Overview
+
Technical details
+
Accessories
+
Application
The 3111 temperature converter measures standard TC J and K temperature sensors, and provides an isolated analog voltage or current output.
High 3 port isolation provides surge suppression and protects the control system from transients and noise.
The 3111 can be mounted in the safe area or in Zone 2 / Division 2 areas.
Approved for marine applications.
Technical characteristics
Flexibly powered by 24 VDC (±30%) via power rail or connectors.
< 30 ms fast response time with simultaneous sensor error detection when selected.
Selectable 300 ms response time when signal dampening is needed.
Selectable internal/external CJC.
Excellent conversion accuracy in all available ranges, better than 0.05% of span.
Meeting the NAMUR NE21 recommendations, the 3111 provides top measurement performance in harsh EMC environments.
The device meets the NAMUR NE43 standard defining out of range and sensor error output values.
A visible green LED indicates operational status of the unit and the input sensor.
All terminals are protected against overvoltage and polarity error.
High galvanic isolation of 2.5 kVAC.
Excellent signal/noise ratio of > 60 dB.
Mounting / installation / programming
Selectable DIP-settings for easy configuration of more than 1000 factory calibrated measurement ranges.
The narrow 6 mm housing allows up to 165 units to be mounted per meter of DIN rail, without any air gap between units.
Wide ambient temperature range of -25...+70°C.
DNV-GL marine certificate
Metrology Pattern Approval (MPA)
Environmental Conditions
Operating temperature
-25°C to +70°C
Storage temperature
-40°C to +85°C
Calibration temperature
20...28°C
Relative humidity
< 95% RH (non-cond.)
Protection degree
IP20
Installation in
Pollution degree 2 & meas. / overvoltage cat. II
Mechanical specifications
Dimensions (HxWxD)
113 x 6.1 x 115 mm
Weight approx.
70 g
DIN rail type
DIN EN 60715/35 mm
Wire size
0.13...2.5 mm2 / AWG 26...12 stranded wire
Screw terminal torque
0.5 Nm
Vibration
IEC 60068-2-6
2...25 Hz
±1.6 mm
25...100 Hz
±4 g
Common specifications
Supply voltage
16.8...31.2 VDC
Max. required power
0.70 W
Max. power dissipation
0.70 W
Isolation voltage, test / working
2.5 kVAC / 300 VAC (reinforced)
Zone 2 / Div. 2
250 VAC
Response time (0...90%, 100...10%)
< 30 ms / 300 ms (selectable)
Signal / noise ratio
Min. 60 dB
Programming
DIP-switches
Signal dynamics, input
23 bit
Signal dynamics, output
18 bit
Accuracy
Better than 0.05% of selected range
EMC immunity influence
< ±0.5% of span
Extended EMC immunity: NAMUR NE21, A criterion, burst
< ±1% of span
Incorrect DIP-switch setting identification
0 V / 0 mA output; LED 0.5 s / 1 Hz
Input specifications
Temperature range, TC J
-100...+1200°C
Temperature range, TC K
-180...+1372°C
Min. measurement range (span) - TC J & K
50°C
Accuracy: the greater of
Better than 0.05% of span or 0.5°C
Temperature coefficient: the greater of
0.1°C/°C or ≤ ±0.01%/°C
Sensor cable resistance
< 5 kΩ per wire
Cold junction compensation (CJC): Accuracy @ external Pt100 input
Better than ±0.15°C
Cold junction compensation (CJC): Accuracy @ internal CJC
Better than ±2.5°C
Internal CJC error detection
Yes
External CJC error detection
Yes - selectable via DIP-switch
Open Thermocouple detection
Yes - selectable via DIP-switch
Output specifications
Updating time
10 ms
Signal range
0...23 mA
Programmable signal ranges
0 / 4...20 mA
Sensor error indication (0...20 mA)
0 mA or 23 mA / OFF
Sensor error indication (4...20 mA)
3.5 mA or 23 mA / acc. to NAMUR NE43 or OFF
Load (@ current output)
≤ 600 Ω
Load stability
≤ 0.01% of span / 100 Ω
Current limitation @ low output load
< 60 mA peak / < 4 mA average
Programmable signal ranges
0/1...5 and 0/2...10 V
Sensor error indication
0 V / 10% above the max. / none
Open output
< 18 V
I.S. / Ex marking
ATEX
II 3 G Ex nA IIC T4 Gc
IECEx
Ex nA IIC T4 Gc
FM, US
Cl. I, Div. 2, Gp. A, B, C, D T4 or Cl. I, Zone 2, AEx nA IIC T4
FM, CA
Cl. I, Div. 2, Gp. A, B, C, D T4 or Cl. I, Zone 2, Ex nA IIC T4
EAC Ex
2Ex nA IIC T4 Gc X
Observed authority requirements
EMC
2014/30/EU
LVD
2014/35/EU
ATEX
2014/34/EU
RoHS
2011/65/EU
EAC
TR-CU 020/2011
EAC Ex
TR-CU 012/2011
Approvals
ATEX
KEMA 10ATEX0147 X
IECEx
KEM 10.0068X
c FM us
FM17US0004X / FM17CA0003X
UL
UL 61010-1
DNV-GL Marine
TAA00001RW
EAC Ex
RU C-DK.HA65.B.00355/19
Is this information helpful?