4116
 

Universal transmitter

 

4116

 

  • Input for RTD, TC, Ohm, potentiometer, mA and V
  • 2-wire supply > 16 V
  • FM-approved for installation in Div. 2
  • Output for current, voltage and 2 relays
  • Universal AC or DC supply
  1. Overview + -

  2. Technical details + -

  3. Accessories + -


Application

  • Linearized, electronic temperature measurement with RTD or TC sensor.
  • Conversion of linear resistance variation to a standard analog current / voltage signal, i.e. from solenoids and butterfly valves or linear movements with attached potentiometer.
  • Power supply and signal isolator for 2-wire transmitters.
  • Process control with 2 pairs of potential-free relay contacts and analog output.
  • Galvanic separation of analog signals and measurement of floating signals.
  • The 4116 is designed according to strict safety requirements and is therefore suitable for application in SIL 2 installations.
  • Suitable for the use in systems up to Performance Level “d” according to ISO-13849.

Technical characteristics

  • When 4116 is used in combination with the 45xx display / programming units, all operational parameters can be modified to suit any application. As the 4116 is designed with electronic hardware switches, it is not necessary to open the device for setting of DIP-switches.
  • A green / red front LED indicates normal operation and malfunction. A yellow LED is ON for each active output relay.
  • Continuous check of vital stored data for safety reasons.
  • 4-port 2.3 kVAC galvanic isolation.

Mounting / installation / programming

  • Very low power consumption means units can be mounted side by side without an air gap – even at 60°C ambient temperature.
  • Configuration, monitoring, 2-point process calibration and more are accomplished using PR's 45xx detachable displays.
  • All programming can be password-protected.

Data sheet & Manuals


Data sheet

Manuals

Manuals in Russian

Supplementary documentation


EU Declaration of Conformity

Modbus configuration manual

FMEDA report

ISO 13849 declaration

EMC data

Approvals & Certificates


FM certificate

SIL certificate

UL certificate

DNV marine certificate

DNV EU-RO marine approval

EAC declaration

EAC LVD declaration

Metrology Pattern Approval (MPA)

Environmental Conditions

Operating temperature -20°C to +60°C
Storage temperature -20°C to +85°C
Calibration temperature 20...28°C
Relative humidity < 95% RH (non-cond.)
Protection degree IP20

Mechanical specifications

Dimensions (HxWxD) 109 x 23.5 x 104 mm
Dimensions (HxWxD) w/ 4501/451x 109 x 23.5 x 116 / 131 mm
Weight approx. 175 g
Weight incl. 4501 / 451x (approx.) 190 g / 205 g
Wire size 0.13...2.08 mm2 AWG 26...14 stranded wire
Screw terminal torque 0.5 Nm
Vibration IEC 60068-2-6
2...13.2 Hz ±1 mm
13.2...100 Hz ±0.7 g

Common specifications

Supply

Supply voltage, universal 21.6...253 VAC, 50...60 Hz or 19.2...300 VDC
Fuse 400 mA SB / 250 VAC
Max. required power ≤ 2.5 W
Max. power dissipation ≤ 2.5 W

Isolation voltage

Test voltage 2.3 kVAC
Working voltage 250 VAC (reinforced) / 500 VAC (basic)

Response time

Temperature input (0...90%, 100...10%) ≤ 1 s
mA / V input (0...90%, 100...10%) ≤ 400 ms

Auxiliary supplies

2-w. supply (term. 44...43) 25...16 VDC / 0...20 mA
Programming PR 4500 communication interfaces
Signal dynamics, input 24 bit
Signal dynamics, output 16 bit
Signal / noise ratio Min. 60 dB (0...100 kHz)
Accuracy Better than 0.1% of sel. range
EMC immunity influence < ±0.5% of span
Extended EMC immunity: NAMUR NE21, A criterion, burst < ±1% of span

Input specifications

RTD input

RTD type Pt10/20/50/100/200/250; Pt300/400/500/1000; Ni50/100/120/1000; Cu10/20/50/100
Cable resistance per wire 50 Ω (max.)
Sensor current Nom. 0.2 mA
Effect of sensor cable resistance (3-/4-wire) < 0.002 Ω / Ω
Sensor error detection Yes
Short circuit detection < 15 Ω

Linear resistance input

Linear resistance min....max. 0 Ω...10000 Ω

Potentiometer input

Potentiometer min....max. 10 Ω...100 kΩ

TC input

Thermocouple type B, E, J, K, L, N, R, S, T, U, W3, W5, LR
Cold junction compensation (CJC) via ext. sensor in 5910 20...28°C ≤ ±1°C, -20...20°C / 28...70°C ≤ 2°C
CJC via int. mounted sensor ±(2.0°C + 0.4°C * Δt)
Sensor error detection Yes
Sensor error current: When detecting / else Nom. 2 μA / 0 μA

Current input

Measurement range 0...23 mA
Programmable measurement ranges 0...20 and 4...20 mA
Input resistance Nom. 20 Ω + PTC 50 Ω
Sensor error detection: Loop break 4...20 mA Yes

Voltage input

Measurement range 0...12 VDC
Programmable measurement ranges 0/0.2...1, 0/1...5, 0/2...10 VDC
Input resistance Nom. 10 MΩ

Output specifications

Current output

Signal range 0...23 mA
Programmable signal ranges 0...20/4...20/20...0/20...4 mA
Load (@ current output) ≤ 800 Ω
Load stability ≤ 0.01% of span / 100 Ω
Sensor error indication 0 / 3.5 / 23 mA / none
NAMUR NE43 Upscale/Downscale 23 mA / 3.5 mA
Output limitation, on 4...20 and 20...4 mA signals 3.8...20.5 mA
Output limitation, on 0...20 and 20...0 mA signals 0...20.5 mA
Current limit ≤ 28 mA

Voltage output

Signal range 0...10 VDC
Programmable signal ranges 0/0.2...1; 0/1...5 ; 0/2...10; 1...0.2/0; 5...1/0; 10...2/0 V
Load (@ voltage output) ≥ 500 kΩ

Relay output

Relay functions Setpoint, Window, Sensor error, Latch, Power and Off
Max. voltage 250 VAC / VDC
Max. current 2 A
Max. AC power 500 VA
Max. DC current, resistive load > 30 VDC See manual for details

Observed authority requirements

EMC 2014/30/EU
LVD 2014/35/EU
RoHS 2011/65/EU
EAC TR-CU 020/2011

Approvals

c UL us, UL 508 E231911
FM 3025177
DNV Marine TAA0000101
EU RO MR Type Approval MRA000000Z
SIL Hardware assessed for use in SIL applications
 

Is this information helpful?

 

Rate us

Your request has been sent successfully. 0 items on your list
Your contact information
Please insert your last name
Please insert your last name
Please insert a valid email address
Please insert a valid phone number. Use only numbers.
Please insert your job title
Please insert your company name.
Please insert your company address
Please insert a valid zip code
Please insert a city
Please select country
Please read and agree with PR electronics’ Privacy Policy.
You have not added any products to your quote list
When browsing the website, you can add products to a quote list by simply clicking “Add to quote list" on the individual product pages. Once all relevant products are included, send the list to us and you will get a quotation within 24 hours. If you don't submit the list, it will be accessible on the website for 21 days. We hope you will find the functionality useful.
Thank you for requesting a quotation. We will get back to you by phone or email within 24 hours.

Need help?

If you need support, you are always welcome to contact us

Stay updated!

Register here to receive our newsletter