6334B
 

2-wire programmable transmitter

 

6334B

 

  • TC input
  • High measurement accuracy
  • Galvanic isolation
  • Can be installed in Ex zone 0
  • 1- or 2-channel version
  1. Overview + -

  2. Technical details + -

  3. Accessories + -


Application

  • Linearized temperature measurement with TC sensor.
  • Amplification of bipolar mV signals to a 4...20 mA signal, optionally linearized according to a defined linearization function.

Technical characteristics

  • Within a few seconds the user can program PR6334B to measure temperatures within all TC ranges defined by the norms.
  • Cold junction compensation (CJC) with a built-in temperature sensor.
  • A limit can be programmed on the output signal.
  • Continuous check of vital stored data for safety reasons.

Mounting / installation

  • Mounted vertically or horizontally on a DIN rail. Using the 2-channel version up to 84 channels can be mounted per meter.
  • The 6334B can be mounted in zone 0, 1, 2 and zone 20, 21, 22 including M1.

Data sheet & Manuals


Data sheet

Manuals

Manuals in Russian

Approvals & Certificates


ATEX certificate

IECEx certificate

EAC declaration

EAC Ex certificate

Metrology Pattern Approval (MPA), Belarus

Metrology Pattern Approval (MPA), Kazakhstan

Metrology Pattern Approval (MPA), Russia

Supplementary documentation


EU Declaration of Conformity

CCC statement

Environmental Conditions

Operating temperature -40°C to +85°C
Storage temperature -40°C to +85°C
Calibration temperature 20...28°C
Relative humidity < 95% RH (non-cond.)
Protection degree IP20

Mechanical specifications

Dimensions (HxWxD) 109 x 23.5 x 104 mm
Weight (1 / 2 channels) 145 / 185 g
DIN rail type DIN EN 60715/35 mm
Wire size 0.13...2.08 mm2 AWG 26...14 stranded wire
Screw terminal torque 0.5 Nm

Common specifications

Supply

Supply voltage 7.2...30 VDC
Max. required power ≤ 0.7 W/≤ 1.4 W (1 ch./2 ch.)
Power dissipation, per channel 0.17...0.7 W

Isolation voltage

Isolation voltage, test / working 1.5 kVAC / 50 VAC

Response time

Response time (programmable) 1...60 s
Voltage drop 7.2 VDC
Warm-up time 5 min.
Programming Loop Link
Signal / noise ratio Min. 60 dB
Accuracy Better than 0.05% of selected range
EEprom error check < 3.5 s
Signal dynamics, input 18 bit
Signal dynamics, output 16 bit
Effect of supply voltage change < 0.005% of span / VDC
EMC immunity influence < ±0.5% of span
Extended EMC immunity: NAMUR NE21, A criterion, burst < ±1% of span

Input specifications

Common input specifications

Max. offset 50% of selected max. value

TC input

Thermocouple type B, E, J, K, L, N, R, S, T, U, W3, W5, LR
Cold junction compensation (CJC) < ±1.0°C

Voltage input

Measurement range -12...150 mV
Min. measurement range (span) 5 mV
Input resistance 10 MΩ

Output specifications

Current output

Signal range 4…20 mA
Min. signal range 16 mA
Load (@ current output) ≤ (Vsupply - 7.2) / 0.023 [Ω]
Sensor error indication Programmable 3.5…23 mA
NAMUR NE43 Upscale/Downscale 23 mA / 3.5 mA

Common output specifications

Updating time 440 ms
of span = of the presently selected range

Observed authority requirements

EMC 2014/30/EU
ATEX 2014/34/EU
RoHS 2011/65/EU
EAC TR-CU 020/2011
EAC Ex TR-CU 012/2011

Approvals

ATEX KEMA 06ATEX0115 X
IECEx DEK 14.0047 X
EAC Ex RU C-DK.HA65.B.00355/19
 

Is this information helpful?

 

Rate us

Your request has been sent successfully. 0 items on your list
Your contact information
Please insert your last name
Please insert your last name
Please insert a valid email address
Please insert a valid phone number. Use only numbers.
Please insert your job title
Please insert your company name.
Please insert your company address
Please insert a valid zip code
Please insert a city
Please select country
Please read and agree with PR electronics’ Privacy Policy.
You have not added any products to your quote list
When browsing the website, you can add products to a quote list by simply clicking “Add to quote list" on the individual product pages. Once all relevant products are included, send the list to us and you will get a quotation within 24 hours. If you don't submit the list, it will be accessible on the website for 21 days. We hope you will find the functionality useful.
Thank you for requesting a quotation. We will get back to you by phone or email within 24 hours.

Need help?

If you need support, you are always welcome to contact us

Stay updated!

Register here to receive our newsletter