Programmable transmitter
PR 5116A
- Input for RTD, TC, mV, Ohm, potentiometer, mA and V
- 2-wire supply > 16.5 V
- Bipolar voltage input
- Output for current, voltage and 2 relays
- Universal supply by AC or DC
Application
- Linearized, electronic temperature measurement with RTD or TC sensor.
- Conversion of linear resistance variation to a standard analog current / voltage signal, i.e. from solenoids and butterfly valves or linear movements with attached potentiometer.
- Power supply and signal isolator for 2-wire transmitters.
- Process control with 2 potential-free relay contacts which can be configured for advanced functions.
- Galvanic separation of analog signals and measurement of floating signals.
Technical characteristics
- Within a few seconds the user can program PR5116A to suit the specific application.
- By way of the front push-button the input can be calibrated to the exact span of the process. Zero drift on the process signal can be adjusted by a single press of the front buttton.
- A green front LED indicates normal operation and malfunction. A yellow LED is ON for each active output relay.
- Continuous check of vital stored data for safety reasons.
- 3-port 3.75 kVAC galvanic isolation.
Mounting / installation
- Mounted vertically or horizontally on a DIN rail. As the devices can be mounted without any distance between neighboring units, up to 42 devices can be mounted per meter.
Data sheet & Manuals
Data sheet
- 5116A.pdf
- Latest version
Manuals
- 5116V108_UK.pdf
- 5116V107_UK.pdf
- 5116V106_UK.pdf
- 5116V105_UK.pdf
- 5116V104_UK.pdf
- 5116V103_UK.pdf
- 5116V102.pdf
- 5116V101.pdf
- Previous versions
- Latest version
Manuals in Russian
- 5116V108_RU.pdf
- 5116V107_RU.pdf
- 5116V106_RU.pdf
- 5116V105_RU.pdf
- 5116V104_RU.pdf
- 5116V103_RU.pdf
- Previous versions
- Latest version
Supplementary documentation
EU Declaration of Conformity
- 5116DoC_EU_105_UK.pdf
- 5116DoC_EU_104_UK.pdf
- 5116DoC_EU_103_UK.pdf
- 5116DoC_EU_102_UK.pdf
- 5116DoC_EU_101_UK.pdf
- 5116DoC_EU_100_UK.pdf
- Previous versions
- Latest version
PR default configurations
- PR_default_configurations.pdf
- Latest version
Safety note
Safety note
Approvals & Certificates
UL certificate
- 5116A_B_UL.pdf
- Latest version
DNV marine certificate
- DNV_2231_41xx_51xx_53xx.pdf
- Latest version
EAC declaration
- EAC-Declaration.pdf
- Latest version
EAC LVD declaration
- EAC_LVD-Declaration.pdf
- Latest version
Metrology Pattern Approval (MPA), Russia
- MPA_Russia.pdf
- Latest version
Order form
Environmental Conditions
Operating temperature | -20°C to +60°C |
Calibration temperature | 20...28°C |
Relative humidity | < 95% RH (non-cond.) |
Protection degree | IP20 |
Mechanical specifications
Dimensions (HxWxD) | 109 x 23.5 x 130 mm |
Weight approx. | 225 g |
DIN rail type | DIN EN 60715/35 mm |
Wire size | 0.13...2.08 mm2 AWG 26...14 stranded wire |
Screw terminal torque | 0.5 Nm |
Vibration | IEC 60068-2-6 |
2...13.2 Hz | ±1 mm |
13.2...100 Hz | ±0.7 g |
Common specifications
Supply |
|
Supply voltage, universal | 21.6...253 VAC, 50...60 Hz or 19.2...300 VDC |
Fuse | 400 mA SB / 250 VAC |
Max. required power | 2.4 W |
Max. power dissipation | ≤ 2.0 W |
Isolation voltage |
|
Isolation voltage, test / working | 3.75 kVAC / 250 VAC |
PELV/SELV | IEC 61140 |
Response time |
|
Temperature input, programmable (0...90%, 100...10%) | 400 ms...60 s |
mA / V input (programmable) | 250 ms...60 s |
Auxiliary supplies |
|
2-wire supply (pin 54...52) | 28...16.5 VDC / 0...20 mA |
Programming | PR 5909 Loop Link communications interface |
