sheet
- 9116A.pdf
- Latest version
Manuals
- 9116V003_109_UK.pdf
- 9116V003_108_UK.pdf
- 9116BV003_107_UK.pdf
- 9116BV003_106_UK.pdf
- 9116BV003_105_UK.pdf
- 9116BV003_104_UK.pdf
- 9116BV003_103_UK.pdf
- 9116BV002_102_UK.pdf
- 9116BV001_101_UK.pdf
- 9116BV001_100_UK.pdf
- 9116AV003_102_UK.pdf
- 9116AV003_101_UK.pdf
- 9116AV003_100_UK.pdf
- Previous versions
- Latest version
Manuals in Russian
- 9116V003_109_RU.pdf
- 9116V003_108_RU.pdf
- 9116L001_101_RU.pdf
- 9116BV003_107_RU.pdf
- 9116BV003_106_RU.pdf
- 9116BV003_105_RU.pdf
- 9116BV003_104_RU.pdf
- 9116BV003_103_RU.pdf
- 9116BV002_102_RU.pdf
- 9116BV001_101_RU.pdf
- Previous versions
- Latest version
Manuals in Portuguese (Brazil)
- 9116V003_109_BR.pdf
- 9116V003_108_BR.pdf
- 9116BV003_107_BR.pdf
- 9116BV003_106_BR.pdf
- 9116BV003_105_BR.pdf
- 9116BV003_104_BR.pdf
- Previous versions
- Latest version
Safety manual (SIL)
- 9116_Safety_manualV5R0.pdf
- Latest version
Approvals & Certificates
ATEX certificate
- 9116A_issue4.pdf
- 9116A_issue3.pdf
- 9116A_issue2.pdf
- 9116A_issue1.pdf
- Previous versions
- Latest version
IECEx certificate
- 9116AIEC_issue4.pdf
- 9116AIEC_issue3.pdf
- 9116AIEC_issue2.pdf
- Previous versions
- Latest version
FM certificate
- 9116_FM19US0058X_FM19CA0031X.pdf
- Latest version
SIL certificate
- 9116_001_SIL.pdf
- Latest version
UL certificate
- 9116xxU9_UL913.pdf
- 9116xxx_UL61010.pdf
- Previous versions
- Latest version
DNV marine certificate
- DNV_9xxx_4511.pdf
- Latest version
ClassNK certificate
- ClassNK-TA18527M_91xx_92xx_94xx.pdf
- Latest version
EAC declaration
- EAC-Declaration.pdf
- Latest version
EAC LVD declaration
- EAC_LVD-Declaration.pdf
- Latest version
EAC Ex certificate
- EAC_Ex.pdf
- Latest version
Metrology Pattern Approval (MPA), Russia
- MPA_Russia.pdf
- Latest version
Supplementary documentation
EU Declaration of Conformity
- 9116DoC_EU_103_UK.pdf
- 9116DoC_EU_102_UK.pdf
- 9116DoC_EU_102_UK.pdf
- 9116DoC_EU_101_UK.pdf
- 9116DoC_EU_100_UK.pdf
- Previous versions
- Latest version
Modbus configuration manual
- 9116_MCM_101.pdf
- 9116_MCM_100.pdf
- Previous versions
- Latest version
EMC data
- 9000_EMC_data.pdf
- Latest version
CCC statement
- 9116_CCC_statement.pdf
- Latest version
Assessment report
- AssessmentReport_9116_V1R0.pdf
- Latest version
FMEDA report
- FMEDA_PR_9116_V2R1.pdf
- Latest version
ISO 13849 declaration
- 9116_ISO_13849_declaration.pdf
- Latest version
Safety note
Safety note
- SN9116_109_2007.pdf
- SN9116_108_1902.pdf
- SN9116_107_1811.pdf
- SN9116_106_1613.pdf
- SN9000_105_1503.pdf
- Previous versions
- Latest version
SIL declaration
Environmental Conditions
Operating temperature | -20°C to +60°C |
Storage temperature | -20°C to +85°C |
Calibration temperature | 20...28°C |
Relative humidity | < 95% RH (non-cond.) |
Protection degree | IP20 |
Installation in | Pollution degree 2 & meas. / overvoltage cat. II |
Mechanical specifications
Dimensions (HxWxD) | 109 x 23.5 x 104 mm |
Dimensions (HxWxD) w/ 4501/451x | 109 x 23.5 x 116 / 131 mm |
Weight approx. | 185 g |
Weight incl. 4501 / 451x (approx.) | 200 g / 215 g |
DIN rail type | DIN EN 60715/35 mm |
Wire size | 0.13...2.08 mm2 AWG 26...14 stranded wire |
Screw terminal torque | 0.5 Nm |
Vibration | IEC 60068-2-6 |
2...13.2 Hz | ±1 mm |
13.2...100 Hz | ±0.7 g |
Common specifications
Supply |
|
Supply voltage | 19.2...31.2 VDC |
Fuse | 1.25 A SB / 250 VAC |
Max. required power | ≤ 2.1 W |
Max. power dissipation | ≤ 1.7 W |
Isolation voltage |
|
Test /working: Input to any | 2.6 kVAC / 300 VAC reinforced isolation |
Analog output to supply | 2.6 kVAC / 300 VAC reinforced isolation |
Status relay to supply | 1.5 kVAC / 150 VAC reinforced isolation |
Response time |
|
Temperature input, programmable (0...90%, 100...10%) | 1...60 s |
