4114
Universal transmitter
- Input for RTD, TC, Ohm, potentiometer, mA and V
- 2-wire supply > 16 V
- FM-approved for installation in Div. 2
- Output for current and voltage
- Universal AC or DC supply
Advanced features
- Programmable by way of detachable display front (4501), process calibration, signal simulation, password protection, error diagnostics and help text available in several languages.
Application
- Linearized, electronic temperature measurement with RTD or TC sensor.
- Conversion of linear resistance variation to a standard analog current / voltage signal, i.e. from solenoids and butterfly valves or linear movements with attached potentiometer.
- Power supply and signal isolator for 2-wire transmitters.
- Process control with standard analog output.
- Galvanic separation of analog signals and measurement of floating signals.
- The 4114 is designed according to strict safety requirements and is therefore suitable for application in SIL 2 installations.
- Suitable for the use in systems up to Performance Level “d” according to ISO-13849.
Technical characteristics
- When 4114 is used with the 4501 display / programming front, all operational parameters can be modified to suit any application. As the 4114 is designed with electronic hardware switches, it is not necessary to open the device for setting of DIP-switches.
- A green / red front LED indicates normal operation and malfunction.
- Continuous check of vital stored data for safety reasons.
- 3-port 2.3 kVAC galvanic isolation.
Environmental Conditions
Operating temperature | -20°C to +60°C |
Storage temperature | -20°C to +85°C |
Calibration temperature | 20...28°C |
Relative humidity | < 95% RH (non-cond.) |
Protection degree | IP20 |
Mechanical specifications
Dimensions (HxWxD) | 109 x 23.5 x 104 mm |
Dimensions (HxWxD) w/ 4501/451x | 109 x 23.5 x 116 / 131 mm |
Weight approx. | 155 g |
Weight incl. 4501 / 451x (approx.) | 170 g / 185 g |
Wire size | 0.13...2.08 mm2 AWG 26...14 stranded wire |
Screw terminal torque | 0.5 Nm |
Vibration | IEC 60068-2-6 |
2...13.2 Hz | ±1 mm |
13.2...100 Hz | ±0.7 g |
Common specifications
Supply |
|
Supply voltage, universal | 21.6...253 VAC, 50...60 Hz or 19.2...300 VDC |
Fuse | 400 mA SB / 250 VAC |
Max. required power | ≤ 2.0 W |
Max. power dissipation | ≤ 2.0 W |
Isolation voltage |
|
Isolation voltage, test / working | 2.3 kVAC / 250 VAC |
Response time |
|
Temperature input (0...90%, 100...10%) | ≤ 1 s |
mA / V input (0...90%, 100...10%) | ≤ 400 ms |
Auxiliary supplies |
|
2-w. supply (term. 44...43) | 25...16 VDC / 0...20 mA |
Programming | PR 4500 communication interfaces |
Signal / noise ratio | Min. 60 dB (0...100 kHz) |
Accuracy | Better than 0.1% of sel. range |
EMC immunity influence | < ±0.5% of span |
Extended EMC immunity: NAMUR NE21, A criterion, burst | < ±1% of span |
Input specifications
RTD input |
|
RTD type | Pt10/20/50/100/200/250; Pt300/400/500/1000; Ni50/100/120/1000; Cu10/20/50/100 |
Cable resistance per wire | 50 Ω (max.) |
Sensor current | Nom. 0.2 mA |
Effect of sensor cable resistance (3-/4-wire) | < 0.002 Ω / Ω |
Sensor error detection | Yes |
Short circuit detection | < 15 Ω |
Linear resistance input |
|
Linear resistance min....max. | 0 Ω...10000 Ω |
Potentiometer input |
|
Potentiometer min....max. | 10 Ω...100 kΩ |
TC input |
|
Thermocouple type | B, E, J, K, L, N, R, S, T, U, W3, W5, LR |
Cold junction compensation (CJC) via ext. sensor in 5910 | 20...28°C ≤ ±1°C, -20...20°C / 28...70°C ≤ 2°C |
CJC via int. mounted sensor | ±(2.0°C + 0.4°C * Δt) |
Sensor error detection | Yes |
Sensor error current: When detecting / else | Nom. 2 μA / 0 μA |
Current input |
|
Measurement range | 0...23 mA |
Programmable measurement ranges | 0...20 and 4...20 mA |
Input resistance | Nom. 20 Ω + PTC 50 Ω |
Sensor error detection: Loop break 4...20 mA | Yes |
Voltage input |
|
Measurement range | 0...12 VDC |
Programmable measurement ranges | 0/0.2...1, 0/1...5, 0/2...10 VDC |
Input resistance | Nom. 10 MΩ |
Output specifications
Current output |
|
Signal range | 0...23 mA |
Programmable signal ranges | 0...20/4...20/20...0/20...4 mA |
Load (@ current output) | ≤ 800 Ω |
Load stability | ≤ 0.01% of span / 100 Ω |
Sensor error indication | 0 / 3.5 / 23 mA / none |
NAMUR NE43 Upscale/Downscale | 23 mA / 3.5 mA |
Output limitation, on 4...20 and 20...4 mA signals | 3.8...20.5 mA |
Output limitation, on 0...20 and 20...0 mA signals | 0...20.5 mA |
Current limit | ≤ 28 mA |
Voltage output |
|
Signal range | 0...10 VDC |
Programmable signal ranges | 0/0.2...1; 0/1...5 ; 0/2...10; 1...0.2/0; 5...1/0; 10...2/0 V |
Load (@ voltage output) | ≥ 500 kΩ |
of span | = of the currently selected measurement range |
Observed authority requirements
EMC | 2014/30/EU |
LVD | 2014/35/EU |
RoHS | 2011/65/EU |
EAC | TR-CU 020/2011 |
EAC LVD | TR-CU 004/2011 |
Approvals
c UL us, UL 508 | E231911 |
FM | 3025177 |
DNV Marine | TAA0000101 |
EU RO MR Type Approval | MRA000000Z |
SIL | Hardware assessed for use in SIL applications |

7423
Ceramic socket for Pt100 sensor
7430B
Pt100 cable sensor
7430C
Pt100 cable sensor
7440
Thermowell for PR 7400 Pt100 sensor
4501
Display / programming front
4511
Communication enabler
4512
Bluetooth communication enabler
4590
ConfigMate
5910
CJC connector
7007
2-digit digital potentiometer
7008
3-digit digital potentiometer
7009
10-turn potentiometer, 200 Ω
7010
10-turn potentiometer, 20 kΩ
7011
Dial for 10-turn potentiometer
7012
1-turn potentiometer, 1 kΩ
7015
1-turn potentiometer, 10 kΩ
7016
1-turn potentiometer, 100 kΩ
7020
Knob for 1-turn potentiometer
7020A
Knob for 10-turn potentiometer
7028
10-turn potentiometer, 2 kΩ
8510
8 unit 4511 Modbus cable
8511
4511 Y-splitter Modbus cable
8513
RJ45 Modbus termination
8514
3 X RJ45 female Y-splitter
8515
RJ45 female to female cable adapter
8516
RJ45 female to female shielded cable adabter