Signal / noise ratio | Min. 60 dB (0...100 kHz) |
Accuracy | Better than 0.05% of selected range |
Signal dynamics, input | 22 bit |
Signal dynamics, output | 16 bit |
Auxiliary voltages: Reference voltage | 2.5 VDC ±0.5% / 15 mA |
EMC immunity influence | < ±0.5% of span |
Extended EMC immunity: NAMUR NE21, A criterion, burst | < ±1% of span |
Input specifications
Common input specifications |
|
Max. offset | 50% of selected max. value |
RTD input |
|
RTD type | Pt46, Pt100, Ni100, Cu53, lin. R |
Cable resistance per wire | 10 Ω (max. 50 Ω) |
Sensor current | Nom. 0.2 mA |
Effect of sensor cable resistance (3-/4-wire) | < 0.002 Ω / Ω |
Sensor error detection | Yes |
TC input |
|
Thermocouple type | B, E, J, K, L, N, R, S, T, U, W3, W5, LR |
Cold junction compensation (CJC) | < ±1.0°C |
Sensor error current | Nom. 30 μA |
Sensor error detection | Yes |
Current input |
|
Measurement range | 0...100 mA |
Min. measurement range (span) | 4 mA |
Input resistance: Supplied unit | Nom. 10 Ω + PTC 10 Ω |
Input resistance: Non-supplied unit | RSHUNT = ∞, VDROP < 6 V |
Sensor error detection | Loop break 4...20 mA |
Voltage input |
|
Measurement range |
0...250 VDC
-2500...+2500 mV |
Min. measurement range (span) | 5 mV |
Input resistance |
Nom. 10 MΩ (≤ 2.5 VDC)
Nom. 5 MΩ (> 2.5 VDC) > 5 MΩ (mV input) |
Potentiometer via 2.5 V ref. | 170 Ω |
Output specifications
Current output |
|
Signal range | 0...20 mA |
Min. signal range | 10 mA |
Load (@ current output) | ≤ 600 Ω |
Load stability | ≤ 0.01% of span / 100 Ω |
Current limit | ≤ 28 mA |
Sensor error indication | Programmable 0...23 mA |
NAMUR NE43 Upscale/Downscale | 23 mA / 3.5 mA |
Passive 2-wire mA output |
|
Signal range | 4...20 mA |
Load stability | ≤ 0.01% of span / 100 Ω |
Max. external 2-wire supply | 29 VDC |
Effect of external 2-wire supply voltage variation | < 0.005% of span / V |
Voltage output |
|
Signal range | 0...10 VDC |
Min. signal range | 500 mV |
Load (@ voltage output) | ≥ 500 kΩ |
Relay output |
|
Relay functions |
Increasing / decreasing
Window |
Max. voltage | 250 VAC / VDC |
Max. current | 2 A |
Max. AC power | 500 VA |
Max. DC current, resistive load > 30 VDC | See manual for details |
Sensor error reaction | Break / Make / Hold / None |
of span | = of the presently selected range |
Observed authority requirements
EMC | 2014/30/EU |
LVD | 2014/35/EU |
RoHS | 2011/65/EU |
EAC | TR-CU 020/2011 |
EAC LVD | TR-CU 004/2011 |
Approvals
c UL us, UL 508 | E231911 |
DNV Marine | TAA0000101 |
Do you need help choosing the right device?Our sales engineers are ready to guide you to the device that best fits your application. How to contact us?You can use our quote function or contact form with no obligation. With the quote function, you simply add the devices you are interested in and receive a quote. We will get back to you within 24 hours on business days.
After you orderWhen your order is placed, you will receive a confirmed delivery date within two business days. As soon as your package has been shipped, you will receive an email with tracking details, so you always know where your delivery is. |
![]() |
State-of-the-art manufacturing Our 8,500 sqm integrated and automated manufacturing campus in Denmark covers the entire value-chain from design and development to manufacturing. It allows us to design and optimize for testing and manufacturing thereby constantly driving quality up and costs down. |
![]() |
Dedicated Presale / Aftersales
|
![]() |
Product reliability |
![]() |
Product deployment
|
![]() |
Smart products |