mA / V input (programmable) | 0.4...60 s |
Auxiliary supplies |
|
9116x1x: 2-w. sup. (term. 54...52) | 28...16.5 VDC / 0...20 mA |
9116x2x: 2-w. sup. (term. 54...52) | 21.4...16.5 VDC / 0...20 mA |
Programming | PR 4500 communication interfaces |
Signal dynamics, input | 24 bit |
Signal dynamics, output | 16 bit |
Signal / noise ratio | Min. 60 dB (0...100 kHz) |
Accuracy | Better than 0.1% of sel. range |
Input specifications
RTD input |
|
RTD type | Pt10/20/50/100/200/250/300/Pt400/500/1000; Ni50/100/120/1000 |
Cable resistance per wire | 50 Ω (max.) |
Sensor current | Nom. 0.2 mA |
Effect of sensor cable resistance (3-/4-wire) | < 0.002 Ω / Ω |
Sensor error detection | Programmable ON / OFF |
Short circuit detection | Yes |
TC input |
|
Thermocouple type | B, E, J, K, L, N, R, S, T, U, W3, W5, LR |
Cold junction compensation (CJC) via ext. sensor in 5910 | 20...28°C ≤ ±1°C, -20...20°C / 28...70°C ≤ 2°C |
CJC via int. mounted sensor | ±(2.0°C + 0.4°C * Δt) |
Sensor error detection | Programmable ON or OFF (only wire breakage) |
Current input |
|
Measurement range | 0...23 mA |
Programmable measurement ranges | 0...20 and 4...20 mA |
Input resistance | Nom. 20 Ω + PTC 50 Ω |
Sensor error detection | Loop break 4...20 mA |
Voltage input |
|
Measurement range | 0...12 VDC |
Programmable measurement ranges | 0/0.2...1, 0/1...5, 0/2...10 VDC |
Input resistance | Nom. >10 MΩ |
Output specifications
Current output |
|
Signal range | 0...23 mA |
Programmable signal ranges | 0...20/4...20/20...0/20...4 mA |
Load (@ current output) | ≤ 600 Ω |
Load stability | ≤ 0.01% of span / 100 Ω |
Sensor error indication | 0 / 3.5 / 23 mA / none |
NAMUR NE43 Upscale/Downscale | 23 mA / 3.5 mA |
Current limit | ≤ 28 mA |
Passive 2-wire mA output |
|
Max. external 2-wire supply | 26 VDC |
Effect of external 2-wire supply voltage variation | < 0.005% of span / V |
Relay output |
|
Relay functions | Setpoint, Window, Sensor error, Power and Off |
Max. voltage | 250 VAC / VDC |
Max. current | 2 A |
Max. AC power | 500 VA |
Max. DC current, resistive load > 30 VDC | See manual for details |
Status relay |
|
Max. voltage | 125 VAC / 110 VDC |
Max. current | 0.5 AAC / 0.3 ADC |
Max. AC power | 62.5 VA / 32 W |
Observed authority requirements
EMC | 2014/30/EU |
LVD | 2014/35/EU |
ATEX | 2014/34/EU |
RoHS | 2011/65/EU |
EAC | TR-CU 020/2011 |
EAC Ex | TR-CU 012/2011 |
EAC LVD | TR-CU 004/2011 |
Approvals
ATEX | KEMA 10ATEX0053 X |
IECEx | KEM 10.0022X |
c FM us | FM19US0058X / FM19CA0031X |
c UL us, UL 61010-1 | E314307 |
c UL us, UL 913 | E233311 (only 9116xx-U9) |
EAC Ex | RU C-DK.HA65.B.00355/19 |
DNV Marine | TAA00000JD |
ClassNK | TA18527M |
SIL | SIL 2 certified & fully assessed acc. to IEC 61508 |

7423
Ceramic socket for Pt100 sensor
7430B
Pt100 cable sensor
7430C
Pt100 cable sensor
7440
Thermowell for PR 7400 Pt100 sensor
4510
Display / programming front
4511
Communication enabler
4512
Bluetooth communication enabler
4590
ConfigMate
3405
Power connector unit
9410
Power control unit
9421
Power supply
5910
CJC connector
5913
CJC connector
7007
2-digit digital potentiometer
7008
3-digit digital potentiometer
7009
10-turn potentiometer, 200 Ω
7011
Dial for 10-turn potentiometer
7012
1-turn potentiometer, 1 kΩ
7015
1-turn potentiometer, 10 kΩ
7020
Knob for 1-turn potentiometer
7020A
Knob for 10-turn potentiometer
7028
10-turn potentiometer, 2 kΩ
8510
8 unit 4511 Modbus cable
8511
4511 Y-splitter Modbus cable
8513
RJ45 Modbus termination
8514
3 X RJ45 female Y-splitter
8515
RJ45 female to female cable adapter
8516
RJ45 female to female shielded cable adapter
8517
3 x RJ45 female shielded Y-splitter
9400_1
Power rail 15 mm profile
9400_2
Power rail 7.5 mm profile
9402
Extra end covers for power rail